Therma-Stor Ultra-Aire 65H Manual Download Page 4

n

  

4.1B Space 

Location should have enough clearance to handle the unit’s 
overall dimensions as well as the necessary return/supply 
ductwork to the unit. 

n

  

4.1C Low Voltage Wiring 

Unit location should be in an area where field wiring the 
remote controls (low voltage) to the unit will be possible. 

n

  

4.1D Back-Draft Damper

 (P/N 4023647)

It is recommended that a back draft damper be used in 
the discharge duct of the Ultra-Aire 65H, especially when 
connecting to the supply ducting system. The backdraft 
damper prevents supply air from counter flowing through 
the Ultra-Aire 65H when it is not operating. The unit location 
should be chosen to allow installation of this accessory. 

n

  

4.1E Support Structure and Suspension 

Place the Ultra-Aire 65H on supports to raise the base of the 
unit. Do not place the Ultra-Aire 65H directly on structural 
building members without vibration absorbers or unwanted 
noise may result. 

The Ultra-Aire 65H may be suspended with a hang kit 
(4028111) or a suitable alternative from structural members, 
as long as the suspending assembly supports the Ultra-Aire 
65H’s base in its entirety. Do not hang the Ultra-Aire 65H 
from the cabinet. Remember to place a drain pan under the 
unit if it is suspended above a finished area or above an area 
where water leakage could cause damage. 

4.2 Electrical Requirements 

 

WARNING!

 

 

WARNING: DO NOT ALLOW THE YELLOW LEAD FROM 

THE ULTRA-AIRE TO CONTACT THE RED LEAD FROM THE 

ULTRA-AIRE OR DAMAGE TO THE TRANSFORMER WILL 

RESULT. 

The Ultra-Aire 65H plugs into a common grounded 
115VAC outlet. The device draws 5.5 Amps under normal 
operating conditions. If used in an area which may become 
wet, a ground fault interrupter (GFI) protected circuit is 
recommended. Please, consult local electrical codes for any 
further information. 

Therma-Stor LLC offers a family of control devices for use 
with the Ultra-Aire 65H. The controls are to be located 
remotely from the unit and located in the space to be 
conditioned. The controls are low voltage (24 volt) and should 
be connected to the Ultra-Aire 65H with low voltage wire 
(thermostat or other appropriate). 

CAUTION 

Do not install the control panel where it may not 

accurately sense the relative humidity such as near 

HVAC supply registers, near exterior doors, on an outside 

wall, near a window, or near a water source. 

The installer must supply the wiring between the Ultra-Aire 
65H and the control panel. Be sure to safely route the control 
wiring to prevent damage during installation. 

CAUTION 

Do not cross wires when connecting the Ultra-Aire 65H and 
the remote control panel or damage to the transformer may 
result. The remote controls of the Ultra-Aire 65H are powered 
by a low voltage circuit (24VAC) and must NEVER contact or 
be connected to a high voltage circuit. 

The control wires leaving the Ultra-Aire 65H and the remote 
control panels are numbered and color-coded to prevent 
confusion. Some of the control wires leaving the Ultra-Aire 
65H may not be used with certain control panels and should 
be left unconnected with wire nuts taped onto the stripped 
ends for safety. Be sure to consult the electrical schematic in 
this manual or inside the access panel of the Ultra-Aire 65H 
before making control connections. 

4.3 Condensate (Water) Removal 

CAUTION

A trap in the drain line is preferred, but not required for 
the unit to drain properly. Local codes may require a trap. 
Use care to keep the pipe assembly as flat to the floor as 
possible. Kinks and/or humps will prevent proper drainage.

FOR HVAC INSTALLER ONLY

4

Ultra-Aire 65H Installer’s & Owner’s Manual

Hang Kit (4028111) shown suspending a UA65H. Available 

from your dealer or Therma-Stor. Call 1-800-533-7533.

Summary of Contents for Ultra-Aire 65H

Page 1: ...tandard MERV 14 optional n Compact design n 5 year warranty P O Box 8680 Madison WI 53708 TOLL FREE 1 800 533 7533 www thermastor com sales thermastor com TS 422c INSTALLER S OWNER S MANUAL HVAC INSTA...

Page 2: ...4D Installation in an Attic 6 4 4E Installation in a Structure with No Forced Air HVAC System 7 4 4F Ducting for High Efficiency Filtration 7 4 5 Compressor Release and Noise Abatement 7 4 6 Controls...

Page 3: ...edrooms den utility room or family room The ductwork of the existing heating system can be used to supply air to the home 2 Registrations The Ultra Aire 65H conforms to UL STD 474 and CSA Standard C22...

Page 4: ...al electrical codes for any further information Therma Stor LLC offers a family of control devices for use with the Ultra Aire 65H The controls are to be located remotely from the unit and located in...

Page 5: ...he isolated areas of the home like the bedrooms den utility room or family room The ductwork of the existing heating system can be used to supply air to the home If the existing supply goes to isolate...

Page 6: ...stallation Install a separate 8 return for the Ultra Aire 65H in a central area of the structure Optional Duct the supply of the Ultra Aire to a 8 x 8 x 8 tee damper adjusted to 20 open to the basemen...

Page 7: ...es the return duct to be removed Failure to use flex duct will prevent filter access Three feet of flex duct should be adequate to access the filter 4 6 Controls All control panels should be mounted i...

Page 8: ...8 Ultra Aire 65H Installer s Owner s Manual ATTENTION INSTALLER...

Page 9: ...ncy and may cause the compressor to cycle off and on unnecessarily on the defrost control DO NOT operate the unit without a filter or with a less effective filter Operating the unit without a filter o...

Page 10: ...Optional Parts List Ultra Aire 65H Indoor Air Quality System Part No Description 4027158 Filter MERV 11 4028085 Pump Kit 4028111 Hang Kit 4023647 8 Gravity Damper 4020646 8 Butterfly Damper 4027415 8...

Page 11: ...66 Defrost Timer 4027149 Indicator Light 4027151 Overflow Switch 4027161 Transformer FOR HOMEOWNER ROUTINE MAINTENANCE Part No Description 4027158 Air Filter MERV 11 4027422 4 Pack 4027427 12 Pack The...

Page 12: ...t to a high pressure and temperature 10 2 Troubleshooting Neither fan nor compressor running Dehumidification is being called for No fan call 1 Unit unplugged or no power to outlet 2 Humidity control...

Page 13: ...a new charge must be accurately weighed in If any of the old charge is left in the system it must be recovered before weighing in the new charge Refer to the unit nameplate for the correct charge wei...

Page 14: ...y Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point...

Page 15: ...sts related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibili...

Page 16: ...n any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2008 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phon...

Reviews: