User Setup – Discharge Control Setup
Discharge Control Setup Screen
The EC fans modulate in order to maintain the
discharge refrigerant pressure setpoint.
Figure 42 - User Setup – Discharge Control Setup
Screen
Table 7 – Discharge Control Setup Parameters
Menu Item
Description
Default Value
Mode
In Auto Mode, the fans adjust to
maintain optimum performance.
In manual mode, it holds to the
Manual Mode Position input
valve.
AUTO
Kp Proportional
PID
value
0.010
Ti Integral
PID
value
250.000
Td Derivative
PID
value
0.000
Discharge
Setpoint
Discharge Setpoint Value
350 PSIG
Low Temp
Setpoint
Low temp setpoint relating to low
percent setpoint – (During the
start sequence)
45°F (7°C)
User Setup – Dynmic Lift Setup
Dynamic Lift Setup Screen
The Dynamic Lift control logic adjusts the chiller
head pressure to improve energy efficiency.
Figure 43 - User Setup – Dynamic Lift Setup Screen
Table 8 – Dynamic Lift Parameters
Menu Item
Description
Default Value
Action
Enable or Disable the Dynamic lift
feature
ENABLED
Kp Proportional
PID
value
0.010
Ti Integral
PID
value
250.000
Td Derivative
PID
value
0.000
EXV Setpoint Optimal EXV target position
95%
User Setup - Modbus RTU Setup
Modbus RTU Setup Screen
This Modbus RTU Setup Screen provides the ability
to modify communication parameters. Default
Modbus RTU Settings: Baud-57600, Data Length-8,
Parity-Odd, Stop Bits-1.