14
40.020.940 - rev. 04 - 2011
IMA-US
English
9
INSTALLATION OF ACCESSORIES
9.1
The heater is provided with a flue connection.
1.
Fit a flue (B) to the flue connection (C).
2.
Fit a rain cover (A) to the end of the flue.
9.2
Diameter of the flue connection
/i
9.3
Outlet hose
An outlet hose must be fitted to the outlet of the
heater, in order to blow heated air to a remote
area away from the heater.
Please contact the dealer for information about
maximum lengths of outlet hoses, bends,
distribution pipes and hose clamps.
9.4
Diameters of outlet hoses
/i
/i
9.5
Room thermostat
See the instructions of the room thermostat.
10
STANDARDS AND GUIDELINES
For the standards and guidelines, go to
www.thermobile.nl.
Caution
The flue must point upwards. Never
place the flue horizontal. An angle of 45°
is acceptable; minimum length flue 40
inch.
IMA 61
IMA 111
IMA 185
7 inch
8 inch
8 inch
Caution
Check the temperature resistance of the
used hose.
Number of
outlets
IMA 61
IMA 111
IMA 185
inch
inch
inch
1
∅
16
∅
20
∅
24
2
∅
12
∅
15
∅
20
3
-
-
∅ 15
4
-
∅
12
∅
12
Back
pressure of
fan
IMA 61
IMA 111
IMA 185
lb/ft
2
lb/ft
2
lb/ft
2
8.35
8.35
9.4