background image

All installations and services must be performed by qualified service personnel. 

Power (Side-Wall) Venting-Important Note Regarding 

 

c

CAUTION:  The  manufacturer  of  this  furnace  will  NOT  assume  responsibility  for 

damage to, and deterioration of, exterior building materials, e.g. brick, siding, clapboards, 
and  etc.,  in  close  proximity  to  the  vent  terminal  due  to  operation  of  a  power  vented,  oil 
furnace. This policy is applicable regardless of the cause of sooting. 
 
Two (2) problems typically arise when power venting any oil-fired appliance. 

1)

 

Soot  buildup  may  occur  at  an  accelerated  rate  on  critical  components  of  the 
furnace  oil  burner,  e.g.  the  primary  control  flame  sensor  (“cad  cell”),  the  burner 
head, oil nozzle, and etc. 

2)

 

Severe  damage  may  occur  to  external  surfaces  of  the  structure  in  the  event  the 
furnace  continually  produces  a  high  level  of  smoke  in  the  flue  gases.  Excess 
smoke  and  soot  can  be  produced  for  many  reasons,  some  of  which  cannot  be 
successfully controlled by the installer and the appliance manufacturer. 

 
NOTICE: The manufacturer of this furnace recommends the use of a chimney to vent this 
residential  oil  furnace.  If  a  power  venter  must  be  used,  it  is  the  responsibility  of  the 
installer and power venter manufacturer to design and assemble a satisfactory power vent 
system. 
 

 

 
A.  VENTING: 
 
NOTE:
 On the VHF-A** it is possible to rotate the flue elbow (which is factory installed for vertical discharge) 90° 
counterclockwise from the vertical position to adapt to various venting systems. 
 

 

c

  CAUTION  MUST  BE  TAKEN  NOT  TO  EXCEED  90°  ROTATION  (OF  THE  FLUE 

ELBOW) COUNTERCLOCKWISE OR RIGHT FROM THE VERTICAL POSITION. 

 
 
ROTATION OF FRONT FLUE ELBOW 
 
When  an  installation  requires  that  the  flue  exit  out  the  left  hand  side  casing  on  a  front  flue  unit,  remove  screw 
securing the 90 deg. elbow and rotate it 90° counterclockwise. Then, remove knock-out in side casing and extend 
vent through the opening.  
 
A  trim  collar  may  be  ordered  from  the  manufacter  of  this  furnace  to  hide  the  gap  around  the  flue  pipe.  This  trim 
collar, however, is not required for operation. Trim collar/gasket part numbers(s) 14121 / 330073. 
 
NOTE:  ROTATION OF FLUE PIPE IS ONLY ALLOWED FOR LEFT HAND SIDE VENTING 
APPLICATIONS. 
 
The VHF-A** may be vented through a standard correctly sized chimney. 
 
The VHF-A** may also be horizontally vented through a side wall. The manufacter of this furnace has available the 
Field model FDVS-45/FVOP-415 side wall vent kit for such applications. When installing the FDVS-45/FVOP-415 
side wall vent kit, outside combustion air must also be applied to the burner. The following table identifies 
application order information. 
 
 
 
 
 
 

Summary of Contents for Spirit VHF-ABE

Page 1: ...nce Improper installation adjustment alteration service or maintenance can cause a fire or explosion resulting in property damage personal injury or loss of life For assistance or additional informati...

Page 2: ...ry substantial property damage or death See Page 5 cWARNING THE HEAT EXCHANGER MUST BE CLEANED BY A QUALIFIED SERVICE PERSON See Page 8 cCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF See Page 9 cWAR...

Page 3: ...RETURN AIRFLOW AND AIR TEMPERATURE 3 D FILTERS MOUNTED EXTERNAL TO FURNACE 4 E LIMIT POSITION AND LOCATION 5 F BURNER INSTALLATION 6 G BURNER SPECIFICATIONS AND APPLICATIONS 7 H HEAT EXCHANGER CLEANI...

Page 4: ...located or protected to avoid physical damage by vehicles cWARNING This furnace is not to be used as a construction heater 5 Listed below are definitions of COMBUSTIBLE MATERIAL and NON COMBUSTIBLE MA...

Page 5: ...power venter manufacturer to design and assemble a satisfactory power vent system A VENTING NOTE On the VHF A it is possible to rotate the flue elbow which is factory installed for vertical discharge...

Page 6: ...tioning cooling the furnace should be installed parallel with or on the upstream side of the evaporator coil to avoid condensation in the furnace heat exchanger If the cooling unit is installed with a...

Page 7: ...essary to cut the return air opening in the side or rear casing depending upon the needs of the specific installation The filter rack provided with the furnace refer to Fig 2 will serve as a template...

Page 8: ...ange of the filter rack Connect the return air plenum to the filter rack and slide the filter into place Dimensions for adapting the return air plenum to the filter rack are provided See Fig 2 E LIMIT...

Page 9: ...ig 4 This retainer secures the chamber during shipping and helps to maintain insertion depth DO NOT remove this retainer when installing burner Fig 4 Typical location of the overfire air tap and compo...

Page 10: ...CONE FOR EXAMPLE A NOZZLE RATED AT 0 65 GPH 100 PSIG THAT PROVIDES AN 80 SPRAY ANGLE AND A HOLLOW SPRAY PATTERN WOULD BE ABBREVIATED IN THE TABLE AS 0 65 X 80 A For more specific burner information c...

Page 11: ...With access to the inside of the heat exchanger through the burner area clean out openings and vent pipe connection it is possible to use a long flexible wire brush and an industrial type vacuum clean...

Page 12: ...discoloration of materials and damage from rust or corrosion FLUE PIPE VENT PIPE OR CONNECTOR The furnace vent pipe should be inspected for signs of rust corrosion pitting or holes in pipe and leakage...

Page 13: ...ystem and home cWARNING To avoid injury from moving parts hot surfaces or electrical shock shut off the power to the furnace before removing any furnace access doors to service the air filters The fil...

Page 14: ...MASONRY CHIMNEY W METAL LINER FUEL LINE FILTER DRAFT CONTROL COMBUSTION TESTS Operate burner at least 10 minutes before CO2 in stack pipe INITIAL SERVICE SERVICE SERVICE INSTALLATION Draft Over fire D...

Page 15: ...All installations and services must be performed by qualified service personnel 12 APPENDIX A Replacement Parts List...

Page 16: ...All installations and services must be performed by qualified service personnel 13...

Page 17: ...All installations and services must be performed by qualified service personnel 14...

Page 18: ...All installations and services must be performed by qualified service personnel 15...

Page 19: ...All installations and services must be performed by qualified service personnel 16 APPENDIX B Wiring Diagrams BLOWER SPEED TAPS COOL A C Tap HEAT Heating Tap LOW Constant air or Dehumifier...

Page 20: ...All installations and services must be performed by qualified service personnel 17...

Reviews: