Specifications
B-2
LevelPRO Installation Guide
Thermo Fisher Scientific
Approvals
CSA/C-US approved Class I, Div. 1, Groups B, C, & D; Class II,
Div. 1, Groups E, F, & G; Class III, Div. 1; indoor and outdoor
CSA ENCL 4
Intertek ATEX approved II 2 G Ex d IIC T6 IP66
CE Mark
*Detector-transmitter lengths available in odd increments (3 ft, 5, ft, etc.) as a special order.
for details.
Table B–4.
Outputs/Inputs
Current outputs
Standard: 4–20 mA isolated, loop-powered into 800 ohms,
field scalable
Optional: 4–20 mA isolated, self-powered into 800 ohms, field
scalable
Optional: 4–20 mA non-isolated, self-powered into 800 ohms,
field scalable
Serial outputs
RS485 half-duplex, RS232 full duplex
Fieldbus: A Device Description (DD) for the LevelPRO is
available from the Fieldbus Foundation website. The DD is a
DD4 that is interpreted by a host implementing DD Services 4.x
or higher.
Contact closure outputs
2X 115 Vac/28 Vdc SPDT at 10 A (230 Vac SPDT at8 A)
Inputs
Signal from another LevelPRO detector; additional input for gas
density compensation or buildup available
Dry contact closure
Table B–5.
Mounting Hardware
Integrated transmitter/detector
Integral bolt-on bracket
Gamma ray source
Integral bolt-on bracket
Summary of Contents for LevelPRO Series
Page 2: ......
Page 3: ...LevelPRO Continuous Gamma Level System Installation Guide P N 717760 Revision H ...
Page 4: ......
Page 6: ...This page intentionally left blank ...
Page 8: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 28: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 48: ...This page intentionally left blank ...
Page 96: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...