4.2.3 Wiring RM7800 Display Module individually to the ProtoNode
•
On the RM7800 Series; connect A on terminal strip to Tx+ on the ProtoNode connector.
•
Connect B on terminal strip to Rx- on the ProtoNode connector.
•
Connect C (GND) on terminal strip to GND on the ProtoNode connector.
4.2.4 Optional W iring RW F40 or RW F55 & RM7800 display to the ProtoNode
•
If you have Optional Terminal Strip factory wired to RWF40 or RWF55 & RM7800 display module:
•
On the Terninal Stip; connect AO on terminal strip to Tx+ on the ProtoNode connector.
•
Connect BO on terminal strip to Rx- on the ProtoNode connector.
•
Connect SO on terminal strip to the GND on the ProtoNode connector.
Figure 13: RM7800 Series Wiring to the ProtoNode
Figure 14: Optional Terminal Strip (RWF40 or RWF55 & RM7800 Series) Wiring to the
ProtoNode