Thermo Scientific DLT Installation & Operating Manual Download Page 10

Thermo Scientific Harris Ultra-Low Temperature Freezers

 Installation and Operation

6

5.2.5 Alarm Test (Harris DLT and SLT Freezers)

To test the cold and warm alarms, complete the following steps:

1. Press and hold the Alarm Test pad. The digital temperature 

display indicates rising temperature. When the temperature 
reaches the warm alarm value, the alarm sounds.

Note:

The temperature of the refrigerated space does not 

change during this procedure. Only the sensor is heated.

2. Release the Alarm Test pad, the sensor and display return to 

cabinet temperature in a few minutes.

You can press the Alarm Reset pad to silence the alarm but the 
alarm will ring back in five to seven minutes. You can silence the 
alarm in this manner as many times as necessary until the sensor 

cools below the warm alarm temperature. The alarm quits 
automatically when the sensor cools below the warm alarm 
value.

Note:

There is a limit on the alarm test feature. The alarm test 
will not commence if the warm alarm set point is more 
than 15 degrees warmer than the operating temperature 

set point. 

6 Backup System (Optional)

When you purchase a built-in CO

2

 or LN

2

 optional backup 

system for the freezer, the backup system control panel is located 
behind a hinged panel adjacent to the grill (refer to Figure 4).

Note:

Always purchase the cylinders which are equipped with 

siphon tubes for withdrawing liquid from the bottom of 
the cylinder. CO

2

 cylinders must be kept at room 

temperature to function properly. LN

bottles are 

functional at any reasonable temperature.

Use the panel below to set the backup initiation temperature, 
usually 10 to 15×C warmer than the operating set point.

Figure 4.  Control Panel for Optional 

Built-In Backup System

TEMPERATURE ºC

PUSH

TO SET

SET POINT

ADJUST

POWER

OFF

ON

Power

Switch

Temperature Control

Set Point Screw

Temperature Control

Set Button

Digital Temperature

Display

Note:

Harris ELT Series units and DLT chest models use 

free-standing, field installed Backup Systems.

6.1 CO

2

 and LN

2

 Precautions

Observe the following precautions when using liquid CO

2

 and 

LN

2

 backup systems.

WARNING!

If a CO

2

 or LN

2

 cylinder falls and a 

valve is knocked off, the cylinder becomes a deadly 
and completely unguided missile. Transport the 
cylinders in a handtruck or cart with secure chain ties 
for the cylinder. After cylinders are connected to the 
equipment, securely attach them with chains to a 
solid, stationary object such as a building column.

WARNING!

CO

2

 and LN

2

 liquids are non-poisonous 

but are very cold and will burn unprotected skin. 
Always wear protective eyewear and clothing when 
changing cylinders or working on the piping systems 
attached to an active source of liquid refrigerant.

WARNING!

 The gases produced by evaporation of 

CO

2

 or LN

2

 are non-poisonous but displace the 

oxygen in a confined space and can cause 
asphyxiation. 

Do not store the cylinders in 

subsurface or enclosed areas

.

CAUTION!

When closing the cylinder valve, make 

sure that the injection solenoid is energized to allow all 
the liquid to bleed off instead of being trapped in the 
supply tubing. Failure to do this results in activation of 
the pressure relief device, which could damage the 
freezer and requires replacing if it is activated.

CAUTION!

For chest and upright models ordered 

with factory installed built-in backup systems, the flow 
of liquid CO

2

 or LN

2

 will be discontinued if the door or 

lid is opened during operation of the backup system. 
For units operated with free-standing, field installed 
type backup system, the flow of liquid CO

2

 or LN

2

 will 

be discontinued upon door or lid opening 

only

 if the 

switch provided with the free-standing package is 
installed on the freezer.

6.2 Installation

Field installed systems are supplied with complete installation 

and operating instructions. If your system is factory installed, the 
freezer is shipped with a coiled length of tubing to connect the 
freezer to the bottles:

3/8 in. OD copper tubing for connection to the CO

2

 supply.

5/8 in. OD copper tubing covered with Armaflex

 insulating 

tubing for connection to the LN

supply.

Straighten the coiled tubing and connect one end to the labeled 
connection on the freezer and the other end to the supply bottle or 

building supply fitting. 

Summary of Contents for DLT

Page 1: ...Installation and Operation Manual Thermo Scientific Harris DLT SLT and ELT Ultra Low Temperature Freezers...

Page 2: ...d trademark of Armacell International GmBH All other trademarks are the property of Thermo Fisher Scientific Inc and its subsidiaries 2007 Thermo Fisher Scientific All rights reserved Suva is a regist...

Page 3: ...ocking the Door 2 4 5 2 Unlocking the Door 2 4 5 3 Opening the Door 2 4 6 Compressor Mounts 3 4 7 Pressure Equalization Port 3 5 Operation Harris DLT and SLT Series Freezers 4 5 1 Control Panel Featur...

Page 4: ...arm 9 8 Maintenance and Troubleshooting 10 8 1 Condenser Maintenance 10 8 1 1 Cleaning the Condenser 10 8 1 2 Cleaning the Condenser Filter 10 8 2 Gasket Maintenance 10 8 3 Defrosting the Freezer 10 8...

Page 5: ...the compressors to operate for a prolonged time period Attempting to utilize this freezer improperly may jeopardize user product safety or cause undue stress or damage to the refrigeration compressors...

Page 6: ...the prong is removed the warranty is invalidated 4 3 Voltage Safeguard Freezers are equipped with a standard built in Voltage Safeguard circuit to detect and adjust low line voltage The Voltage Safeg...

Page 7: ...qualization Port When an upright ultra low temperature freezer door is opened room temperature air rushes into the storage compartment When the door is closed the fixed volume of air is cooled rapidly...

Page 8: ...rease temperature values 18 Increment Pad Use this pad to increase temperature values The following indicators are available only when the freezer is equipped with the optional backup system refer to...

Page 9: ...the Warm Alarm Set Point 4 Release both pads when the digital temperature display window shows the correct set point value When the cabinet temperature drops below the Warm Alarm setting turn the key...

Page 10: ...serve the following precautions when using liquid CO2 and LN2 backup systems WARNING If a CO2 or LN2 cylinder falls and a valve is knocked off the cylinder becomes a deadly and completely unguided mis...

Page 11: ...wer WARNING You must push the Power Switch to the ON position in order to activate the backup system 6 4 System Status Lights In addition to the backup control system the built in backup system includ...

Page 12: ...ty 5 6 6 5 7 5 14 ft3 Empty 5 4 6 2 7 0 1 2 Full 4 8 5 5 6 3 1 2 Full 4 5 5 2 5 9 Full 3 5 4 2 4 8 Full 3 4 3 9 4 4 17 ft3 Empty 6 5 7 5 8 7 17 ft3 Empty 6 2 7 1 8 1 1 2 Full 5 5 6 3 7 3 1 2 Full 5 3...

Page 13: ...t Point and simultaneously press and hold the Set Point Display button The temperature display changes to read the existing set point value 2 Turn the set point screw clockwise for a colder setting an...

Page 14: ...inet 2 Turn off the freezer 3 Open the outer door and all inner doors 4 Let the freezer stand with doors open for at least 24 hours This allows both the interior and foamed refrigerant system to warm...

Page 15: ...a virtually unlimited standby life unless they develop a leak These containers hold liquid at room temperature and high pressure Several bottles can be connected together increasing the effective len...

Page 16: ...oxes for all chest models except 3 1 and 4 5 cu ft 6230 Single split rack holds 4 3 in boxes for all chest models except 3 1 and 4 5 cu ft 6231 Basket Rail Kit for 6 8 cu ft chest freezers 6217 Basket...

Page 17: ...rogen cylinder Description Catalog No Temperature recorder 6 in circular chart seven day drive panel mounted for 40 C to 95 C Not available for Harris Classic chest models which use 6383 6 Factory ins...

Page 18: ...rdering 5612 Deluxe Electronic Remote Alarm System User programmable to sound alarm in the event of temperature rise or power failure Can dial up to four telephone numbers to advise of alarm condition...

Page 19: ...die unter diese RoHS Anweisungfallen finden Sie unter www thermo com Conformit WEEE Questo prodotto deve rispondere alla direttiva dell Unione Europea 2002 96EC in merito ai Rifiuti degli Apparecchi...

Page 20: ...can be found on the dataplate attached to the equipment If available please provide the date purchased the source of purchase manufacturer or specific agent rep organization and purchase order number...

Page 21: ...Thermo Fisher Scientific Inc 275 Aiken Road Asheville NC 28804 United States www thermofisher com 38257H01 Rev J...

Reviews: