Refrigeration Maintenance
78
Charging the System
1. Insure that all compartment bulkheads are
open. Ceiling mounted bulkheads should not
be stored close to the evaporator outlets as this
will restrict airflow.
2. Determine the correct charge for the unit as
configured. The actual weight of the charge
may vary somewhat due to length of
refrigerant lines.
3. The unit should still be in Evacuation mode.
Add as much of the charge as possible as
liquid through the discharge service valve and
receiver tank outlet valve.
4. Back seat and crack the discharge service
valve.
5. Back seat the receiver tank outlet valve.
6. Crack the suction service valve.
7. Exit the Evacuation mode by turning the
Zone1/Host On/Off switch Off, and then back
On.
8. Turn all zones On and set all zone setpoints
for the lowest possible temperature to insure
that all zones run in Cool mode. Allow the
unit to start.
9. Cover the condenser as required to maintain
discharge pressure from 325 to 400 psig (2241
to 2758 kPa) and add the remaining charge by
weight as liquid through the suction service
valve.
10. If necessary, continue to add refrigerant until
the ball in the receiver tank sight glass is
floating but is no higher than 1/2 way up the
glass. If they system is overcharged, remove
refrigerant until the ball in the receiver tank
sight glass is floating but is no higher than 1/2
way up the glass.
11. Continue to operate the unit and monitor the
sight glass until all compartment temperatures
are at or below 0 F (-18 C).
12. If the receiver tank sight glass level drops, add
additional refrigerant as required to maintain
refrigerant in the bottom 1/2 of the sight glass.
13. When refrigerant level is correct back seat all
service valves, remove the gauge manifold,
and securely replace valve stem covers with
seals and service port caps before returning
the unit to service.
Summary of Contents for Spectrum DE 30-2
Page 4: ...4...
Page 12: ...Safety Precautions 12...
Page 16: ...Specifications 16...
Page 31: ...Unit Description 31 1 Access Panels 2 Defrost Dampers Figure 12 Back View of Unit 1 2 AGA215...
Page 42: ...Operating Instructions 42...
Page 48: ...Electrical Maintenance 48...
Page 106: ...Structural Maintenance 106...
Page 110: ...Mechanical Diagnosis 110...
Page 114: ...Remote Evaporator Specifications 114...
Page 116: ...Remote Evaporator Maintenance Inspection Schedule 116...
Page 122: ...Remote Evaporator Electrical Maintenance 122...
Page 126: ...Remote Evaporator Refrigeration Service Operations 126...
Page 128: ...Remote Evaporator Structural Maintenance 128...
Page 130: ...Remote Evaporator System Diagnosis 130...
Page 134: ...Wiring and Schematic Diagrams Index 134...
Page 135: ...135 Schematic Diagram Page 1 of 2...
Page 136: ...136 Schematic Diagram Page 2 of 2...
Page 137: ...137 Wiring Diagram Page 1 of 4...
Page 138: ...138 Wiring Diagram Page 2 of 4...
Page 139: ...139 Wiring Diagram Page 3 of 4...
Page 140: ...140 Wiring Diagram Page 4 of 4...