Therma-Stor Ultra Aire XT105H Owner'S Manual Download Page 13

7.6A Checking Compressor Motor Circuits 

Perform the following tests if the impeller fan runs but the 
compressor does not with the fan switch and ventilation timer OFF 
and the humidity control ON. 

1.  Unplug the unit; remove the cabinet side and the electrical 

connection cover on the compressor top. 

2.  Plug in the unit and turn the humidity control to ON. Check for 

110 volts from compressor terminal R to overload terminal 
3 using an AC voltmeter. If voltage is present, go to step 
3. If no voltage, there may be a loose connection in the 
compressor circuit. Test each component for continuity. See 
the appropriate section if a defect is suspected. 

3.  Unplug the unit, and then disconnect the red and yellow wires 

from compressor terminals R & S. Using an ohmmeter check 
continuity between the points listed below. 

4.  Compressor terminals C and S: No continuity indicates an 

open start winding. The compressor must be replaced. 
Normal start winding resistance is 3 to 7 ohms. 

5.  Compressor terminals C and R: No continuity indicates an 

open run winding. The compressor must be replaced. Normal 
run winding resistance is .5 to 2 ohms. 

6.  Compressor terminal C and overload terminal 1: No continuity 

indicates a defective overload lead. 

7.  Overload terminals 1 and 3: If there is no continuity, the 

overload may be tripped. Wait 10 minutes and try again. 
If there is still no continuity, it is defective and must be 
replaced. 

8.  Compressor terminal C and compressor case: Continuity 

indicates a grounded motor. The compressor must be 
replaced. 

9.  Disconnect the wires from the run capacitor. Set the 

ohmmeter to the Rx1 scale. The capacitor is shorted and 
must be replaced if continuity exists across its terminals. 
If there is no needle movement with the meter set on the 
Rx100000 scale, the capacitor is open and must be replaced. 

10.  Reconnect the wires to the compressor and capacitor. Plug 

in and turn on the unit. If the compressor fails to start, 
replace the run capacitor. 

7.6B Replacing a Burned Out Compressor 

The refrigerant and oil mixture in a compressor is chemically 
very stable under normal operating conditions. However, when an 
electrical short occurs in the compressor motor, the resulting high 
temperature arc causes a portion of the refrigerant oil mixture to 
break down into carbonaceous sludge, a very corrosive acid, and 
water. These contaminants must be carefully removed otherwise 
even small residues will attack replacement compressor motors 
and cause failures. 

The following procedure is effective only if the system is monitored 
after replacing the compressor to insure that the clean up was 
complete. 

1.  This procedure assumes that the previously listed compressor 

motor circuit tests revealed a shorted or open winding. 

2.  Remove and properly dispose of the system charge. DO NOT 

vent the refrigerant or allow it to contact your eyes or skin. 

3.  Remove the burned out compressor. Use rubber gloves if 

there is any possibility of contacting the oil or sludge. 

4.  To facilitate subsequent steps, determine the type of burn 

out that occurred. If the discharge line shows no evidence 
of sludge and the suction line is also clean or perhaps has 
some light carbon deposits, the burn out occurred while the 
compressor was not rotating. Contaminants are therefore 
largely confined to the compressor housing. A single 
installation of liquid and suction line filter/driers will probably 
clean up the system. 

If sludge is evident in the discharge line, it will likely be found in 
the suction line. This indicates the compressor burned out while 
running. Sludge and acid have been pumped throughout the 
system. Several changes of the liquid and suction filter/driers will 
probably be necessary to cleanse the system. 

5.  Correct the system fault that caused the burn out. Consult the 

factory for advice. 

6.  Install the replacement compressor with a new capacitor and 

an oversized liquid line filter. 

In a running burn out, install an oversized suction line filter/drier 
between the accumulator and compressor. Thoroughly flush the 
accumulator with refrigerant to remove all trapped sludge and to 
prevent the oil hole from becoming plugged. A standing burn out 
does not require a suction line filter/drier. 

7.  Evacuate the system with a good vacuum pump and accurate 

vacuum gauge. Leave the pump on the system for at least an 
hour. 

8.  Operate the system for a short period of time, monitoring the 

suction pressure to determine that the suction filter is not 
becoming plugged. Replace the suction filter/drier if pressure 
drop occurs. If a severe running burn out has occurred, 
several filter/driers may have to be replaced to remove all of 
the acid and moisture. 

NOTE: NEVER use the compressor to evacuate the system or 
any part of it. 

13

Ultra-Aire XT105H, XT155H, and XT205H Installer’s & Owner’s Manual

Summary of Contents for Ultra Aire XT105H

Page 1: ...outdoor air may be ducted to the unit via a six inch round duct This provides fresh air to dilute pollutants and replenish oxygen content in the building The amount of fresh air ventilation can be reg...

Page 2: ...2 Ultra Aire XT105H XT155H and XT205H Installer s Owner s Manual...

Page 3: ...3 Ultra Aire XT105H XT155H and XT205H Installer s Owner s Manual...

Page 4: ...are Foot Typical Minimum Performance 80 F and 60 RH Water Removal Efficiency 105 Pints Day 8 8 Pints kWh 155 Pints Day 7 3 Pints kWh 205 Pints Day 5 7 Pints kWh Duct Connections Inlet 10 Round Duct Co...

Page 5: ...FOR HVAC INSTALLER ONLY 5 Ultra Aire XT105H XT155H and XT205H Installer s Owner s Manual...

Page 6: ...6 Ultra Aire XT105H XT155H and XT205H Installer s Owner s Manual...

Page 7: ...Ultra Aire Dehumidifier 7 Ultra Aire XT105H XT155H and XT205H Installer s Owner s Manual...

Page 8: ...T155H and XT205H Installer s Owner s Manual P N 4028539 with remote P N 4028407 Ultra Aire Dehumidifier RED YELLOW BLUE GREEN or BROWN WHITE Internal Connections OPTIONAL DAMPER 24 VAC DMP COMP FAN Ul...

Page 9: ...y the transformer Dehumidifier on Connect yellow and blue wires Fan only on Connect yellow and green or brown wires Accessory power 24volt AC power supply available for HVAC accessories between yellow...

Page 10: ...10 Ultra Aire XT105H XT155H and XT205H Installer s Owner s Manual DEH 3000 DEH 3000R DEH 3000 DEH 3000R Part No 4028539 Part No 4028407...

Page 11: ...peration and no further oiling is required 6 4 Optional Fresh Air Return Check and clean the screen on the outdoor fresh air return seasonally The screen may become plugged during the seasons when the...

Page 12: ...ls from the main unit together only the impeller fan should run Disconnect the wires 3 Connect the yellow and blue pigtails from the main unit together the compressor and impeller fan should run 4 If...

Page 13: ...a very corrosive acid and water These contaminants must be carefully removed otherwise even small residues will attack replacement compressor motors and cause failures The following procedure is effe...

Page 14: ...ction tube between the accumulator and the compressor It will automatically shut the compressor off if the low side refrigerant temperature drops due to excessive frost formation on the evaporator coi...

Page 15: ...ONTROL WIRING Electric Schematics of the Ultra Aire XT N O WHT 4 UNIT E BOX 1 59 1413 WHT 4 BLK 1 8 2 3 2 2 2 3 7 5 COM COM 115V 24V WHT 6 BLU 7 YEL 6 RED 1 GRN 5 RED 6 5 WHT 6 BLU 2 BLU 2 BLK 1 BRN 3...

Page 16: ...029714 1 XT155 Compressor Overload NOT SHOWN 4031574 1 XT205 Compressor Overload LOCATED IN COMPRESSOR CAP Item Part No Qty Description 8 4032196 1 XT105 Impeller 8 4026657 1 XT155 Impeller 8 4031089...

Page 17: ...Condensate Pump Kit External 4023672 1 Duct Damper 6 Diameter Electrically Actuated 4025560 1 Switch Black SPDT On Off 4024369 1 Merv 11 Standard Filter 20 x 16 x 2 4032221 1 Filter Box Needed when M...

Page 18: ...is shut release the door latch Collar Install Remove the 2 round ducts oval duct seal and small bag of mounting hardware from inside the rectangle opening Adhere seal onto the back of oval duct and mo...

Page 19: ...ts related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibilit...

Page 20: ......

Reviews: