Set room influence
With weather-dependent control, the feed
temperature can be adjusted if there is a large
divergence between the room temperature and
the setpoint temperature.
Offset supply temperature
=
∆
T
v
Set room influence
= PI
Setpoint value of room temperature = T
R set
Actual value of room temperature = T
R act
∆
Tv
= PI (T
R set
– T
R act
)
Example: T
R set
= 20 °C T
R act
= 18 °C PI = 3
∆
Tv
= 3 x ( 20 °C - 18 °C) = 6 K
Result: The feed temperature is increased by 6 K.
The higher the selected room influence, the
greater the influence of the room temperature
on the feed temperature.
Set maintenance period
With maintenance, it is a question of a
"reminder function".
Confirm
SERVICE
by pressing
OK
.
The display shows
MONTHS BEFORE
NEXT SERVICE
.
Use the
+
or
–
keys or the rotary control
to enter the value and confirm by
pressing
OK
.
34
SERVICE
MONTHS BEFORE
NEXT SERVICE
12