Operating Instructions
53
Change the Humidity Setpoint
1. Press the
S
ETPOINT
key. The Setpoint menu
appears with the cursor in the [TEMP SETP]
line.
2. Press the
F2
or
F3
key to scroll to [HUM
SETP] line.
3. Press the
F4
key to enter a new setpoint. An
Enter Arrow appears in the menu line and the
current setpoint disappears.
4. Enter (type) the new setpoint in the LCD
display using the general purpose keypad. The
cursor moves to the right of the screen as each
key entry is acknowledged and displayed.
NOTE: Always check that the setpoint
entered in the LCD display is correct before
proceeding.
Press and hold the
F4
key until the cursor stops
flashing. The new setpoint is recorded in the
controller and appears in the LCD display.
5. Press the
ESC
key to exit the Setpoint screen.
Changing the Advanced Fresh Air
Management (AFAM) or Advanced
Fresh Air Management Plus
(AFAM+) Setting
For AFAM or AFAM+ operating instructions, see
AFAM+ instructions in the Operating Section.
Figure 30: Setpoint Menu
Setpoint Menu
- Opti-Set
- Temp. Setp.
- Bulb Mode
- Evap Fan Spd
- Defrost Trm.
- Economy Mode
- Hum. Control
- Hum. Setp.
- AFAM
- AFAM Delay
- AFAM Rate
- C02 Max.
NOTE: All screens are NOT
present on all units. The
screens that display on the
controller are determined by
the Controller Software
settings and the options
installed on the unit.
Summary of Contents for 098916
Page 5: ......
Page 11: ...Table of Contents 10...
Page 19: ...Service Guide 18...
Page 28: ...Specifications 27 Figure 2 Physical Specifications AMA313...
Page 41: ...Unit Description Features Options 40...
Page 105: ...Operating Instructions 104...
Page 155: ...Servicing The Unit 154...
Page 187: ...Index 186...
Page 189: ...Wiring and Schematic Diagrams Index 188...
Page 190: ...189 Wiring Schematic...
Page 191: ...190 Wiring Diagram Page 1 of 2...
Page 192: ...191 Wiring Diagram Page 2 of 2...