ENGLISH
ACCESSORIES SUPPLIED WITH THE UNIT
TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS
No additional charge of compressor oil is necessary.
L Tot. = Total tubing length (L1 + L2 + L3...)
Ln =
Maximum tubing length of a single indoor unit (n=1,2,3...)
REQUIRED AMOUNT OF ADDITIONAL REFRIGERANT
For tubing 1/4 “ - 3/8” = 15g/m
For tubing 1/4 “ - 1/2” = 20g/m
LIMIT OF ELEVATION DIFFERENCE - OUTDOOR UNIT/INDOOR UNIT: 10m (H1, H2, H3, H4)
LIMIT OF ELEVATION DIFFERENCE BETWEEN INDOOR UNITS: 5m (H)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits ø 5
1
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for
reburring)
16. Hex. key
Tools required for installation (not supplied)
REGULATION (EU) No. 517/2014 - F-GAS
The unit contains R410A, a fluorinated greenhouse gas
with a global warming potential (GWP) of 2087.50. Do not
release R410A into the atmosphere.
1.
REDUCTION 1/2F - 3/8M + PIPE UNION 3/8
2.
REDUCTION 3/8F - 1/2M + PIPE UNION 1/2 (2pcs for GR9FI110)
3.
CONICAL COVER
4.
DRAIN TUBE
2
4
1
3
8
TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS
No additional charge of compressor oil is necessary.
L Tot. = Total tubing length (L1 + L2 + L3...)
Ln =
Maximum tubing length of a single indoor unit (n=1,2,3...)
REQUIRED AMOUNT OF ADDITIONAL REFRIGERANT
For tubing 1/4 “ - 3/8” = 15g/m
For tubing 1/4 “ - 1/2” = 20g/m
LIMIT OF ELEVATION DIFFERENCE - OUTDOOR UNIT/INDOOR UNIT: 10m (H1, H2, H3, H4)
LIMIT OF ELEVATION DIFFERENCE BETWEEN INDOOR UNITS: 5m (H)
1.Standard screwdriver
2.Phillips head screwdriver
3.Knife or wire stripper
4.Tape measure
5.Level
6.Sabre saw or key hole saw
7.Hacksaw
8. Core bits ø 5
1
9.Hammer
10.Drill
11.Tube cutter
12.Tube flaring tool
13.Torque wrench
14.Adjustable wrench
15.Reamer (for
reburring)
16.Hex. key
Tools required for installation (not supplied)
REGULATION (EU) No. 517/2014 - F-GAS
The unit contains R410A, a fluorinated greenhouse gas with
a global warming potential (GWP) of 2087.50. Do not
release R410A into the atmosphere.
1. REDUCTION 1/2F - 3/8M + PIPE UNION 3/8
2. REDUCTION 3/8F - 1/2M + PIPE UNION 1/2 (2pcs for GR9FI110)
3. CONICAL COVER
4. DRAIN TUBE
ACCESSORIES SUPPLIED WITH THE UNIT
2
4
1
3
L Tot. (m)
L n (m)
L Tot. (m)
L n (m)
1 UNIT
30
-
50
-
AFEX 080
2 UNITS
40
30
65
30
AFEX 110
3 UNITS
40
30
65
30
4 UNITS
40
30
65
30
AT SHIPMENT
ADDITIONAL REFRIGERANT
EG
16