Manual DALI button interface TA 4 S DALI-2
12
8
Operating modes
The TA 4 S DALI-2 button interface is a push button input device according to standard
IEC 62386 Part 301 and an absolute input device according to standard IEC 62386 Part 302.
The TA 4 S DALI-2 button interface is delivered and operated with operating mode 0x00 ex
works. The operating mode cannot be changed.
8.1
Memory bank 2 – push button instance
In memory bank 2, the button contact type of push button instances 2 to 5 is stored.
Memory bank 2
Value range of button contact type:
•
0x00: NO contact (factory setting)
•
0xFF: opening contact NC
Address
Instance
Description
Default
value
(factory)
RESET
value
Value
range
Memory
type
0x00
Address of last position
in this memory bank
0x03
no
change
-
ROM
0x01
Indicator byte (defined by
manufacturer) – version
of the memory bank
0x01
no
change
-
ROM
0x02
Memory bank lock byte
0xFF
0xFF
0xFF / 0x55
RAM
0x03
2
Type of contact of button
C1
0x00
0x00
0x00 / 0xFF
NVM
0x04
3
Type of contact of button
C2
0x00
0x00
0x00 / 0xFF
NVM
0x05
4
Type of contact of button
C3
0x00
0x00
0x00 / 0xFF
NVM
0x06
5
Type of contact of button
C4
0x00
0x00
0x00 / 0xFF
NVM
0x07-
0xFF
Not implemented /
reserved
Response
NO
no
change
-
ROM