The Ultra-Aire 65H generates condensate. Install a 3/4" male 
nominal pipe thread adapter to the drain pan. It is necessary 
to assemble your own drain pipe assembly utilizing 3/4" 
PVC pipe to get the condensate to a floor or other drain. Pipe 
is commonly available in 10’ lengths from building supply, 
plumbing or hardware stores. Grade of pitch should be 1" 
per 10'.  

4.3A Lifting Condensate 

A condensate pump may installed if lift is required to dispose 
of the condensate.  

4.3B Condensate Pump Kit (4028085)

A condensate pump kit is available from the factory for use 
with the Ultra-Aire 65H and provides 15' of lift. Condensate is 
automatically pumped to a remote location when the water 
level in the pump’s reservoir rises to close the float switch. 
The pump also contains a safety float switch. The white leads 
from this switch extend from beneath the pump cover. This 
switch should be installed in series with the field wire that 
connects the blue (#5) lead from the Ultra-Aire 65H to the 
the control panel. If the pump fails, this switch opens the 
compressor control circuit and stops water production before 
the reservoir overflows. The Ultra-Aire 65H will continue to 
ventilate or circulate air as normal, but will not dehumidify 
until this switch closes. 

4.4 Ducting 

CAUTION

Replacing the filter requires the return duct to be 

removed. Failure to use flex duct will prevent filter 

access. Three feet of flex duct should be adequate to 

access the filter.

For the ideal installation, draw air from the central part of the 
home and return it to the isolated areas of the home like the 
bedrooms, den, utility room, or family room. The ductwork 
of the existing heating system can be used to supply air to 
the home. If the existing supply goes to isolated areas of 
the home, discharge the supply of the Ultra-Aire 65H into 
the supply of the existing heating system. Installation of a 
separate supply duct to the Ultra-Aire 65H from a central 
area is recommended. 

4.4A Supply Air 

CAUTION

DO NOT draw air directly from the kitchen, laundry, or 

isolated basement.

 

You may draw air from a basement that is open to the home. 
All flexible ducting connected to the Ultra-Aire 65H should be 
UL listed. 

A short piece of flexible ducting on all Ultra-Aire 65H duct 
connections is recommended to reduce noise and vibration 
transmitted to rigid ductwork in the structure. Ducting the 
Ultra-Aire 65H as mentioned requires consideration of the 
following points: 

Duct Sizing: For total duct lengths up to 25', use a minimum 
8" diameter round or equivalent rectangular. For longer 
lengths, use a minimum 10" diameter or equivalent. Grills 
or diffusers on the duct ends must not excessively restrict 
airflow.

Connecting to existing HVAC systems:

  An optional 8" 

check backdraft damper is available from the factory to 
prevent reverse air flow through the Ultra-Aire 65H. If the 
Ultra-Aire 65H is ducted to the supply of an air handler, the 
check damper should be placed in the Ultra-Aire 65H supply 
duct.  

CAUTION

Contact the factory when connecting to a static pressure 

of greater than or equal to +.5" WG.

FOR HVAC INSTALLER ONLY

5

Ultra-Aire 65H Installer’s & Owner’s Manual

Flex Duct

Duct Collar

Hard Duct

|

      3 Feet        

|

Condensate Pump Kit (4028085) shown installed. Available from 

your dealer or Therma-Stor. Call 1-800-533-7533.

Summary of Contents for Ultra-Aire 65H

Page 1: ...tandard MERV 14 optional n Compact design n 5 year warranty P O Box 8680 Madison WI 53708 TOLL FREE 1 800 533 7533 www thermastor com sales thermastor com TS 422c INSTALLER S OWNER S MANUAL HVAC INSTA...

Page 2: ...4D Installation in an Attic 6 4 4E Installation in a Structure with No Forced Air HVAC System 7 4 4F Ducting for High Efficiency Filtration 7 4 5 Compressor Release and Noise Abatement 7 4 6 Controls...

Page 3: ...edrooms den utility room or family room The ductwork of the existing heating system can be used to supply air to the home 2 Registrations The Ultra Aire 65H conforms to UL STD 474 and CSA Standard C22...

Page 4: ...al electrical codes for any further information Therma Stor LLC offers a family of control devices for use with the Ultra Aire 65H The controls are to be located remotely from the unit and located in...

Page 5: ...he isolated areas of the home like the bedrooms den utility room or family room The ductwork of the existing heating system can be used to supply air to the home If the existing supply goes to isolate...

Page 6: ...stallation Install a separate 8 return for the Ultra Aire 65H in a central area of the structure Optional Duct the supply of the Ultra Aire to a 8 x 8 x 8 tee damper adjusted to 20 open to the basemen...

Page 7: ...es the return duct to be removed Failure to use flex duct will prevent filter access Three feet of flex duct should be adequate to access the filter 4 6 Controls All control panels should be mounted i...

Page 8: ...8 Ultra Aire 65H Installer s Owner s Manual ATTENTION INSTALLER...

Page 9: ...ncy and may cause the compressor to cycle off and on unnecessarily on the defrost control DO NOT operate the unit without a filter or with a less effective filter Operating the unit without a filter o...

Page 10: ...Optional Parts List Ultra Aire 65H Indoor Air Quality System Part No Description 4027158 Filter MERV 11 4028085 Pump Kit 4028111 Hang Kit 4023647 8 Gravity Damper 4020646 8 Butterfly Damper 4027415 8...

Page 11: ...66 Defrost Timer 4027149 Indicator Light 4027151 Overflow Switch 4027161 Transformer FOR HOMEOWNER ROUTINE MAINTENANCE Part No Description 4027158 Air Filter MERV 11 4027422 4 Pack 4027427 12 Pack The...

Page 12: ...t to a high pressure and temperature 10 2 Troubleshooting Neither fan nor compressor running Dehumidification is being called for No fan call 1 Unit unplugged or no power to outlet 2 Humidity control...

Page 13: ...a new charge must be accurately weighed in If any of the old charge is left in the system it must be recovered before weighing in the new charge Refer to the unit nameplate for the correct charge wei...

Page 14: ...y Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point...

Page 15: ...sts related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibili...

Page 16: ...n any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2008 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phon...

Reviews: