background image

All installations and services must be performed by qualified service personnel.

 

 

7

Compressor contactor 

The control provides switched 24VAC to operate a compressor contactor.  Rating shall be class   
2 - 24 VAC pilot duty @ 24 VAC (< 200mA).   

EAC (electronic air cleaner) 

The control provides a 120VAC output for an electronic air cleaner. This output is energized 
whenever the fan motor is energized (either low, heat or cool speed).  Connection is made via male 
quick connect terminal labeled "EAC". 

 

Humidifier 

The control provides a 120 VAC output for a humidifier.  Connections are made to a male quick 
connect terminal labeled "FAN".  
 

Status LED 

A red LED is provided to indicate any thermostat input has been recognized by the microprocessor 
on the control.  See Diagnostic Features for a function description of operation.   
 

Thermostat Input LEDs 

Four green LEDs are placed beneath their respective thermostat connections (W, Y, G and DEHUM) 
and operate whenever a call is present.  See Diagnostic Features for a function description of 
operation.   
 

Motor CFM LED 

This green LED will flash once for every 100CFM the blower is producing. 

 

E.  Operating Modes 

 

Standby Mode 

All outputs are off and the control is waiting for a thermostat demand.  The thermostat inputs, and 
limit switch are continuously monitored.  The control initiates action when a thermostat call is 
received or limit switch opens. 
 

Fan Mode 

A call for fan ("G") is received from the thermostat.  If no other mode is calling for blower operation, 
the control will choose a “Low” speed value from the position of DIP switch SW1 positions 4 through 
6, as shown in the CFM Tables and operate the fan at that speed.  The fan mode will be operated as 
long as the "G" input is calling

 

and neither the Heat mode nor the Cool mode is calling for blower 

operation. When the Heat and Cool modes call for blower operation, their respective outputs will take 
over after their respective turn-on time delays have expired. The speed Output is present until the 
fan call is satisfied. 
 

Cooling Mode 

A call for cool ("Y") is received from the thermostat.  If the heat mode is not active or the anti-short 
cycle delay is not in effect, the control will energize the “CC” terminal.  After a 10 second delay 
blower ramps up to the “COOL” speed determined by the position of DIP switch SW1 (positions 4 
through 6) determine a speed as shown in CFM Tables. 
When the call for cool is satisfied, the “CC” terminal is de-energized and the cooling off delay of 45 
seconds is started.  Forty-five seconds later the blower speed ramps toward zero and the control 
reverts to Standby Mode. 
 

Dehumidification Operation 

If a call for dehumidification is received while the Cool Mode is active, blower speeds will be 
reduced.  The speed value will be selected from the DEHUM column of the CFM Tables.  This input 
may only be used on systems using a thermostatic expansion valve (TXV) on the evaporator. 
 

Summary of Contents for OD6F/RA072DV5

Page 1: ...SOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER REFER...

Page 2: ......

Page 3: ...BEGINNING PAGE I BLOWER CONTROLLER INFORMATION 2 A TERMINAL DEFINITIONS FIELD WIRING 2 B WIRING SWITCHES 3 C INPUTS 6 D OUTPUTS 6 E OPERATING MODES 7 F CFM TABLES 9 II ECM TROUBLESHOOTING 19 A DIAGNOS...

Page 4: ......

Page 5: ...Thermostat call for heat R 24 VAC to thermostat G Thermostat call for fan Y Thermostat call for cool DEHUM Humidistat call for dehumidification TXV systems ONLY Thermostat Humidistat connections for...

Page 6: ...services must be performed by qualified service personnel 3 B WIRING SWITCHES TURN OFF THE ELECTRICAL POWER to the furnace before attempting to disconnect blower wiring OH6 OH8 OD6 OL6 Single Stage F...

Page 7: ...All installations and services must be performed by qualified service personnel 4 OH6 OD6 OL6 2 STAGE Figure 2 Blower Wiring...

Page 8: ...All installations and services must be performed by qualified service personnel 5 Figure 3 Board Layout with Switches...

Page 9: ...R This input has an indicator LED that will light when the control receives a call for cooling Refer to the Cool Mode section for the control operation Thermostat call for dehumidification DEHUM 24 V...

Page 10: ...received or limit switch opens Fan Mode A call for fan G is received from the thermostat If no other mode is calling for blower operation the control will choose a Low speed value from the position o...

Page 11: ...ard zero Table 1 ON and OFF Blower Delay Time Switch Settings Motor Blower Speed Three blower speed outputs are provided A G call for fan will provide the Low speed only A W heat call will provide the...

Page 12: ...their respective air flow rates for the ECM blower motor To change air flow rates from that of the shipped settings use the respective SW1 dipswitch on the furnace s integrated control board see Figu...

Page 13: ...1 Switch Settings Clg Tonage Cool Continuous 0 2 0 5 6 OFF 5 OFF 4 OFF 2 799 500 1 2 109 2 1 186 6 OFF 5 OFF 4 ON 2 5 1017 508 1 8 160 2 5 230 6 OFF 5 ON 4 OFF 3 1210 605 2 4 220 3 3 308 6 OFF 5 ON 4...

Page 14: ...3 OFF 2 ON 1 OFF 883 706 79 883 75 706 94 883 94 3 OFF 2 ON 1 ON 968 744 72 968 69 774 86 968 86 3 ON 2 OFF 1 OFF 1054 843 66 1054 63 843 79 1054 79 3 ON 2 OFF 1 ON 1153 922 60 1153 58 922 72 1153 72...

Page 15: ...e F0 02 05 3 OFF 2 OFF 1 OFF 1202 78o 1 6 146 2 5 233 3 OFF 2 OFF 1 ON 1315 71o 84o 1 9 174 2 7 252 3 OFF 2 ON 1 OFF 1429 65o 77o 2 3 206 3 2 294 3 OFF 2 ON 1 ON 1565 60o 70o 78o 2 6 242 3 6 337 Facto...

Page 16: ...00 500 557 1 0 89 1 8 161 6 OFF 5 OFF 4 ON 2 5 1018 509 703 1 4 121 2 1 192 6 OFF 5 ON 4 OFF 3 1212 606 848 1 8 159 2 6 231 6 OFF 5 ON 4 ON 3 5 1406 703 994 2 3 203 3 1 290 Factory SW1 Switch Settings...

Page 17: ...l SW 1 Switch Settings Heating CFM Aprox Rise F 0 Aprox Rise F 0 Aprox Rise F 0 0 2 0 5 3 OFF 2 OFF 1 OFF 755 73 1 3 114 1 9 173 3 OFF 2 OFF 1 ON 826 66 80 1 4 121 2 1 191 3 OFF 2 ON 1 OFF 898 61 74 1...

Page 18: ...Air Flow Static Pressure Amps Watts Fan Control SW 1 Switch Settings Clg Tonage Cool Continous 0 2 0 5 6 OFF 5 OFF 4 OFF 2 799 500 1 3 115 2 0 185 6 OFF 5 OFF 4 ON 2 5 1017 508 1 8 168 2 5 234 6 OFF 5...

Page 19: ...898 92 3 OFF 2 ON 1 ON 983 786 64 983 67 786 84 983 84 3 ON 2 OFF 1 OFF 1068 854 59 1068 62 854 77 1068 77 3 ON 2 OFF 1 ON 1168 934 54 1168 57 934 71 1168 71 Factory SW1 Switch Settings 3 ON 2 ON 1 O...

Page 20: ...1 Switch Settings Heating CFM Aprox Rise F 0 Aprox Rise F 0 Aprox Rise F 0 0 2 0 5 3 OFF 2 OFF 1 OFF 755 73 o 1 1 93 1 7 154 3 OFF 2 OFF 1 ON 826 66 o 80 o 1 2 105 1 9 168 3 OFF 2 ON 1 OFF 898 61 o 74...

Page 21: ...essure in W C Fan Control SW 1 Sw itch Setting Clg Tonnage Cool Continuous 0 2 0 5 6 OFF 5 OFF 4 OFF 2 799 500 1 2 100 1 9 162 6 OFF 5 OFF 4 ON 2 5 1017 508 1 8 155 2 5 223 6 OFF 5 ON 4 OFF 3 1210 605...

Page 22: ...are driven by the Y W G and DEHUM inputs and are located directly below those inputs They will light to indicate the presence of these signals The red Board Status LED has two functions 1 It will lig...

Page 23: ...nt check Motor oscillates up down while being tested off of blower It is normal for motor to oscillate with no load on shaft Motor starts but runs erratically Varies up and down or intermittent Check...

Page 24: ...Install drip loops Locate connectors above 7 and 4 o clock positions Use authorized motor and control model s for replacement Replace one motor or control model with another unless an authorized repla...

Page 25: ...All installations and services must be performed by qualified service personnel 22 T stat in bad location Figure 4 ECM pin connectors...

Page 26: ...RNESS TO MOTOR IF CONNECTIONS ARE GOOD AND MOTOR STILL DOES NOT RUN REPLACE MOTOR THIS GUIDE SHOULD BE USED IN THE CASE OF A STOPPED OR MANFUNCTIONED ECM BLOWER MOTOR THE FOLLOWING SHOULD HELP ESTABLI...

Page 27: ...THE INSTRUCTIONS IN THE BOXES CHECK 24V SUPPLY TO INTEGRATED CONTROL IS THERE 24V ACROSS R B C ON THE INTEGRATED CONTROL REPLACE INTEGRATED CONTROL CHECK CONNECTIONS AND WIRES AT INTEGRATED CONTROL IF...

Page 28: ...Status LED Off 1 HEAT mode On 2 BLOWER HEAT 3 Status LED Flashes 1 COOL mode On 2 Blower On Delay Started 3 Condenser On 4 Status LED On continuous 1 FAN mode On 2 BLOWER LOW 3 Status LED On continuo...

Page 29: ...Fire Connect 2 Stage T stat to both W1 and W2 Single Stage T stat W2 Connect single stage T stat to W2 only BLOWER Speeds HEAT The Heating Blower speed selected by positions 1 2 3 of SW1 CFM tables on...

Reviews: