background image

 

 

Manual DALI button interface TA 4 S DALI-2 

 

13 

 

 

 

8.2

 

Memory bank 3 – absolute input device 

 
The parameters of absolute input device instances 0 and 1, which are not defined by DALI-2, are 

stored in memory bank 3.  
 

Address 

 

Instance  Description 

Default 

value 

(factory) 

RESET 

value 

Value 

range 

Memory 

type 

0x00 

 

Address of last position 

in this memory bank 

0x03 

no 

change 

ROM 

0x01 

 

Indicator byte (defined 

by manufacturer) – 

version of the memory 
bank 

0x01 

no 

change 

ROM 

0x02 

 

Memory bank lock byte 

0xFF 

0xFF 

0xFF / 0x55 

RAM 

0x03 

Sensor type of sensor T1 

0x03 

0x03 

 0x00 – 0x03 

NVM 

0x04 

Offset of sensor T1 

0x80 

0x80 

0x01 – 0xFF 

NVM 

0x05 

Range of sensor T1 

0x00 

0x00 

0x00 / 0x01 

NVM 

0x06 

Hysteresis of sensor T1 

0x00 

0x00 

0x00 – 0xFF 

NVM 

0x07 

Filter of sensor T1 

0x02 

0x02 

0x00 – 0x0B 

NVM 

0x08 

Beta low of sensor T1 

0xE4 

0xE4 

0x00 – 0xFF 

NVM 

0x09 

Beta high of sensor T1 

0x11 

0x11 

0x00 – 0xFF 

NVM 

0x0A 

Sensor type of sensor T2 

0x03 

0x03 

0x00 – 0x03 

NVM 

0x0B 

Offset of sensor T2 

0x80 

0x80 

0x01 – 0xFF 

NVM 

0x0C 

Range of sensor T2 

0x00 

0x00 

0x00 / 0x01 

NVM 

0x0D 

Hysteresis of sensor T2 

0x00 

0x00 

0x00 – 0xFF 

NVM 

0x0E 

Filter of sensor T2 

0x02 

0x02 

0x00 – 0x0B 

NVM 

0x0F 

Beta low of sensor T2 

0xE4 

0xE4 

0x00 – 0xFF 

NVM 

0x10 

Beta high of sensor T2 

0x11 

0x11 

0x00 – 0xFF 

NVM 

0x11-0xFF   

Not implemented / 

reserved 

Response 

NO 

no 

change 

ROM 

 

 

Value range of sensor type: 

 

0x00: Theben sensors, see table below 

 

0x01: Theben sensor 9070191 

 

0x02: any 100 k

Ω

 NTC with known B or beta [K] (see also value range of parameter beta 

low/beta high) 

 

0x03: 100 

kΩ variable resistor (factory setting)

 

 

Theben sensors 

Recommended 

measurement 

range 

Max. measurement range 

Sensor 

type 

Range 0x00 

Range 0x01 

9070191, wall installation 

temperature sensor  

0 °C ... 40 °C 

0 °C ... 75 °C 

-25 °C … 75 °C 

0x01 

9070321, floor sensor 

0 °C ... 40 °C 

0 °C ... 85 °C 

-25 °C ... 75 °C 

0x00 

9070459, room temperature 
sensor  

-10 °C ... 50 °C 

0 °C ... 85 °C 

-25 °C ... 75 °C 

0x00 

9070489, contact temperature 
sensor  

0 °C ... 80 °C 

0 °C ... 85 °C 

-25 °C ... 75 °C 

0x00 

9070496, Flush-mounted 
temperature sensor  

0 °C ... 40 °C 

0 °C ... 85 °C 

-25 °C ... 75 °C 

0x00 

 

 

 

 

 

 

 

Summary of Contents for 4960094

Page 1: ...2021 01 14_307569 Manual DALI button interface TA 4 S DALI 2 TA 4 DALI 2 4960094 ...

Page 2: ...nical data 6 4 Product characteristics 7 4 1 Usage 7 4 2 Functionality 7 4 3 Dimensions 8 5 Connection 9 6 Installation 10 7 Settings 11 7 1 Settings via the DALI bus 11 8 Operating modes 12 8 1 Memory bank 2 push button instance 12 8 2 Memory bank 3 absolute input device 13 8 3 Assignment of short addresses 16 8 4 Button function C1 C4 16 8 5 Determining measurement values T1 T2 via the DALI bus ...

Page 3: ...or use as contractually agreed between the manufacturer and the user Any other use is considered to be unacceptable The manufacturer does not accept liability for any resulting damages 1 3 Explanation of terms The TA 4 S DALI 2 DALI button interface is a push button processing unit of an input control device according to standard IEC 62386 Part 301 as well as an absolute input device according to ...

Page 4: ...nment of the short addresses random addressing for the button interfaces is carried out via the application controller After start up the TA 4 S DALI 2 button interface captures the binary states of the connected buttons and transmits this information to the higher level controller application controller as a DALI telegram If variable resistors or temperature sensors are connected the measured val...

Page 5: ...ected to the TA 4 S DALI 2 button interface 2 2 Overview of available instances Instance no Instance name Instance type Standard Memory bank 0 Absolute input device T1 2 IEC 62386 302 3 1 Absolute input device T2 2 IEC 62386 302 3 2 Button C1 1 IEC 62386 301 2 3 Button C2 1 IEC 62386 301 2 4 Button C3 1 IEC 62386 301 2 5 Button C4 1 IEC 62386 301 2 ...

Page 6: ... Ambient temperature 15 C 50 C Pollution degree 2 Rated impulse voltage 4 kV Connection type DALI Screw terminals Cable cross section 0 14 1 5 mm one wire 0 14 1 5 mm fine wire 0 25 0 5 mm fine wire with crimp terminal with and without plastic sleeve Length of connecting wires for buttons or temperature sensor 25 cm Max cable length for buttons or temperature sensor 30 m CE Declaration of Conformi...

Page 7: ...nnect variable resistors e g sliders potentiometers or various Theben temperature sensors according to standard IEC 62386 Part 302 The sensor is selected in the memory bank The measurement values can be corrected with an adjustable offset if for example the measurement deviates from a reference instrument For the inputs for variable resistors or temperature sensors an adjustable filter is availabl...

Page 8: ...Manual DALI button interface TA 4 S DALI 2 8 4 3 Dimensions ...

Page 9: ...evice must be provided Plug for connection lead DALI connection A connection lead with plug is supplied for connecting buttons C1 to C4 variable resistors or Theben temperature sensors T1 and T2 The cable length is 25 cm and can be extended up to max 30 m if required Connection of buttons C1 to C4 Connection of variable resistors or Theben temperature sensors T1 and T2 BK Black BN Brown RD Red OG ...

Page 10: ...Manual DALI button interface TA 4 S DALI 2 10 6 Installation The TA 4 S DALI 2 button interfaces are installed in conventional flush mounted boxes according to DIN 49073 ...

Page 11: ...mands are set by the application controller via the DALI bus The TA 4 S DALI 2 button interface supports the parameters and configuration commands according to IEC 62386 Part 103 301 302 Parameters which are not defined by the standard are stored in the memory bank The default values of the parameters in the factory settings are also according to standard IEC 62386 Part 103 301 302 incl DiiA Guide...

Page 12: ...ory bank 2 Value range of button contact type 0x00 NO contact factory setting 0xFF opening contact NC Address Instance Description Default value factory RESET value Value range Memory type 0x00 Address of last position in this memory bank 0x03 no change ROM 0x01 Indicator byte defined by manufacturer version of the memory bank 0x01 no change ROM 0x02 Memory bank lock byte 0xFF 0xFF 0xFF 0x55 RAM 0...

Page 13: ...ype of sensor T2 0x03 0x03 0x00 0x03 NVM 0x0B 1 Offset of sensor T2 0x80 0x80 0x01 0xFF NVM 0x0C 1 Range of sensor T2 0x00 0x00 0x00 0x01 NVM 0x0D 1 Hysteresis of sensor T2 0x00 0x00 0x00 0xFF NVM 0x0E 1 Filter of sensor T2 0x02 0x02 0x00 0x0B NVM 0x0F 1 Beta low of sensor T2 0xE4 0xE4 0x00 0xFF NVM 0x10 1 Beta high of sensor T2 0x11 0x11 0x00 0xFF NVM 0x11 0xFF Not implemented reserved Response N...

Page 14: ...also chapter 8 5 Measurement values T1 T2 Value range Hysteresis The Hysteresis parameter can be used to reduce the DALI bus load The event telegrams are not sent until the measurement value has changed by the value of the set hysteresis The setting range is 0x00 to 0xFF this corresponds to a hysteresis range of o 0 1 C to 25 5 C or o 100 Ω to 25 5 kΩ One unit corresponds to 0 1 C or 100 Ω Sensor ...

Page 15: ...r to be stored in the memory bank the four digit number must first be converted to hex format and then stored in the beta low and beta high bytes Example B or Beta 4580 which corresponds to Hex 11E4 Beta low 0xE4 factory setting Beta high 0x11 factory setting The setting range for beta low is 0x00 to 0xFF and for beta high 0x00 to 0xFF Summary of setting options for parameters Sensor type Offset R...

Page 16: ...2 button interface has 2 instances to the measurement values of the connected sensors Instance 0 supplies the measurement value of sensor T1 Instance 1 supplies the measurement value of sensor T2 on the DALI bus in accordance with IEC 62386 Part 302 According to DALI standard IEC 62386 103 302 the value of an absolute input device instance is obtained either by querying directly or by evaluating t...

Page 17: ...used the following steps are necessary to display the obtained value Temperature sensor with a positive temperature range Setting in memory bank 3 sensor type 0x00 0x01 or 0x02 Setting in memory bank 3 range 0x00 Temperature measurement value C event info 10 Temperature sensor with a negative temperature range Setting in memory bank 3 sensor type 0x00 0x01 or 0x02 Setting in memory bank 3 range 0x...

Page 18: ...ecommended measurement range 0 C 40 C Item no 9070191 Details www theben de en Floor sensor Recommended measurement range 0 C 40 C Item no 9070321 Details www theben de en Room temperature sensor Protection rating IP 65 Recommended measurement range 10 C 50 C Item no 9070459 Details www theben de en ...

Page 19: ...flap housing for measuring the temperature at pipes and curved surfaces Recommended measurement range 0 C 80 C Item no 9070489 Details www theben de en Flush mounted temperature sensor For flush mounting Recommended measurement range 0 C 40 C Item no 9070496 Details www theben de en ...

Page 20: ...ace TA 4 S DALI 2 20 10 Contact Theben AG Hohenbergstr 32 72401 Haigerloch Germany GERMANY Phone 49 7474 692 0 Fax 49 7474 692 150 Hotline Phone 49 7474 692 369 hotline theben de Addresses telephone numbers etc www theben de en ...

Reviews: