Default Settings: 

 

55°F Heat Set Point

 

 

3°F Differential

 

 
At the default settings the heater turns on at 52°F and operates until temperature has reached 55°F.  
Refer to Digital Temperature Controller Programming section for details on changing these 
parameters. 
 
Corrosion Protection 
 
The copper tubing and aluminum fins used in the air conditioner refrigeration circuit are subject to 
damage in the presence of corrosive chemicals such as hydrogen sulfide, chlorine, etc.  Condenser 
and evaporator coils are available with electrostatically applied epoxy coating to prevent corrosion.  
Three options are available to protect the air conditioner from premature failure due to corrosion. 
 
 

A-Level Protection: 

 

 

Coated condenser coils. Included in NEMA Type 4X units. Available in NEMA Types 
12 and 4.  

 

B-

 Level Protection:

 

 

 

Coated condenser and evaporator coils. Available in NEMA Types 12, 4 and 4X. 

 

C-

 Level Protection:

 

 

 

Coated condenser and evaporator coils plus coated refrigeration tubing. All copper 
joints brazed with 45% silver solder, then epoxy painted.  Available on NEMA Types 
12, 4 and 4X units.  

Note

: C-Level Protection is strongly recommended for 4X 

applications requiring 316 stainless steel.

 

 
Low Ambient 
 
This option consists of circuitry to protect the compressor in a low ambient temperature environment.  
The low ambient package is designed to provide an optimum constant low current in the compressor 
motor during the non-cooling state.  This option provides internal heat to the compressor to protect it 
from stalls and hard starts during long periods of compressor off state. 
 
Dry Contact 
 
This option provides an early warning capability to your enclosure to aid in the protection of your 
expensive equipment.  The Dry Contact is programmed with an individual dry contact set point to 
monitor the enclosure temperature limit that you require.  When the enclosure temperature has 
exceeded the maximum limit, the Form C gold plated contact will activate to notify you that there is a 
problem in achieving your cooling set point. 
 

 

 

Default Settings: 

 

105°F Dry Contact High Temperature Alarm Set Point

 

 

2°F Recovery Differential

 

 

3min Temperature Alarm Delay

 

 

 
At the default settings the Dry Contact initial conditions are normally open and/or normally closed.  
When the unit is powered on and the temperature exceeds 105°F for a period longer than 3 minutes 
the Dry Contact will activate. At this time the normally open contact will close and the normally closed 
contact will open. This state will remain until the temperature has decreased to 103°F.   

Summary of Contents for TM061 Series

Page 1: ...User Technical Manual TM061 TM081 Series Rev 1 7...

Page 2: ...le delay updated Remote Controller option description 1 6 10 01 18 B Slotnick Updated warranty unit specifications 1 7 10 02 18 B Slotnick Updated mounting instructions added sealed enclosure warning...

Page 3: ...Moving the Air Conditioner 5 Unit Label 5 Operation 6 Preliminary Testing 6 Mounting the Air Conditioner 7 Unit Specifications 8 Options 10 System Faults 13 Digital Temperature Controller Programming...

Page 4: ...cting the Equipment Thermal Edge air conditioning equipment is designed manufactured and packed to prevent damage from normal handling shock and vibration during shipment It is necessary to inspect yo...

Page 5: ...he template below and keep this information in a safe place for warranty and ordering parts To prevent damage to equipment electrical panel and wiring and to prevent personal injury assure that the po...

Page 6: ...r conditioner is the proper voltage and phase Check the electric power source for proper ground wire and neutral wire installation per 2008 NEC Assure that the electric power is protected by a circuit...

Page 7: ...closure roof Be careful not to damage the gasket on the bottom of the air conditioner by trapping tools or objects between the air conditioner and the enclosure From inside the enclosure install the p...

Page 8: ...ded Fuse Selection Amps KVA Rating K Watts Refrigerant Type Refrigerant Amount ounces Low High Unit Pressures psi TM061126 99 121 35 7 10 6 2 20 Amp Class CC CCMR Time Delay 1 3 R438a 24 120 320 TM061...

Page 9: ...ses are not recommended of Ampere Rating Opening Time 110 15min Minimum 125 1hr Maximum 200 12sec Minimum 4min Maximum 2 SCCR rating is based on the SCCR rating for the circuit protection device insta...

Page 10: ...s Note C Level Protection is strongly recommended for 4X applications requiring 316 stainless steel Low Ambient This option consists of circuitry to protect the compressor in a low ambient temperature...

Page 11: ...r Available Heater capacities range from 100 Watts to 950 Watts Default Settings 55 F Heat Set Point 3 F Differential At the default settings the heater output turns on at 52 F and operates until the...

Page 12: ...control all settings from a remote location with an applicable Allen Bradley Rockwell PLC A DIN rail is required inside the electrical enclosure for mounting the communication components Full specifi...

Page 13: ...time delay A thermal overload protects the compressor against faults In the event that the snowflake status LED is not flashing on the display and the compressor is not running an internal fault may...

Page 14: ...value 4 Use the UP or DOWN arrow key to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds without pressing a k...

Page 15: ...45 F for 3 minutes after initial 30 min start up delay No Output 2 HA2 Condenser High Temperature Alarm P2 145 F for 3 minutes Compressor Off 2 LA2 Condenser Low Temperature Alarm P2 50 F for 3 minute...

Page 16: ...life of the Air Conditioner Air Filter Service If the air conditioner is equipped with an optional condenser filter remove the filter and wash if washable or replace if not washable Dry thoroughly be...

Page 17: ...VAC Compressor Thermal Overload TM061 31552 2 for 120VAC 31574 2 for 230VAC 480VAC TM081 31020 2 for 120VAC 31080 2 for 230VAC 480VAC Gasket Installation Kit 71318 TM68 Evaporator Fan 42100 1 1 for 12...

Page 18: ...s on position ON OFF Toggle Switch then Retry Verify input power meets voltage requirements as shown in the UL label YES If problem is still present contact technical support Unit Overheats Insufficie...

Page 19: ...sor Use meter 3 Check for faulty evaporator fan 3 Measure Temperature at Evaporator Verify Heat Load Requirements Is unit capacity adequate for internal head load Possible low refrigerant Is compresso...

Page 20: ...ind controller CA YES NO Check Low Pressure Switch Connections and Verify Pressure switch is closed Use meter 3 P1 or P2 NO YES Check probe connections potential faulty probe LA LA2 HA HA2 YES Refer t...

Page 21: ...g e Physical Dimensions Water overflow excessive Check drain is it plugged YES NO Clean condensate pan and drain add 1 tbsp bleach to upper pan monthly to kill mold Is Air Conditioner sealed against...

Page 22: ...al edge com SP ENG 211 000 17 Rev 1 7 22 P a g e Electrical Schematics System Schematic Digital Controller Schematic Note Schematics apply to all voltages optional accessories wiring not provided in t...

Page 23: ...dge factory in Dallas Texas Use of equipment for other than its designed purpose or operating conditions Operation in harsh oily corrosive or other abnormal environmental conditions without the proper...

Page 24: ...Number Serial Number Customer name and contact info email phone number and address Shipping method Pack unit in a suitable packing for shipment preferably the original packaging if available Air Condi...

Page 25: ...sembly channels facing UP 4 Starting from the left connect the wires by inserting them into the lower receptacles located on the front of connector in the following order NOTE If using stranded wires...

Reviews: