And now follow the next steps with max care:
•
Close the valves on the EMX port of outdoor unit (050, 065, 080, 110).
•
Disconnect the bypass from the valves on the EMX port (take care of it because you will need it in case of
dismount of AF ACS B unit).
•
Connect the copper pipes between outdoor unit and AF ACS B for (050, 065, 080, 110).
(warmly suggested a strong insulation in order to avoid loses of precious energy).
•
Perform the vacuum procedure.
•
Open the valves of EMX port.
•
Connect the water to the tank (It is recommended to install an expansion tank of 18 lt, service valves on the
connections of the water circuit in order to make installation and maintenance operations easier and a pipe
on the high pressure safety output of the security valve).
•
It is warmly suggested to install the filter upstream the water circuit and a softener or polyphosphate filter to
avoid limestone.
Refrigerant Circuit
AF ACS B is a component that may be connected to the other types of indoor units at the same time and without spe-
cific limitations by using the special connection for AF ACS B and duly considering the length of the AF ACS B pipe to
be added to the total length set by the outdoor unit (we advise a specific insulation of the AF ACS B pipes to guarantee
the minimum dispersion of energy).
Connection Limits
4
3
2
1
L5
L4
L3
L2
L1
H1
H4
H5
H
H2
H3
STANDARD LOAD
ADDITIONAL LOAD
L Tot (m)
L n (m)
L Tot (m)
L n (m)
AFEX 050
Mono
7,5
-
20
-
Dual
15
12
30
25
AFEX 065
Mono
20
-
35
-
Dual
30
25
45
30
Trial
30
20
45
25
AFEX 080
Mono
30
-
50
-
Dual
40
30
65
30
Trial
40
30
65
30
Quadri
40
30
65
30
AFEX 110
Mono
30
-
50
-
Dual
40
30
65
30
Trial
40
30
65
30
Quadri
40
30
65
30
MAXIMUM HEIGHT DIFFERENCE OUTDOOR UNIT/INDOOR UNIT:
10 m - H1, H2, H3, H4, H5
MAXIMUM HEIGHT DIFFERENCE BETWEEN INDOOR UNITS:
5 m - H
Tot L = Total length of pipes, given by the sum of pipe lengths for each indoor unit (L1+L2+L3...)
L n = Maximum pipe length per single indoor unit (n = 1, 2, 3...)
Summary of Contents for AF ACS 220 B
Page 22: ...ITALIANO 22 AFEX AF ACS B AF ACS B AF ACS B 8 8 Flussostato non fornito...
Page 23: ...ITALIANO 23 AFEX AF ACS B AF ACS B AF ACS B 11 11 Flussostato non fornito...
Page 24: ...ITALIANO 24 AFEX AF ACS B AF ACS B AF ACS B AF ACS B AF ACS B 8 8 8 8 Flussostato non fornito...
Page 45: ...ENGLISH 45 AFEX AF ACS B AF ACS B AF ACS B 8 8 Flow switch not supplied OTHER INDOOR UNITS...
Page 46: ...ENGLISH 46 AFEX AF ACS B AF ACS B AF ACS B 11 11 Flow switch not supplied OTHER INDOOR UNITS...