Program description

FB-KE: 07

SRC KNX

Rev 1

SRC_KNX_620_BMA_E_2009_10_08_001.doc

Seite 9 von 14

Erstellt am 12.01.2010

Temperature controller, continuous

This controller sends value telegrams (type KNX: 5.001, EIB: EIS 6) as control values, e.g. for servo drives or fans for
controlling room temperature. For each current value received by the sensor, a new control value is calculated and
sent if necessary.
The input values of the controller can be handled by any KNX device with suitable communication objects. However,
the  channel  is  optimised  for  operating  with  an  EnOcean  temperature  sensor  supported  by  the  gateway.  Output
objects of a sensor channel and the matching input objects of a control channel can be connected in the same device
via group addresses.
The send interval of the temperature sensor  is usually  adjustable via jumpers in the device. For  the sensors  tested
with the device, the best results were obtained with a send interval of max. 16 minutes. With this value, the sensors
were  easily able to continue transmitting through the night if installed in a location that  was  not too  dark during the
day. The installation location of the sensor is decisive for the effectiveness of the control and should be selected with
care and after sufficient testing.
The control value from the controller is calculated by the following method:

Control value change = 42 * (set value – current value)
Control value = old control value + control value change;

Example:
A temperature difference of 3 °C results in a control value change of ~50 % (without limitation).

Communication objects

The devices printed in italics are typical application examples.

Input objects:

Presence:

From  a  time  switch;

presence  detector  or  presence  key  of  a  supported  room  control  unit.  The

presence is switched on with an ON telegram and off with an OFF telegram or after a switch-off delay
Temperature:

From a temperature sensor;

current temperature value; used as the current value for the control

Set  value  adjustment:

From  the  set  value  adjustment  of  a  supported  room  control  unit;

used  for  set  value

adjustment but also for specification of a basic set value.
Window:

From a window contact;

When an ON telegram is received via this communication object, the valves

switch off after a delay defined in the parameters and the control pauses. When an OFF telegram is received,
the delay is switched off and the control is activated.
Switch between heating/cooling:

From the central control unit;

If heating/cooling via a communication object

is  set  in  the  parameters  settings,  this  communication  object  is  visible.  It  can  be  used  to  change  over  the
operating mode of the channel. Heating is activated with an ON telegram and cooling with an OFF telegram.

Comm. object

KNX (EIB) type

Size

Channel … : Presence

1.001 (EIS 1)

1 bit

Channel … : Temperature

9.002 (EIS 5)

2 bytes

Channel … : Set value
adjustment

9.002 (EIS 5)

2 bytes

Channel … : Frost

1.001 (EIS 1)

1 bit

Channel… : Switch between
heating/cooling

1.001 (EIS 1)

1 bit

Output objects:

Heating on/off:

To a boiler or visualisation;

If the sent control value from the heating controller changes from

0 % to a value greater than 0 %, an ON telegram is sent via this communication object; an OFF telegram is sent
in the opposite case.
Cooling  on/off:

To  an  air  conditioner  or  visualisation;

If  the  sent  control  value  from  the  cooling  controller

changes  from  0 % to  a value  greater  than  0 %,  an ON telegram  is  sent via this communication  object;  an  OFF
telegram is sent in the opposite case.
Heating value:

To a drive;

control value from the heating controller

Cooling value:

To a fan or flap control;

control value from cooling controller

Summary of Contents for 312424

Page 1: ...ch sensor of a switch module Various switching functions Switching and dimming Blind up down Room control unit with the following options Slide switch presence key Set value adjustment Multiple contac...

Page 2: ...ic transformers ballasts etc near the gateway Detailed information on coverage planning and HF penetration can be found in the sensor data sheets and at Figure 3 KNX ENO 620 622 from the outside The d...

Page 3: ...right of the dot is the number of connected devices If a further connection to this channel is not possible the display shows an F In learn mode a sending EnOcean device can be connected to a cable i...

Page 4: ...eystroke on the bottom key causes an ON telegram to be sent On off rocker top bottom Same as above but the functions of the top and bottom of the rocker switch are reversed Value key A short or long k...

Page 5: ...m darker or switch off the dimmer is switched on or dimmed up dimming is stopped when the key is released On off brighter darker rocker top bottom A short keystroke on the top key switches the dimmer...

Page 6: ...to the temperature Slide switch presence key Some Thermokon devices have either a presence key or a slide switch If the Presence key function is selected on the ETS pressing the key causes the gateway...

Page 7: ...Thermokon window contact SRW01 Omnio window contact FK101 Up to four EnOcean window contacts can be linked to one channel Whether or not a telegram should be sent when a window is opened or closed an...

Page 8: ...osed throughout the delay period The telegram sent when the contact is opened can be sent with a switch off delay For this the contact must remain open throughout the delay period Comm object KNX EIB...

Page 9: ...esence key of a supported room control unit The presence is switched on with an ON telegram and off with an OFF telegram or after a switch off delay Temperature From a temperature sensor current tempe...

Page 10: ...Only those communication objects and parameters that are needed for the mode are displayed Light controller continuous This controller type is provided for constant light control with a dimmer via val...

Page 11: ...nce of 50 lux causes a control value change of 15 without limitation For a set value of 200 lux a brightness difference of 50 lux causes a control value change of 7 without limitation Communication ob...

Page 12: ...witch off delay is started with the first OFF telegram of the detector if the control is active Light controller on off This controller type is available for light control An upper and lower threshold...

Page 13: ...t of the on off light value controller They differ in that the input object for the current value is of a different type Comm object KNX EIB type Size Channel Input temperature 9 002 EIS 5 2 bytes Con...

Page 14: ...y an energy saving function can be implemented in which the user can switch on the light as needed The controller switches off the light automatically if the user clearly forgot to switch it off The a...

Reviews: