2-1
Chapter 2
Installation
This chapter contains information regarding the installation of the
Ramsey Mercury
Free Tilt
Sensor
system.
2.1 Control Unit Installation
Model 20-35-NM-F & 20-35-NM-F-4X
1.
The Control Unit should be mounted in a vibration-free area where the ambient
temperature does not fall below -40°C (-40°F) or exceed 50°C (122°F).
2.
The unit enclosure will accept two holes in the bottom for input of 3/4” diameter
conduits/cable gland.
3.
Use two separate conduits/cable glands, one for the probe and one for the
control and/or power circuits.
4.
The terminals will accept a 12 AWG stranded wire (maximum)
5.
For electrical connections, refer to Figure 2-7.