Diagnosis: Troubleshooting, Status Messages, Alarm Codes
180
120
Suction Pressure Sensor
• Indicate a problem exists with this sensor or its
wiring. The sensor is reading out of the range, or
appears to be open or shorted
PTI Test
• Reading did not decease by 0.15 bar (2.175 psi)
between compressor on and off
Check wiring at J14 and J15 to be correct and
connected
Check J14 and J15 plugs are plugged into MRB
Check voltage at J15 pin12 to be 0.5 – 4.5 volts
Check cable No 1 and cable No. 3 between the
controller and MRB
121
Discharge Pressure Sensor
• Indicate a problem exists with this sensor or its
wiring. The sensor is reading out of the range, or
appears to be open or shorted
PTI Test
• Reading did not increase by 0.15 bar (2.175 psi)
between compressor on and off
Check wiring at J14 and J15 to be correct and
connected
Check J14 and J15 plugs are plugged into MRB
Check voltage at J14 pin11 to be 0.5 – 4.5 volts
Check cable No 1 and cable No. 3 between the
controller and MRB
122
CO2 Sensor Calibration Error
• Occurs during pretrip (PTI) test only
• Sensor reading is less < 17% or > 25%
Replace CO2 sensor
Alarm Codes, Descriptions and Corrective Actions (Continued)
Code
Description
Corrective Action
Summary of Contents for 098916
Page 5: ......
Page 11: ...Table of Contents 10...
Page 19: ...Service Guide 18...
Page 28: ...Specifications 27 Figure 2 Physical Specifications AMA313...
Page 41: ...Unit Description Features Options 40...
Page 105: ...Operating Instructions 104...
Page 155: ...Servicing The Unit 154...
Page 187: ...Index 186...
Page 189: ...Wiring and Schematic Diagrams Index 188...
Page 190: ...189 Wiring Schematic...
Page 191: ...190 Wiring Diagram Page 1 of 2...
Page 192: ...191 Wiring Diagram Page 2 of 2...