Thermal Solutions ProtoNode Start-up Guide
Page 9 of 47
3
SETUP FOR PROTONODE
3.1 Record Identification Data
Each ProtoNode has a unique part number located on the side or the back of the unit. This number
should be recorded, as it may be required for technical support. The numbers are as follows:
Model
Part Number
ProtoNode FPC-N34 BACnet
FPC-N34-0643
ProtoNode FPC-N35 LonWorks
FPC-N35-0644
Figure 1: ProtoNode Part Numbers
•
FPC-N34 units have the following 3 ports: BACnet RS-485 + Et Modbus RS-485
•
FPC-N35 units have the following 3 ports: Lo Et Modbus RS-485
3.2 Point Count Capacity and Registers per Device
The total number of registers presented by all the devices attached to the ProtoNode cannot
exceed:
Part number
Total Registers
FPC-N34-0643
1,500
FPC-N35-0644
1,500
Figure 2: Supported Point Count Capacity
Devices
Registers Per Device
RWF40
15
RM7800
37
RWF55
10
Figure 3: Registers per Device