Manual DALI button interface TA 4 S DALI-2
14
Value range of offset
The offset can be used to correct the measurement value if, for example, the measurement
deviates from a reference device.
•
The setting range is 0x01 to 0xFF; this corresponds to an offset range of
o
{-12.7 °C to +12.7 °C} or
o
{-12.7
kΩ to +12.7
kΩ}
•
One unit corresponds to 0.1 °C or 100
Ω
Value range "Range":
The "Range" parameter can be used to select temperature sensors with a positive or negative
temperature range.
•
0x00: Temperature sensors with a positive temperature range (factory setting)
•
0x01: Temperature sensor with a negative temperature range
See also
chapter 8.5 Measurement values T1/T2
Value range "Hysteresis":
The "Hysteresis" parameter can be used to reduce the DALI bus load. The event telegrams are
not sent until the measurement value has changed by the value of the set hysteresis.
•
The setting range is 0x00 to 0xFF; this corresponds to a hysteresis range of
o
{0.1 °C to 25.5 °C} or
o
{100 Ω to +25.5 kΩ}
•
One unit corresponds to 0.1 °C or 100
Ω
Sensor type
Offset
0x00, 0x01, 0x02
0x03
0x01: corresponds to
-12.7 °C
-12.7
kΩ
0x02: corresponds to
-12.6 °C
-12.6
kΩ
…..
…..
…..
0x80: factory setting
0 °C
0 Ω
0x81: corresponds to
+0.1 °C
+0.1 kΩ
…..
…..
…..
0xFF: corresponds to
+12.7 °C
+12.7 kΩ
Sensor type
Hysteresis
0x00, 0x01, 0x02
0x03
0x00: factory setting
0.1 °C
100 Ω
0x01: corresponds to
0.1 °C
100 Ω
0x02: corresponds to
0.2 °C
200 Ω
…..
…..
…..
0x80: corresponds to
12.8 °C
12.8 kΩ
…..
…..
…..
0xFF: corresponds to
25.5 °C
25.5 kΩ