 FAULTS

Make sure the electric power supply is

switched off and the fuel tank is full,

before you start troubleshooting.

6.1  

Troubleshooting table

 Warning

 

Switch off power during maintenance!

Fault

Nr.

Cause

Solution

Who

The convector 

heater does not 

start up.

1

The convector heater is not live. Check the electric connection.

User

2

The burner relay is not working:

the indicator is on.

Press the reset button in the

operating panel. See fig. 5 (I).

User

3

A malfunction has occurred in 

the burner automat.

Replace the burner automat.

Dealer

4

The thermostat has not been 

set correctly.

Correct the settings.

Dealer

5

The room thermostat is 

defective.

Replace the thermostat.

User

6

There is no cap on the

thermostat connection.

Replace the cap if the room

thermostat is not in use.

User

7

The fuel pump is stuck.

Replace the fuel pump.

Dealer

8

The maximum thermostat is

stopping the convector heater.

Check (and correct) the air flow.

Reset the convector heater.

User

9

The combination thermostat is

defective.

Replace the combination

thermostat.

Dealer

10

The frequency controller is in

disorder.

Reset the frequency controller,

see fig. 5 (G).

User

11

The capacitor of the burner 

motor is defective.

Replace the capacitor.

Dealer

12

The room thermostat has been

placed in the hot-air flow.

Install the room thermostat 

away from the hot-air flow.

User

The fan is starting 

up immediately.

13

The fan thermostat has not 

been set correctly.

Correct the settings.

See malfunction 9.

Dealer

The convector 

heater is starting 

up, but no flame is 

forming.

14

The pump coupling is defective. Replace the pump coupling.

Dealer

15

The pressure regulator in the 

fuel pump is stuck.

Check the nozzle.

Replace the pump.

Dealer

16

The pump pressure is incorrect,

or the filter inside the pump is

clogged.

Adjust the pump pressure using

a pressure gauge.

Dealer

17

The main filter is clogged.

Clean or replace the filter.

User

18

The shut-off valve of the fuel 

filter is closed.

Reset the thermostat. See fig. 5

(B).

User

19

The fuel tank is empty.

Open up the drain tap to drain

the condensate and fill the tank.

User

Summary of Contents for IMAC 4000 OIL US

Page 1: ...IMAC 4000 OIL US USER MANUAL...

Page 2: ...2 40 020 950 rev 01 2019 IMAC 4000 US A B C D E F G H I J K O P Q R 1 2 3 4...

Page 3: ...3 40 020 950 rev 01 2019 IMAC 4000 US 6 5 7...

Page 4: ...4 40 020 950 rev 01 2019 IMAC 4000 US Language English 5...

Page 5: ...nty regulations Environment Note The convector heater is made of various metals and synthetic materials The heater also contains electronic parts which must be treated as electronic waste Please conta...

Page 6: ...ignited by the spark between the electrodes The light of the flame that is created will activate the photocell This photocell checks whether a good combustion is brought about In case of poor or no c...

Page 7: ...ches stinging eyes Dizziness disorientation Difficulty breathing feels of being suffocated Proper ventilation air exchange OSHA 29 CFR 1926 57 to support combustion and maintain acceptable air quality...

Page 8: ...nimum distance is 1 m 5 Ensure that the heated air is allowed to flow freely The minimum distance between the outlet and any obstacle is 5 m 6 Check the ventilation surface per kW a surface area of 25...

Page 9: ...ly before carrying out any maintenance 5 3 V belts Fig 7 Impression V belt tension 13 mm 32 2 N 1 Remove the upper and lower side panels A 2 Lower the motor B by turning the adjusting nuts C 3 Remove...

Page 10: ...ect the air flow Reset the convector heater User 9 The combination thermostat is defective Replace the combination thermostat Dealer 10 The frequency controller is in disorder Reset the frequency cont...

Page 11: ...nt and the amount of soot Dealer 26 The settings of the nozzle holder and or the forcer plate are incorrect or dirty Correct the settings of the nozzle holder and the forcer plate Clean the nozzle and...

Page 12: ...es will not close Close the cock see fig 8 B User Contact your dealer Dealer The convector heater stops 35 An overheating problem has occurred in the convector heater Reduce the resistance at the outl...

Page 13: ...ion Check the temperature resistance of the hose used Contact your dealer for information about the maximum length of the exhaust hoses bends manifolds and hose clamps The maximum static pressure in t...

Page 14: ...14 40 020 950 rev 01 2019 IMAC 4000 OIL US English Date Description Maintenance or Failure Action by A...

Page 15: ...15 40 020 950 rev 01 2019 English IMAC 4000 OIL US Date Description Maintenance or Failure Action by...

Page 16: ...16 40 020 950 rev 01 2019 IMAC 4000 OIL US English IMAC 4000 A Fuel filter 41 520 031 B Nozzle C Electrodes block D Set of V belts 41 740 318 2xSPA 2240LW B...

Page 17: ...18 000 24 000 24 000 CFM 10 595 14 715 14 715 Max pressure Pa 400 1000 700 Warm air T C 44 31 43 F 111 88 109 Current A 18 29 29 Nozzle SLW USG hr 6 00 60 S Fan thermostat C 35 F 95 Burner thermostat...

Page 18: ...18 40 020 950 rev 01 2019 IMAC 4000 US...

Page 19: ...care but Thermobile Industries B V cannot be held liable for possible errors in the information or the consequences thereof The information provided herein may not be reproduced and or published in an...

Page 20: ...NDUSTRIES BV Konijnenberg 80 4825 BD Breda Nederland Postbus 3312 4800 DH Breda Nederland Bedrijfsnummer 3502 T 31 0 76 587 34 50 F 31 0 76 587 27 89 info thermobile com www thermobile com 40 020 950...

Reviews: