Program description

FB-KE: 07

SRC KNX

Rev 1

SRC_KNX_620_BMA_E_2009_10_08_001.doc

Seite 13 von 14

Erstellt am 12.01.2010

Switch-off telegram when going beyond a value: These two parameters define the working range of the control,
or the hysteresis.
Attention: Not every value that can be set here can be represented via the 2-byte-float object type. It is important
to check the values at the which the controller actually switches.
Wait for switch-off telegram to start switch-off delay : If the presence is evaluated by the controller, the switch-
off  delay  is  restarted  with  every  ON  telegram to  the  presence object  when  set  to  "No".  When  set  to  "Yes",  the
switch-off delay is started with the first OFF telegram if the control is active.
Switch-off delay after detection of presence: After this time elapses, the presence is switched off if presence was
not switched on again during this time via the communication object.
Off-time  after  switching  manually:  If  switching  manually,  the  on/off  controller  stays  in  the  state  specified
through  manual  control  for  the  set  time  period.  After  this  time  elapses,  the  automatic  mode  is  resumed  as
defined by the operating mode.
Inverted sending: The states sent by the switching output can be inverted here.

Temperature controller, on/off

The operating mode of this controller is identical to that of the on/off light value controller. They differ in that the input
object for the current value is of a different type.

Comm. object

KNX (EIB) type

Size

Channel… : Input temperature

9.002 (EIS 5)

2 bytes

Controller, common 2-byte-float, on/off

The operating mode of this controller is identical to that of the on/off light value controller. Again, they differ in that the
input object for the current value is of a different type.

Comm. object

KNX (EIB) type

Size

Channel… : Input 2-byte-float

9.001 (EIS 5)

2 bytes

Also, the upper and lower limit values must be entered separately using two parameters for value and multiplier.

Controller, common 0… 255, on/off

The operating mode of this controller is identical to that of the on/off light value controller. Again, they differ in that the
input object for the current value is of a different type.

Comm. object

KNX (EIB) type

Size

Channel… : Input value 0… 255 

5.001 (EIS 6)

1 byte

Application example: heating controller

The following figure shows an example of temperature control setup. Both the current temperature and the set value
adjustment are sent by a room operating unit. The controller in the gateway calculates the control value and sends it
to the heating valve via the KNX bus. If a presence detector or a window contact are integrated in the system, their
values can be taken into account by the controller to achieve an optimal level of energy efficiency.

KNX drive
for radiator

EnOcean
Room control unit

EnOcean
Window contact

EnOcean
Presence detector

KNX EnOcean

Gateway

KNX ENO 622

Summary of Contents for 312424

Page 1: ...ch sensor of a switch module Various switching functions Switching and dimming Blind up down Room control unit with the following options Slide switch presence key Set value adjustment Multiple contac...

Page 2: ...ic transformers ballasts etc near the gateway Detailed information on coverage planning and HF penetration can be found in the sensor data sheets and at Figure 3 KNX ENO 620 622 from the outside The d...

Page 3: ...right of the dot is the number of connected devices If a further connection to this channel is not possible the display shows an F In learn mode a sending EnOcean device can be connected to a cable i...

Page 4: ...eystroke on the bottom key causes an ON telegram to be sent On off rocker top bottom Same as above but the functions of the top and bottom of the rocker switch are reversed Value key A short or long k...

Page 5: ...m darker or switch off the dimmer is switched on or dimmed up dimming is stopped when the key is released On off brighter darker rocker top bottom A short keystroke on the top key switches the dimmer...

Page 6: ...to the temperature Slide switch presence key Some Thermokon devices have either a presence key or a slide switch If the Presence key function is selected on the ETS pressing the key causes the gateway...

Page 7: ...Thermokon window contact SRW01 Omnio window contact FK101 Up to four EnOcean window contacts can be linked to one channel Whether or not a telegram should be sent when a window is opened or closed an...

Page 8: ...osed throughout the delay period The telegram sent when the contact is opened can be sent with a switch off delay For this the contact must remain open throughout the delay period Comm object KNX EIB...

Page 9: ...esence key of a supported room control unit The presence is switched on with an ON telegram and off with an OFF telegram or after a switch off delay Temperature From a temperature sensor current tempe...

Page 10: ...Only those communication objects and parameters that are needed for the mode are displayed Light controller continuous This controller type is provided for constant light control with a dimmer via val...

Page 11: ...nce of 50 lux causes a control value change of 15 without limitation For a set value of 200 lux a brightness difference of 50 lux causes a control value change of 7 without limitation Communication ob...

Page 12: ...witch off delay is started with the first OFF telegram of the detector if the control is active Light controller on off This controller type is available for light control An upper and lower threshold...

Page 13: ...t of the on off light value controller They differ in that the input object for the current value is of a different type Comm object KNX EIB type Size Channel Input temperature 9 002 EIS 5 2 bytes Con...

Page 14: ...y an energy saving function can be implemented in which the user can switch on the light as needed The controller switches off the light automatically if the user clearly forgot to switch it off The a...

Reviews: