REMARKS TO ROOM SENSORS 

Location and Accuracy of Room Sensors 

The room sensor should be mounted  in a suitable location for measuring accurate room temperature. The accuracy of the temperature 

measurement also depends directly on the temperature dynamics of the wall. It is important, that the back plate is completely flush to the wall so 

that there is sufficient circulation of air through the vents in the cover, otherwise, deviations in temperature measurement will occur due to 

uncontrolled air circulation. The temperature sensor should not be covered by furniture or other objects. Mounting next to doors (due to draught) 

or windows (due to colder outside wall) should be avoided. 

Surface and Flush Mounting 

The measuring result is influenced by the thermal characteristics of the wall. A solid concrete wall responds to thermal fluctuations within a room 

in a much slower than a light-weight structure wall. Room temperature sensors installed in flush-mounted boxes have a longer response time to 

thermal variations. In extreme cases they detect the radiant heat of the wall even if the air temperature in the room is lower for example. The 

quicker the dynamics of the wall (temperature acceptance of the wall) or the longer the selected inquiry interval of the temperature sensor is the 

smaller the deviations limited in time are. 

» 

TECHNICAL DATA 

Measuring values 

temperature 

Output voltage 

terminal 2 | 3

 (for heating and cooling) 

2x 0..10 V

, min. load 10 kΩ

 

terminal 4

 (for fan)

 

1x 0..10 V, 

min. load 10 kΩ

 

Output switch contact 

terminal 6 | 7 

(electrical heater 3-stage) 

2x normally open contact, 

max. 250 V ~ / 3 A | max. 30 V = / 3 A 

Network technology 

RS485 Modbus, RTU, half-duplex, baud rate 4.800, 9.600, 19.200 or 38.400, parity: non (2 stopbits), even 

or odd (1 stopbit) 

Power supply 

24 V = (±10%) | 24 V ~ (±20%) SELV 

Power consumption 

3 W (24 V =) 

Measuring range temp. 

+1..+50 °C 

Accuracy temperature 

±1 K (typ. at 21 °C) 

Inputs 

terminal 10

  

input for external sensor 

NTC10K 

terminal 11 – ESI | DP

 

input digital for floating contact,  

window contact, dew point 

sensor 

terminal 12 - OCC

 

input digital for floating contact,  

occupancy sensor, key card 

switch 

 

Control functions 

set point adju1..+50 °C, (d16..+30 °C) 

Display 

LCD 64x41 mm, white or black background lighting 

Enclosure 

ABS, pure white or black 

Protection 

IP20 according to EN 60529 

Cable entry 

rear entry 

Connection electrical 

terminal block max. 1,5 mm² 

Ambient condition 

-10..+50 °C, max. 95% rH non-condensing 

Mounting 

flush mounted with standard EU box (Ø=60 mm) 

Communication Modbus 

Communication-section 

1..247  Factory default: 1 

Communication-Interface 

RS485   

Communication-Protocol 

Modbus-RTU   

Baud Rate 

4800 bps / 9600 bps / 19200 bps / 38400 bps (optional)  Factory default: 9600bps 

Parity 

no parity / odd parity / straight parity (optional)  Factory default: no parity 

Data: 

8 bit   

Stop 

2 bit   

 

 

Summary of Contents for LCF02 Touch 3AO2DO

Page 1: ...should only be used for the intended application Unauthorised modifications are prohibited The product must not be used in relation with any equipment that in case of a failure may threaten directly...

Page 2: ...ture acceptance of the wall or the longer the selected inquiry interval of the temperature sensor is the smaller the deviations limited in time are TECHNICAL DATA Measuring values temperature Output v...

Page 3: ...voltage supply it is to be ensured that all positive operating voltage input terminals of the field devices are connected with each other and all negative operating voltage input terminals reference...

Page 4: ...22 Heating valve 29 Off delay active 2 Schedular 9 Fan coil type 16 Set fan speed 23 Valve opening 30 Key locked 3 Room temperature 10 Auto mode 17 Power ON OFF 24 Dew point 31 Eco Mode active 4 Setp...

Page 5: ...ID 247 1 2 Baud rate 1 4800bps 2 9600 3 19200 4 38400 2 3 Parity 0 none 1 odd 2 even 0 4 Stop Bits 1 1 Stopbit 2 2 Stopbits 2 5 Temperature Offset Internal Sensor 5 0 K 5 0 K 0 6 Temperature Offset E...

Page 6: ...114 The display will show the average of both ECO Setpoint Temperatures 25 18 2 21 5 and the leaf symbol to indicate the ECO mode In ECO mode the setpoint is fixed and the device does not react to any...

Page 7: ...switched OFF Switch thermostat to last state before power failure Record and Memorize Turn the thermostat ON Storage during power loss The status will be kept in EEPROM while the power failure so no...

Page 8: ...ture sensor alarm 0x02 external temperature sensor high limit Alarm 0x04 external temperature sensor low limit Alarm 0x08 change over sensor missing alarm 10 0x000A Read only External input 1 0 Contac...

Page 9: ...symbol shall be displayed and blink twice 0 270 0x010E Read write Display Settings 0b00000001 show Setpoint if no setpoint is shown the setpoint keys are locked 0x010D 0x10 lock temp setting 0b000000...

Page 10: ...tion modes 0b00000000 none fan key is locked and the fan symbol will not be displayed 0bxxxx0001 single stage 0bxxxx0010 2 stages 0bxxxx0011 3 stages 0bxxxx1000 EC Fan 0b0001xxxx fan works not in heat...

Page 11: ...Occupied 2 Occupancy sensor Closed Occupied 3 Window contact Open Window Open 4 Window contact Closed Window Open 5 Disable heating Open Heating disabled 6 Disable heating Closed Heating Disabled 7 D...

Page 12: ...nnel A period 1 Start time minute 0 59m min 0 406 0x0196 Read write Time channel A period 1 Set point 0 500 0 50 0 C 0 1 C F 210 407 0x0197 Read write Time channel A period 1 ECO mode 0b00000001 Comfo...

Page 13: ...ute 0 59m min 0 431 0x01AF Read write Time channel B period 3 Set point 0 500 0 50 0 C 0 1 C F 210 432 0x01B0 Read write Time channel B period 3 ECO mode NC 0 433 0x01B1 Read write Time channel B peri...

Page 14: ...0bxABC1234 with binary value 1 for active channel i e 0x01000100 A 2 0 464 0x01D0 Read write Make next day s holiday 0bxxx00000 None 0bxxx00001 0bxxx11111 days of holidays next n days starting next 0...

Page 15: ...0 ventilating PI loop controls fan stages only valves closed HMI mode 0b1xxx xxxx HMI Mode controller OFF 0b1xxx xx01 show symbol ventilating 0b1xxx xx10 show symbol heating 0b1xxx xx11 show symbol co...

Reviews: