29
HOUR COUNTER:
Press the HOURS button to view the operating hours.
HOURS+FAN SPEED:
Press the buttons HOURS+FAN SPEED for 4 seconds, when the machine is
supply, to activate the remote control. Once the remote control is active the led REMOTE lit.
4.3
Alarm list
PROBLEMA
POSSIBLE CAUSE and CORRECTIVE ACTIONS
+
“FULL”
Tank full or not present.
The alarm is automatically reset by inserting the tank correctly.
The alarm is automatically reset by emptying the tank.
+
“Lo
t”
It occurs for two possible reasons: the ambient temperature is too low. To restore, put
the unit in an environment above 10 ° C, if it is not reset, set it to OFF with the POWER
button and disconnect the power supply.
+
“Pro2”
Temperature probe malfunction. In any case, the device continues to operate. Contact
the service to replace the probe
+
“dEFr”
Defrost thermostat malfunction
Dehumidifier goes to stand-by. Please contact the service centre for the replacement
.
+ “HiPS”
High pressure switch intervention alarm.
Clean both air filters.
Disconnect the unit from the power supply.
Open the electrical panel and reset the high-pressure switch.
If the alarm persists, contact the authorised service centre.
+
“LoPS”
Low pressure switch intervention alarm.
Clean both air filters.
Disconnect the unit from the power supply and reconnect it.
If the alarm persists, contact your authorised service centre.
4.4
Fixed drain connection
A fixed condensate drain can be connected to the tank.
16mm hose connection.