4
7. Connection
The presence detectors can be combined as master in
individual switching, master/master in parallel switching or
master/slave parallel switching. Several push buttons can be
connected to one control input. Illuminated push buttons can
only be used with neutral conductor connection.
With the management remote control „SendoPro, theSenda
B/App“, lighting channels C1 to C3 can be assigned to the
required button inputs S1 to S3 via the parameter <Terminal
SX assignment>. The input S3/P can be used for the master/
slave parallel signal or master/master switching, or as button
input S3. The factory setting is „Parallel“.
Up to 50 DALI operating devices can be connected to each
master device. We recommend distributing the DALI operating
devices equally over the 3 external conductors.
L
All detectors and buttons must be connected to the same
external conductor.
L
Connect at least 1 Dali operating device per master.
Individual switching
In individual switching, the presence detector, as master,
detects presence and brightness and controls lighting.
Master
DALI
DA+ DA–
S1 S2
EVG
S3/P
N
L
N
L
EVG
Master/Slave parallel switching
If the detection area covered by one presence detector is
insufficient (larger rooms), then up to 10 detectors can be
operated in parallel by connecting the P terminals. In the
process, presence detection is performed by all detectors
together. The master measures the brightness, operates the
buttons and controls the lighting. All other detectors are used
as slaves. They only provide presence information.
Master
DALI
DA+ DA–
S1 S2
S3/P
N
L
Slave
P
N
L
N
L
EVG
•
Light measurement only with the master
•
Switch up to 10 detectors in parallel
•
Use the same external conductor for all detectors and
buttons
•
Slave: theRonda P360 Slave (2080080)
Master/master parallel switching
Several masters can be used in parallel switching. Each
master controls its lighting groups according to its own
brightness measurements. Time delays and brightness
setpoint values are set individually on each master. Presence
continues to be detected by all detectors.
Master
DALI
DALI
DA+ DA–
S1 S2
S3/P
N
L
N
L
EVG
Master
DA+ DA–
S1 S2
S3/P
N
L
EVG
•
Master with 2 lighting groups and individual brightness
measurement
•
Switch up to 10 detectors in parallel
•
Use the same phase for all detectors and buttons
Integrating an external DALI relay
•
No more than 1 external DALI re
lay can be connected
on one single DALI line. The Dali relay must comply with
Standard IEC 62386-208 (device type 7).
•
The detector automatically detect
s the DALI relay.
•
Switch-on delay and time delay can be set using the
remote control.
Master
DALI
DA+ DA–
S1 S2
EVG
N
L
N
L
EVG
DALI
relay
8. Settings
The presence detectors are supplied with basic settings ready
for operation. The specifications are guidance values. The
optional “SendoPro, theSenda B/App” management remote
control or the “theSenda P” installation remote control are
available for start-up support. They enable remote setting.
The “SendoPro, theSenda B/App” can be used to query, adjust
and optimise parameters. With the “theSenda P”, parame
-
ters can only be adjusted. A range of variable parameters is
available for adjustment with the remote control (see section
“Parameters via remote control”).
Settings via the button
Pressing any button for longer than 15 s triggers the teach-in
of the brightness setpoint value by the teach-in function. In
addition, the teach-in function can be conveniently executed
with the “SendoPro, theSenda B/App” management remote
control or the “theSenda P” installation remote control (see
section “Control commands via remote control”).
The teach-in function via the button can be disabled using
the “SendoPro, theSenda B/App” management remote control
when the <Configuration button/RC> parameter is set to
“disabled”.
Summary of Contents for 2080045
Page 14: ...14 ...