How to disconnect and/or remove AF ACS B unit
In case of AF ACS B is connected to a normal indoor unit port, the unit must be disconnected exactly as any other air
indoor unit, like hi-wall, flow ceiling, etc.
In case of AF ACS B is connected to the EMX port and by any reason it has to be disconnected and replaced, the
installer has to do this procedure using a refrigerant recovery unit:
- close the valves of EMX port;
- connect the refrigerant recovery unit (R410A);
- recover the refrigerant inside the copper pipes and AF ACS B unit;
- disconnect AF ACS and reconnect another AF ACS B unit;
- make the vacuum;
- restore the refrigerant from recovery unit to the pipe and AF ACS B unit;
- disconnect the recovery unit and re-open the valves of EMX port.
In case AF ACS B must be removed definitively:
- close the valves of EMX port;
- connect the refrigerant recovery unit (R410A);
- recover the refrigerant inside the copper pipes and AF ACS B unit;
- disconnect AF ACS B and reconnect the bypass disconnected during the first installation;
- disconnect the recovery unit;
- make the vacuum on the bypass;
- open the valves of EMX port;
- switch on one of the indoor unit in cooling mode;
- connect the recovery unit to one of the liquid valve of indoor units;
- recover the refrigerant inside the outdoor unit;
- disconnect the recovery unit and be sure that the EMX port valves are open.
How to empty the water tank
In case Emix tank has to be removed or replaced, proceed as follows to empty the water tank:
- close the water inlet valve of Emix tank;
- open the sinks’ taps of users connected to Emix tank;
- connect to tube 2 (see figure) a discharge pipe for the water contained in the tank (in case an expansion vessel is
installed, disconnect it);
- open the cap 1 (see figure);
- turn by 90° the screw 3 (see figure);
- the water will come out from the tank through the connected tube.
2
3
1
Summary of Contents for AF ACS 220 B
Page 22: ...ITALIANO 22 AFEX AF ACS B AF ACS B AF ACS B 8 8 Flussostato non fornito...
Page 23: ...ITALIANO 23 AFEX AF ACS B AF ACS B AF ACS B 11 11 Flussostato non fornito...
Page 24: ...ITALIANO 24 AFEX AF ACS B AF ACS B AF ACS B AF ACS B AF ACS B 8 8 8 8 Flussostato non fornito...
Page 45: ...ENGLISH 45 AFEX AF ACS B AF ACS B AF ACS B 8 8 Flow switch not supplied OTHER INDOOR UNITS...
Page 46: ...ENGLISH 46 AFEX AF ACS B AF ACS B AF ACS B 11 11 Flow switch not supplied OTHER INDOOR UNITS...