Therma-Stor Ultra-Aire 65H Manual Download Page 13

13

Ultra-Aire 65H Installer’s & Owner’s Manual

Unit removes some water, but not as much as expected. 

1. Air temperature and/or humidity have dropped. 
2.  Humidity meter and or thermometer used are  

out of calibration.

3. Unit has entered defrost cycle. 
4. Air filter dirty. 
5. Defective defrost thermostat. 
6. Low refrigerant charge. 
7. Air leak such as loose cover or ducting leaks. 
8. Defective compressor. 
9. Restrictive ducting. 
10.Optional Condensate Pump Safety Switch open. 

Unit Test to determine problem: 

1. Detach field control wiring connections from main unit. 
2.  Connect the yellow and green pigtails from the main 

unit together; only the fan should run. Disconnect the 
wires. 

3.  Connect the yellow and blue pigtails from the main unit 

together; the compressor and fan should run. 

4.  If these tests work, the main unit is working properly. 

You should check the control panel and field control 
wiring for problems next. 

5.  Remove the control panel from the mounting box and 

detach it from the field installed control wiring. Connect 
the blue, yellow, and green wires from the control 
panel directly to the corresponding colored pigtails on 
the main unit. Leave the violet, white and red wires 
disconnected! 

6.  Turn on the fan switch; the fan should run. Turn off the 

fan switch. 

7.  Turn on the humidity control; the compressor and fan 

should run. 

8.  If these tests work, the problem is most likely in the 

field control wiring. 

10.3 Refrigerant Charging 

If the refrigerant charge is lost due to service or a leak, a 
new charge must be accurately weighed in. If any of the 
old charge is left in the system, it must be recovered before 
weighing in the new charge. Refer to the unit nameplate for 
the correct charge weight and refrigerant type. 

10.4 Compressor/Capacitor Replacement 

This compressor is equipped with a two terminal external 
overload and a run capacitor, but no start capacitor or relay. 

CAUTION

 

CAUTION-ELECTRICAL SHOCK HAZARD: Electrical power 

must be present to perform some tests. These tests 

should be performed by a qualified service person. 

10.5 Electric Ventilation Damper 

The damper will open when the ventilation is called for, 
allowing fresh air into the structure through the fresh air 
inlet duct. The electric ventilation damper will remain closed 
when the ventilation is not activated in order to prevent 
over-ventilating the structure when the unit is dehumidifying 
or recirculating the indoor air. The electric ventilation damper 
operates on 24 Vac from the control circuit. DO NOT connect 
high voltage to the damper motor or damage to the motor 
will result. DO NOT force the blade of the damper by hand or 
damage to the damper motor may result.

The damper opens in one direction only. The damper rotates 
very slowly, allow sufficient time for the damper to cycle. The 
damper will take approximately one minute to cycle from 
closed to open or from open to closed. 

If the electric ventilation damper fails to operate: 

1.  Check that the wiring is correct and that voltage is 

present at the damper motor. 

2.  Check for any obstruction inside the damper. If the 

electric ventilation damper fails to operate after 
performing these checks, it must be replaced. 

FOR HVAC INSTALLER ONLY

Summary of Contents for Ultra-Aire 65H

Page 1: ...tandard MERV 14 optional n Compact design n 5 year warranty P O Box 8680 Madison WI 53708 TOLL FREE 1 800 533 7533 www thermastor com sales thermastor com TS 422c INSTALLER S OWNER S MANUAL HVAC INSTA...

Page 2: ...4D Installation in an Attic 6 4 4E Installation in a Structure with No Forced Air HVAC System 7 4 4F Ducting for High Efficiency Filtration 7 4 5 Compressor Release and Noise Abatement 7 4 6 Controls...

Page 3: ...edrooms den utility room or family room The ductwork of the existing heating system can be used to supply air to the home 2 Registrations The Ultra Aire 65H conforms to UL STD 474 and CSA Standard C22...

Page 4: ...al electrical codes for any further information Therma Stor LLC offers a family of control devices for use with the Ultra Aire 65H The controls are to be located remotely from the unit and located in...

Page 5: ...he isolated areas of the home like the bedrooms den utility room or family room The ductwork of the existing heating system can be used to supply air to the home If the existing supply goes to isolate...

Page 6: ...stallation Install a separate 8 return for the Ultra Aire 65H in a central area of the structure Optional Duct the supply of the Ultra Aire to a 8 x 8 x 8 tee damper adjusted to 20 open to the basemen...

Page 7: ...es the return duct to be removed Failure to use flex duct will prevent filter access Three feet of flex duct should be adequate to access the filter 4 6 Controls All control panels should be mounted i...

Page 8: ...8 Ultra Aire 65H Installer s Owner s Manual ATTENTION INSTALLER...

Page 9: ...ncy and may cause the compressor to cycle off and on unnecessarily on the defrost control DO NOT operate the unit without a filter or with a less effective filter Operating the unit without a filter o...

Page 10: ...Optional Parts List Ultra Aire 65H Indoor Air Quality System Part No Description 4027158 Filter MERV 11 4028085 Pump Kit 4028111 Hang Kit 4023647 8 Gravity Damper 4020646 8 Butterfly Damper 4027415 8...

Page 11: ...66 Defrost Timer 4027149 Indicator Light 4027151 Overflow Switch 4027161 Transformer FOR HOMEOWNER ROUTINE MAINTENANCE Part No Description 4027158 Air Filter MERV 11 4027422 4 Pack 4027427 12 Pack The...

Page 12: ...t to a high pressure and temperature 10 2 Troubleshooting Neither fan nor compressor running Dehumidification is being called for No fan call 1 Unit unplugged or no power to outlet 2 Humidity control...

Page 13: ...a new charge must be accurately weighed in If any of the old charge is left in the system it must be recovered before weighing in the new charge Refer to the unit nameplate for the correct charge wei...

Page 14: ...y Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point...

Page 15: ...sts related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibili...

Page 16: ...n any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2008 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phon...

Reviews: