IMAC 4000 GAS US

English

6.0 

 FAULTS

Make sure the electric power supply is

switched off and the fuel tank is full,

before you start troubleshooting.

6.1  

Troubleshooting table

 Warning

 

Switch off power during maintenance!

Fault

Nr.

Cause

Solution

Who

The convector 

heater does not 

start up.

1

The convector heater is not live. Check the electric connection.

User

2

The burner relay is not working:

the indicator is on.

Press the reset button in the

operating panel. See fig. 5 (I).

User

3

A malfunction has occurred in 

the burner automat.

Replace the burner automat.

Dealer

4

The thermostat has not been 

set correctly.

Correct the settings.

Dealer

5

The room thermostat is 

defective.

Replace the thermostat.

User

6

There is no cap on the

thermostat connection.

Replace the cap if the room

thermostat is not in use.

User

7

The air pressure switch has not

closed.

Check the air hoses for dirt.

Replace if necessary.

Dealer

8

The maximum thermostat is

stopping the convector heater.

Check (and correct) the air flow.

Reset the convector heater.

User

9

The combination thermostat is

defective.

Replace the combination

thermostat.

Dealer

10

There is no fuel

Check whether the valve in the

fuel supply is open.

User

Check the setting of the gas

appliance regulator.

Dealer

11

The capacitor of the burner 

motor is defective.

Replace the capacitor.

Dealer

12

The room thermostat has been

placed in the hot-air flow.

Install the room thermostat 

away from the hot-air flow.

User

The fan is starting 

up immediately.

13

The fan thermostat has not 

been set correctly.

Correct the settings.

See malfunction 9.

Dealer

The convector 

heater is starting 

up, but no flame is 

forming.

14

There is air in the fuel supply.

De-aerate the fuel supply.

User

15

There is not enough fuel.

Adjust the gas appliance

regulator.

Dealer

16

The main filter is clogged.

Clean or replace the filter.

User

Summary of Contents for IMAC 4000 GAS US

Page 1: ...IMAC 4000 GAS US USER MANUAL...

Page 2: ...2 40 020 950 rev 01 2019 IMAC 4000 US A B C D E F G H I J K L M N O P Q R 1 2 3 4...

Page 3: ...3 40 020 950 rev 01 2019 IMAC 4000 US 5 7...

Page 4: ...4 40 020 950 rev 01 2019 IMAC 4000 US Language English 5...

Page 5: ...bility For warranty and liability see general warranty regulations Environment Note The convector heater is made of various metals and synthetic materials The heater also contains electronic parts whi...

Page 6: ...ible mixture that is ignited by the spark between the electrodes The light of the flame that is created will activate the photocell This photocell checks whether a good combustion is brought about In...

Page 7: ...s Dizziness disorientation Difficulty breathing feels of being suffocated Proper ventilation air exchange OSHA 29 CFR 1926 57 to support combustion and maintain acceptable air quality shall be provide...

Page 8: ...Caution Only use natural gas of the family I2H and propane of the family 13P 4 Make sure there is sufficient distance between the wall and the air inlet Minimum distance is 1 m 5 Ensure that the heate...

Page 9: ...efore carrying out any maintenance 5 3 V belts Fig 7 Impression V belt tension 13 mm 32 2 N 1 Remove the upper and lower side panels A 2 Lower the motor B by turning the adjusting nuts C 3 Remove the...

Page 10: ...7 The air pressure switch has not closed Check the air hoses for dirt Replace if necessary Dealer 8 The maximum thermostat is stopping the convector heater Check and correct the air flow Reset the con...

Page 11: ...orcer plate are incorrect or dirty Correct the settings of the distributor holder and the forcer plate Clean the nozzle and the forcer plate Dealer 23 Exhaust opening or flue connection is in poor con...

Page 12: ...e switched off 31 The magnet valve or valves will not close Close the cock see fig 8 B User Contact your dealer Dealer The convector heater stops 32 An overheating problem has occurred in the convecto...

Page 13: ...ion Check the temperature resistance of the hose used Contact your dealer for information about the maximum length of the exhaust hoses bends manifolds and hose clamps The maximum static pressure in t...

Page 14: ...14 40 021 119 rev 00 2019 IMAC 4000 GAS US English Date Description Maintenance or Failure Action by A...

Page 15: ...15 40 021 119 rev 00 2019 English IMAC 4000 GAS US Date Description Maintenance or Failure Action by...

Page 16: ...pressure propane PSI iwc 0 27 5 8 0 27 5 8 0 32 8 8 Inlet Burner pressure natural gas PSI iwc 0 04 1 2 0 04 1 2 0 08 2 1 Air capacity m hr 18 000 24 000 24 000 CFM 10 595 14 715 14 715 Max pressure P...

Page 17: ...17 40 021 119 rev 00 2019 English IMAC 4000 GAS US...

Page 18: ...18 40 020 950 rev 01 2019 IMAC 4000 US...

Page 19: ...care but Thermobile Industries B V cannot be held liable for possible errors in the information or the consequences thereof The information provided herein may not be reproduced and or published in an...

Page 20: ...NDUSTRIES BV Konijnenberg 80 4825 BD Breda Nederland Postbus 3312 4800 DH Breda Nederland Bedrijfsnummer 3502 T 31 0 76 587 34 50 F 31 0 76 587 27 89 info thermobile com www thermobile com 40 021 119...

Reviews: