17
C. Clearances
1. The AMP is approved for 0" clearance to combustible
materials. The clearances for serviceability are
found in Table 5.
2. Minimum clearances from combustible or
noncombustible construction, 0" sides, 0" back,
0" top.
3. It is the installers responsibility to provide enough
clearance for servicing the appliance in the installed
location.
D. Clearances (French)
1. Dégagements minimaux à assurer entre les parois
de l’appareil et les constructions combustibles ou
incombustibles : 0 po (côtés), 0 po (arrière) et 0
po (dessus).
2. Installation dans une garde-robe : assurer un
dégagement de 24 po devant l’appareil.
E. Closet and Alcove installation
1. Include ventilation air openings in closet
installations.
2. Provide a 1" minimum clearance around water
pipes.
3. Follow vent material manufacturer's instructions
for vent clearances.
4. Clearances for closet or alcove Installation:
Front - 48"
Sides - 36"
Rear - 22"
Top - 20"
Table 5: Clearances for Serviceability
. Pre-Installation and Mounting
(continued)
AMP
Model
Front
(In.)
Rear
(In.)
Right
(In.)
Left
(In.)
Top
(In.)
1000
20
22
6
24
20
1250
20
22
6
24
20
1500
24
22
6
24
20
2000
24
22
6
24
20
2500
36
22
6
36
20
3000
36
22
6
36
20
3500
48
22
6
36
20
4000
48
22
6
36
20
NOTICE
NOTICE
This appliance is approved for zero inch clearance
to combustible or noncombustible material, but
installing the appliance with smaller than the
clearances for serviceability will limit access for
maintenance.
Consult local codes and inspectors before installing
multiple appliances adjacent to each other with
zero clearance.
Closet and alcove installation can cause elevated
temperatures. Follow the required clearances and
use only stainless steel, CPVC, or polypropylene
vent material.