background image

12

Ultra-Aire XT105H, XT155H, and XT205H Installer’s & Owner’s Manual

Compressor is not running. Dehumidification is being called 
for. No fan call.

1.  Defective compressor run capacitor (Sec. 7.6).
2.  Loose connection in compressor circuit.
3.  Defective compressor overload (Sec. 7.6A).
4.  Defective compressor (Sec. 7.6).
5.  Defrost thermostat open.

Compressor cycles on and off. Dehumidification is being called 
for. No fan call

1.   Low ambient temperature and/or humidity causing unit to 

cycle through defrost mode.

2.  Defective compressor overload (Sec. 7.6A).
3.  Defective compressor (Sec. 7.6).
4.  Defrost thermostat defective (Sec. 7.8).
5.  Dirty air filter(s) or air flow restricted.

Fan is not running. Dehumidification or fan is being called for

1.  Loose connection in fan circuit.
2.  Obstruction prevents fan impeller rotation.
3.  Defective fan.
4.  Defective fan relay.

Low dehumidification capacity (evaporator is frosted 
continuously). Dehumidification is being called for

1.  Defrost thermostat loose or defective (Sec. 7.8).
2.  Low refrigerant charge
3.  Dirty air filter(s) or air flow restricted.
4.  Excessively restrictive ducting connected to unit.

No ventilation. Ventilation is being called for.

1. Loose connection in ventilation control circuit 
2. Loose connection in damper power circuit. 
3. Defective fresh air damper.

Unit removes some water, but not as much as expected. 

1. Air temperature and/or humidity have dropped. 
2. Humidity meter and or thermometer used are out of 
calibration. 
3. Unit has entered defrost cycle (Sec. 5.8). 
4. Air filter dirty (Sec. 4.1 & 4.2). 
5. Defective defrost thermostat (Sec 5.8). 
6. Low refrigerant charge (Sec. 5.4). 
7. Air leak such as loose cover or ducting leaks. 
8. Defective compressor (Sec. 5.6). 
9. Restrictive ducting (Sec. 2.4). 
10. Optional Condensate Pump Safety Switch open (Sec 5.11). 

Unit Test to determine problem: 

1. Detach field control wiring connections from main unit. 
2.  Connect the yellow and green pigtails from the main unit 

together; only the impeller fan should run. Disconnect the 
wires. 

3.  Connect the yellow and blue pigtails from the main unit 

together; the compressor and impeller fan should run. 

4.  If these tests work, the main unit is working properly. You 

should check the control panel and field control wiring for 
problems next. 

5.  Remove the control panel from the mounting box and detach 

it from the field installed control wiring. Connect the blue, 
yellow, and green wires from the control panel directly to the 
corresponding colored pigtails on the main unit. Leave the 
violet, white and red wires disconnected! 

6.  Turn on the fan switch; the impeller fan should run. Turn off 

the fan switch. 

7.  Turn on the humidity control; the compressor and impeller fan 

should run. 

8.  If these tests work, the problem is most likely in the field 

control wiring. 

7.4 Refrigerant Charging 

If the refrigerant charge is lost due to service or a leak, a new 
charge must be accurately weighed in. If any of the old charge is 
left in the system, it must be recovered before weighing in the new 
charge. Refer to the unit nameplate for the correct charge weight 
and refrigerant type. 

7.5 Impeller Fan Replacement 

The motorized impeller fan is a unitary assembly consisting of the 
motor and impeller fan. If defective, the complete assembly must 
be replaced. 

1. Unplug the power cord. 
2. Remove the cabinet access panel. 
3.  Remove the screw attaching the impeller fan support bracket 

to the base. 

4.  Disconnect the impeller fan leads inside the electric box. 
5.  Remove fan/bracket assembly by removing 3 screws from 

the bracket and inlet ring assembly. 

6.  Remove the defective impeller fan from the bracket and 

replace with it with the new impeller fan. 

7.  Reassemble the new impeller fan by reversing the above 

procedure. Note: There are two pins on the backside of the 
cabinet that must align with the two holes in the impeller fan 
support bracket. 

7.6 Compressor/Capacitor Replacement  

This compressor is equipped with a two terminal external 
overload and a run capacitor, but no start capacitor or relay  
(See Figure 4). 

Summary of Contents for Ultra Aire XT105H

Page 1: ...outdoor air may be ducted to the unit via a six inch round duct This provides fresh air to dilute pollutants and replenish oxygen content in the building The amount of fresh air ventilation can be reg...

Page 2: ...2 Ultra Aire XT105H XT155H and XT205H Installer s Owner s Manual...

Page 3: ...3 Ultra Aire XT105H XT155H and XT205H Installer s Owner s Manual...

Page 4: ...are Foot Typical Minimum Performance 80 F and 60 RH Water Removal Efficiency 105 Pints Day 8 8 Pints kWh 155 Pints Day 7 3 Pints kWh 205 Pints Day 5 7 Pints kWh Duct Connections Inlet 10 Round Duct Co...

Page 5: ...FOR HVAC INSTALLER ONLY 5 Ultra Aire XT105H XT155H and XT205H Installer s Owner s Manual...

Page 6: ...6 Ultra Aire XT105H XT155H and XT205H Installer s Owner s Manual...

Page 7: ...Ultra Aire Dehumidifier 7 Ultra Aire XT105H XT155H and XT205H Installer s Owner s Manual...

Page 8: ...T155H and XT205H Installer s Owner s Manual P N 4028539 with remote P N 4028407 Ultra Aire Dehumidifier RED YELLOW BLUE GREEN or BROWN WHITE Internal Connections OPTIONAL DAMPER 24 VAC DMP COMP FAN Ul...

Page 9: ...y the transformer Dehumidifier on Connect yellow and blue wires Fan only on Connect yellow and green or brown wires Accessory power 24volt AC power supply available for HVAC accessories between yellow...

Page 10: ...10 Ultra Aire XT105H XT155H and XT205H Installer s Owner s Manual DEH 3000 DEH 3000R DEH 3000 DEH 3000R Part No 4028539 Part No 4028407...

Page 11: ...peration and no further oiling is required 6 4 Optional Fresh Air Return Check and clean the screen on the outdoor fresh air return seasonally The screen may become plugged during the seasons when the...

Page 12: ...ls from the main unit together only the impeller fan should run Disconnect the wires 3 Connect the yellow and blue pigtails from the main unit together the compressor and impeller fan should run 4 If...

Page 13: ...a very corrosive acid and water These contaminants must be carefully removed otherwise even small residues will attack replacement compressor motors and cause failures The following procedure is effe...

Page 14: ...ction tube between the accumulator and the compressor It will automatically shut the compressor off if the low side refrigerant temperature drops due to excessive frost formation on the evaporator coi...

Page 15: ...ONTROL WIRING Electric Schematics of the Ultra Aire XT N O WHT 4 UNIT E BOX 1 59 1413 WHT 4 BLK 1 8 2 3 2 2 2 3 7 5 COM COM 115V 24V WHT 6 BLU 7 YEL 6 RED 1 GRN 5 RED 6 5 WHT 6 BLU 2 BLU 2 BLK 1 BRN 3...

Page 16: ...029714 1 XT155 Compressor Overload NOT SHOWN 4031574 1 XT205 Compressor Overload LOCATED IN COMPRESSOR CAP Item Part No Qty Description 8 4032196 1 XT105 Impeller 8 4026657 1 XT155 Impeller 8 4031089...

Page 17: ...Condensate Pump Kit External 4023672 1 Duct Damper 6 Diameter Electrically Actuated 4025560 1 Switch Black SPDT On Off 4024369 1 Merv 11 Standard Filter 20 x 16 x 2 4032221 1 Filter Box Needed when M...

Page 18: ...is shut release the door latch Collar Install Remove the 2 round ducts oval duct seal and small bag of mounting hardware from inside the rectangle opening Adhere seal onto the back of oval duct and mo...

Page 19: ...ts related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibilit...

Page 20: ......

Reviews: