Read the installation, operation and maintenance instructions 
carefully before installing and operating this device. Proper 
adherence to these instructions is essential to obtain 
maximum benefit from your Ultra-Aire 65H indoor air quality 
system. 

READ AND SAVE THESE INSTRUCTIONS 

•  The device is designed to be installed INDOORS IN A SPACE 

THAT IS PROTECTED FROM RAIN AND FLOODING. 

•  Install the unit with space to access the front panel for 

maintenance and service. DO NOT INSTALL UNIT WITH THE 
FRONT PANEL INACCESSIBLE. 

•  Avoid directing the discharge air at people, or over the 

water in pool areas. 

•  If used near a water source; be certain there is no chance 

the unit could fall into the water or get wet. The unit should 
also be plugged into a GFCI (Ground Fault Circuit Interrupt 
outlet). 

•  DO NOT use the device as a bench or table. 

• DO NOT place the device directly on structural members.

•  A drain pan MUST be placed under the unit if installed 

above a living area or above an area where water leakage 
could cause damage (see local regularity code for more 
information).

Read and Save These Instructions

 WARNING!

 

— This symbol indicates 

important instructions. Failure to heed them can result 

in serious injury or death.

 CAUTION!

 

— This symbol indicates 

important instructions. Failure to heed them can result 

in injury or material property damage.

1. 

 

Intended Application for Ultra-Aire 65H 

For the ideal installation, draw air from the central part of 
the home and return it to isolated areas of the home like the 
bedrooms, den, utility room, or family room. The ductwork of the 
existing heating system can be used to supply air to the home. 

2. Registrations 

The Ultra-Aire 65H conforms to UL STD 474 and CSA 
Standard C22.2 No.92. 

3. Specifications 

Part Number:

 

4027170

Blower:

 

190 CFM @ 0.0" WG

Power:

 

680 Watts @ 80°F and 60% RH

Supply Voltage:

  110-120 VAC – 1phase – 60 Hz

Current Draw:

 

5.50 Amps

Energy Factor: 

 

1.95 L/kWh

Operating Temp.:

  Between 40°F and 95°F Max

Sized for:

 

Up to 1600 Sq. Ft. - Typical

Miniumum Performance at 80°F and 60% RH 

Water Removal:  

65 pints/day

Efficiency: 

4.1 Pints/kWh

Air Filter: 

 

MERV-11

Efficiency: 

 Standard 65% Efficient 
ASHRAE Dust Spot Test

Size: 

9" x 11" x 1"

Power Cord:

 

9', 110-120 VAC, Ground

Drain Connection:

 3/4" Threaded MPT

Drain Hose: 

 

5/8" ID x 8'

Dimensions 

Unit 

Shipping

Width: 

21" 

27" 

Height: 

12" 

17" 

Depth: 

12"    

17" 

Weight: 

55 lbs 

59 lbs  

4. Installation 

4.1 Installation Checklist 

CAUTION

 

Prior to installation of the Ultra-Aire 65H, the following 
checklist should be reviewed. The Ultra-Aire 65H can be 
installed in a variety of locations to meet the owner’s needs, 
and be integrated with existing forced air systems or existing 
ductwork if desired. The location choice is contingent on 
a variety of requirements not limited to: ease of service, 
controls access, drainage, filtration, power, fresh-air 
ventilation (optional), water damage prevention, and current 
regulatory codes (ASHRAE, fire, etc). Please address all of 
these issues before you select the location of the device. 

n

  

4.1A Power Accessibility 

Unit should be located in an area where the cord’s  length (8') 
should easily reach a 110-120 VAC  electrical  outlet with a 
minimum of a 15 A circuit capacity. 

SAFETY PRECAUTIONS

3

Ultra-Aire 65H Installer’s & Owner’s Manual

Summary of Contents for Ultra-Aire 65H

Page 1: ...tandard MERV 14 optional n Compact design n 5 year warranty P O Box 8680 Madison WI 53708 TOLL FREE 1 800 533 7533 www thermastor com sales thermastor com TS 422c INSTALLER S OWNER S MANUAL HVAC INSTA...

Page 2: ...4D Installation in an Attic 6 4 4E Installation in a Structure with No Forced Air HVAC System 7 4 4F Ducting for High Efficiency Filtration 7 4 5 Compressor Release and Noise Abatement 7 4 6 Controls...

Page 3: ...edrooms den utility room or family room The ductwork of the existing heating system can be used to supply air to the home 2 Registrations The Ultra Aire 65H conforms to UL STD 474 and CSA Standard C22...

Page 4: ...al electrical codes for any further information Therma Stor LLC offers a family of control devices for use with the Ultra Aire 65H The controls are to be located remotely from the unit and located in...

Page 5: ...he isolated areas of the home like the bedrooms den utility room or family room The ductwork of the existing heating system can be used to supply air to the home If the existing supply goes to isolate...

Page 6: ...stallation Install a separate 8 return for the Ultra Aire 65H in a central area of the structure Optional Duct the supply of the Ultra Aire to a 8 x 8 x 8 tee damper adjusted to 20 open to the basemen...

Page 7: ...es the return duct to be removed Failure to use flex duct will prevent filter access Three feet of flex duct should be adequate to access the filter 4 6 Controls All control panels should be mounted i...

Page 8: ...8 Ultra Aire 65H Installer s Owner s Manual ATTENTION INSTALLER...

Page 9: ...ncy and may cause the compressor to cycle off and on unnecessarily on the defrost control DO NOT operate the unit without a filter or with a less effective filter Operating the unit without a filter o...

Page 10: ...Optional Parts List Ultra Aire 65H Indoor Air Quality System Part No Description 4027158 Filter MERV 11 4028085 Pump Kit 4028111 Hang Kit 4023647 8 Gravity Damper 4020646 8 Butterfly Damper 4027415 8...

Page 11: ...66 Defrost Timer 4027149 Indicator Light 4027151 Overflow Switch 4027161 Transformer FOR HOMEOWNER ROUTINE MAINTENANCE Part No Description 4027158 Air Filter MERV 11 4027422 4 Pack 4027427 12 Pack The...

Page 12: ...t to a high pressure and temperature 10 2 Troubleshooting Neither fan nor compressor running Dehumidification is being called for No fan call 1 Unit unplugged or no power to outlet 2 Humidity control...

Page 13: ...a new charge must be accurately weighed in If any of the old charge is left in the system it must be recovered before weighing in the new charge Refer to the unit nameplate for the correct charge wei...

Page 14: ...y Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point...

Page 15: ...sts related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibili...

Page 16: ...n any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2008 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phon...

Reviews: