IMAC 4000 GAS US

Fault

Nr.

Cause

Solution

Who

The convector 

heater is starting 

up, but no flame is 

forming.

17

The distributor is blocked or

damaged.

Replace the distributor.

Dealer

18

The electrodes are worn or the

settings are incorrect.

Clean or replace the electrodes. Dealer

19

The magnet valve or valves will

not open.

Check the electric connection.

You should hear a “click” when

the convector

User

Clean or replace the magnet

valve(s).

Dealer

20

The ionization probe is dirty or

defective.

Check and clean the ionization

probe.

User

Test the ionization probe and

replace if necessary.

Dealer

21

The air-inlet valve of the burner 

is not correctly set.

Check the air-inlet valve.

Measure the CO2 content and

the amount of soot.

Dealer

22

The settings of the distributor

holder and/or the forcer plate 

are incorrect or dirty.

Correct the settings of the

distributor holder and the forcer

plate.

Clean the nozzle and the forcer

plate.

Dealer

23

Exhaust opening or flue

connection is in poor condition.

Connect the convector heater 

to a flue that is in good 

condition.

Correct the connections.

User

24

The ignition transformer is

defective.

Test the insulation in relation to

the burner.

Replace the ignition transformer

if necessary.

Dealer

The burner is

starting up poorly

(stutters).

25

There is insufficient fresh-air

supply.

Open a door or window.

Use an outside-air suction

device for the burner.

User

26

There are problems in the 

burner room or heat exchanger.

Clean, repair or replace the

burner room and heat

exchanger, if necessary.

Dealer

The convector

heater burns

intermittently.

27

The burner thermostat has not

been set correctly.

Set the burner thermostat

according to the manufacturer’s

specifications.

Dealer

The burner is

producing soot.

28

The air inlet has not been

correctly set.

Set the air inlet.

Dealer

Summary of Contents for IMAC 4000 GAS US

Page 1: ...IMAC 4000 GAS US USER MANUAL...

Page 2: ...2 40 020 950 rev 01 2019 IMAC 4000 US A B C D E F G H I J K L M N O P Q R 1 2 3 4...

Page 3: ...3 40 020 950 rev 01 2019 IMAC 4000 US 5 7...

Page 4: ...4 40 020 950 rev 01 2019 IMAC 4000 US Language English 5...

Page 5: ...bility For warranty and liability see general warranty regulations Environment Note The convector heater is made of various metals and synthetic materials The heater also contains electronic parts whi...

Page 6: ...ible mixture that is ignited by the spark between the electrodes The light of the flame that is created will activate the photocell This photocell checks whether a good combustion is brought about In...

Page 7: ...s Dizziness disorientation Difficulty breathing feels of being suffocated Proper ventilation air exchange OSHA 29 CFR 1926 57 to support combustion and maintain acceptable air quality shall be provide...

Page 8: ...Caution Only use natural gas of the family I2H and propane of the family 13P 4 Make sure there is sufficient distance between the wall and the air inlet Minimum distance is 1 m 5 Ensure that the heate...

Page 9: ...efore carrying out any maintenance 5 3 V belts Fig 7 Impression V belt tension 13 mm 32 2 N 1 Remove the upper and lower side panels A 2 Lower the motor B by turning the adjusting nuts C 3 Remove the...

Page 10: ...7 The air pressure switch has not closed Check the air hoses for dirt Replace if necessary Dealer 8 The maximum thermostat is stopping the convector heater Check and correct the air flow Reset the con...

Page 11: ...orcer plate are incorrect or dirty Correct the settings of the distributor holder and the forcer plate Clean the nozzle and the forcer plate Dealer 23 Exhaust opening or flue connection is in poor con...

Page 12: ...e switched off 31 The magnet valve or valves will not close Close the cock see fig 8 B User Contact your dealer Dealer The convector heater stops 32 An overheating problem has occurred in the convecto...

Page 13: ...ion Check the temperature resistance of the hose used Contact your dealer for information about the maximum length of the exhaust hoses bends manifolds and hose clamps The maximum static pressure in t...

Page 14: ...14 40 021 119 rev 00 2019 IMAC 4000 GAS US English Date Description Maintenance or Failure Action by A...

Page 15: ...15 40 021 119 rev 00 2019 English IMAC 4000 GAS US Date Description Maintenance or Failure Action by...

Page 16: ...pressure propane PSI iwc 0 27 5 8 0 27 5 8 0 32 8 8 Inlet Burner pressure natural gas PSI iwc 0 04 1 2 0 04 1 2 0 08 2 1 Air capacity m hr 18 000 24 000 24 000 CFM 10 595 14 715 14 715 Max pressure P...

Page 17: ...17 40 021 119 rev 00 2019 English IMAC 4000 GAS US...

Page 18: ...18 40 020 950 rev 01 2019 IMAC 4000 US...

Page 19: ...care but Thermobile Industries B V cannot be held liable for possible errors in the information or the consequences thereof The information provided herein may not be reproduced and or published in an...

Page 20: ...NDUSTRIES BV Konijnenberg 80 4825 BD Breda Nederland Postbus 3312 4800 DH Breda Nederland Bedrijfsnummer 3502 T 31 0 76 587 34 50 F 31 0 76 587 27 89 info thermobile com www thermobile com 40 021 119...

Reviews: