0x1x = EC Fan Auto Mode, stage according control
variable 0x0204 & fan stage thresholds 0x124..129
513
0x0201
Read-write
setpoint temperature
0..500 = 0..+50,0 °C
0
514
0x0202
Read-write
Controller mode Comfort :
0b0000 0000=controller off
(Frost protection active)
0b0000 0001=controller auto mode
(heating&cooling)
0b0000 0010=controller heating mode only
0b0000 0011=controller cooling mode only
0b0000 0100=ventilating
(PI loop controls fan stages
only, valves closed)
1
Controller mode ECO:
0b0001 0000=controller off
(Frost protection active)
0b0001 0001=controller auto mode
(heating&cooling)
0b0001 0010=controller heating mode only
0b0001 0011=controller cooling mode only
0b0001 0100=ventilating
(PI loop controls fan stages
only, valves closed)
HMI mode
0b1xxx xxxx = HMI Mode, controller OFF
0b1xxx xx01 = show symbol "ventilating"
0b1xxx xx10 = show symbol "heating"
0b1xxx xx11 = show symbol "cooling"
0b1xxx x1xx = show symbol " AUTO mode"
0b1xxx x110 = show "AUTO + heating" symbol
0b1xxx x111 = show "AUTO + cooling" symbol
0b1xxx x101 = show "AUTO + ventilating" symbol
0b1xxx 1xxx = reserved
515
0x0203
Read-write
Active Symbols
0x00= show none
0x01= show Leaf
0x02= show dew point
0x04= show frost protect ON
0x08= show open window
0x10= show Attention!
0x20= show hourglass
0x40= show lock
0x80= show ECO
0
516
0x0204
Read-write
Control Variable Y% (HMI Mode)
0-100%
If output is 2-point, output will be ON for control
variable >5%
0.1
%
0
517
0x0205
Read-write
Room temperature on LCD (HMI Mode)
0..500 = 0..+50,0 °C
0.1
%
0
»