FUNCTION DESCRIPTION 

During device start-up the version and type number are displayed on the start screen for a short time. 

While the fan coil thermostat is communicating via the bus, the communication symbol 

starts flashing. If the device does not communicate 

via the bus, the symbol will be disappear after 10 seconds. 

Parameter table 

To enter the parameter table, press the “Mode” + “arrow upwards” Key for more than 3s. Once the Display comes on, it will prompt for the password 

(default 987). The password can be entered digit by digit. Eac

h digit can be increased / decreased using the “▲”or “▼” keys. With the “Mode Key” 

the next digit will be selected.  

Each parameter can be increased / decreased using the “▲”or “▼” keys. With the “Mode Key”

 the display will move on to the next parameter. 

Once the end of the table is reached the parameter setting will be exited to normal operation. 

No. 

Name of parameter 

Parameter definition 

Factory default 

Modbus address 

ID.1- ID.247 

Baud rate 

1:4800bps,2:9600,3:19200,4:38400 

Parity 

0:none

1:odd  2:even 

Stop Bits 

1 = 1 Stopbit; 2, = 2 Stopbits 

Temperature Offset  

Internal Sensor

 

-5,0 K..+5,0 K 

Temperature Offset 

External Sensor

 

-5,0 K..+5,0 K 

Screensaver mode 

0- display button on / off 

1-room temperature and button button on / off 

2- display clock, room temperature and button on / off 

3- display clock, room temperature / button on / off and set point 

4- display all status 

7day 4periods 

programmable 

0=deactivated 1=activated 

Password 

0..999 

987 

10 

Reset to Factory Settings 

Setting Parameter to 1 and press the Mode Key resets the device to 

factory settings. Device stays in Parameter menu for Modbus 

configuration 

11 

reserved 

reserved 

 

The Fancoil controller is designed for fan coil units with 2- or 4-pipe systems for heating and cooling.  

PI-controller 0..10 V 

The manipulated variable is output as a proportional control signal. The type of valve used is set via the configuration registers. 

6WV 

With register address 304, a 6-way valve can also be selected as valve type. You can choose from 2..10 V / 2..10 V INV (Belimo), 0..10 V DN15 / 

DN15 INV, DN20 / DN20 INV (Sauter). 

Electric heater 

The relay contacts 6 and 7 can be used to connect a heating coil with up to 3 stages. With the registers 301 to 303, the switching thresholds of the 

respective stages can be set. 

 

 

Summary of Contents for LCF02 Touch 3AO2DO

Page 1: ...should only be used for the intended application Unauthorised modifications are prohibited The product must not be used in relation with any equipment that in case of a failure may threaten directly...

Page 2: ...ture acceptance of the wall or the longer the selected inquiry interval of the temperature sensor is the smaller the deviations limited in time are TECHNICAL DATA Measuring values temperature Output v...

Page 3: ...voltage supply it is to be ensured that all positive operating voltage input terminals of the field devices are connected with each other and all negative operating voltage input terminals reference...

Page 4: ...22 Heating valve 29 Off delay active 2 Schedular 9 Fan coil type 16 Set fan speed 23 Valve opening 30 Key locked 3 Room temperature 10 Auto mode 17 Power ON OFF 24 Dew point 31 Eco Mode active 4 Setp...

Page 5: ...ID 247 1 2 Baud rate 1 4800bps 2 9600 3 19200 4 38400 2 3 Parity 0 none 1 odd 2 even 0 4 Stop Bits 1 1 Stopbit 2 2 Stopbits 2 5 Temperature Offset Internal Sensor 5 0 K 5 0 K 0 6 Temperature Offset E...

Page 6: ...114 The display will show the average of both ECO Setpoint Temperatures 25 18 2 21 5 and the leaf symbol to indicate the ECO mode In ECO mode the setpoint is fixed and the device does not react to any...

Page 7: ...switched OFF Switch thermostat to last state before power failure Record and Memorize Turn the thermostat ON Storage during power loss The status will be kept in EEPROM while the power failure so no...

Page 8: ...ture sensor alarm 0x02 external temperature sensor high limit Alarm 0x04 external temperature sensor low limit Alarm 0x08 change over sensor missing alarm 10 0x000A Read only External input 1 0 Contac...

Page 9: ...symbol shall be displayed and blink twice 0 270 0x010E Read write Display Settings 0b00000001 show Setpoint if no setpoint is shown the setpoint keys are locked 0x010D 0x10 lock temp setting 0b000000...

Page 10: ...tion modes 0b00000000 none fan key is locked and the fan symbol will not be displayed 0bxxxx0001 single stage 0bxxxx0010 2 stages 0bxxxx0011 3 stages 0bxxxx1000 EC Fan 0b0001xxxx fan works not in heat...

Page 11: ...Occupied 2 Occupancy sensor Closed Occupied 3 Window contact Open Window Open 4 Window contact Closed Window Open 5 Disable heating Open Heating disabled 6 Disable heating Closed Heating Disabled 7 D...

Page 12: ...nnel A period 1 Start time minute 0 59m min 0 406 0x0196 Read write Time channel A period 1 Set point 0 500 0 50 0 C 0 1 C F 210 407 0x0197 Read write Time channel A period 1 ECO mode 0b00000001 Comfo...

Page 13: ...ute 0 59m min 0 431 0x01AF Read write Time channel B period 3 Set point 0 500 0 50 0 C 0 1 C F 210 432 0x01B0 Read write Time channel B period 3 ECO mode NC 0 433 0x01B1 Read write Time channel B peri...

Page 14: ...0bxABC1234 with binary value 1 for active channel i e 0x01000100 A 2 0 464 0x01D0 Read write Make next day s holiday 0bxxx00000 None 0bxxx00001 0bxxx11111 days of holidays next n days starting next 0...

Page 15: ...0 ventilating PI loop controls fan stages only valves closed HMI mode 0b1xxx xxxx HMI Mode controller OFF 0b1xxx xx01 show symbol ventilating 0b1xxx xx10 show symbol heating 0b1xxx xx11 show symbol co...

Reviews: