10
activated with the “SendoPro, theSenda B/App” management
remote control. The detector goes directly into test mode
when the test mode is set:
•
The LED shows the light test mode (5 seconds on, 0.3
seconds off).
•
The presence detector responds exactly as in normal
operating mode, only the reaction to brightness/dark-
ness is faster.
•
In order to simulate this behaviour, either the area below
the presence detector can be illuminated or the blinds
operated.
•
Test mode ends automatically after 10 min.
The detector restarts itself (see switch-on behaviour on
page 12).
L
Note: Do not use a torch to switch on the presence
detector! The adaptive light switching thresholds will be
distorted!
Factory settings
The presence detector is supplied with the following parame-
ter values:
Parameter
Value
Function C1/C2
Control
Function C3
Control
Light measurement source C3
centre
Terminal S1 assignment
C1
Terminal S2 assignment
C2
Terminal S3/P assignment
Parallel
Brightness set point value C1, C2, C3
500 lux
Room correction factor Win, Mid, Inn, Int
0.3
Detection sensitivity (PIR)
Increment 3
Lighting time delay
10 min
Short presence
On
Energy saving mode
eco
Presence switch-on delay
0 s
Presence time delay
10 min
Switch-on dimming value C1, C2, C3
50 %
Configuration type C1/C2, C3
auto
Control speed
Standard
Minimum dimming value
10 %
Maximum dimming value
100 %
Switching off brightness
10 min
Response after dimming
school
Standby time
0 s
Standby dimming value
10 %
IR group address C1
I
IR group address C2
II
IR group address C3
III
Scene 1 C1, C2, C3
30 %
Scene 2 C1, C2, C3
70 %
Configuration button/RC
enabled
LED display motion
off
The parameters can only be set to factory settings by using
the “SendoPro, theSenda B/App” management remote
control.
Reset DALI ECGs
The connected DALI ECGs are reset to factory settings and the
group addresses are deleted.
9. Start-up
Initial operation (system not configured)
After first switching on the system power supply, the detector
is restarted, automatically identifies all connected DALI lamps,
assigns short addresses and manages them in a list. This
stage is indicated by an LED flashing pattern (5 x on briefly
every 3 s) and, depending on the size of the system, can last
up to 3 min.
If no DALI ECG is connected to the detector or a DALI line is
interrupted, the detector shows this with the LED flashing
pattern (LED is on and flashes off briefly twice every 3 s).
If the system is OK, the detector automatically enters con-
figuration mode and waits for configuration of the lighting
groups. This is indicated by the LED flashing pattern (2 x on
briefly every 3 s). If configuration has not been carried out the
system will be in the following operating mode:
•
Detector is in broadcast mode.
•
Function is switching mode (only presence detection, no
light measurement).
•
All lights are controlled with 100% switching/dimming
value.
•
The operating mode is as a fully automatic device.
•
All connected buttons are active. It is possible to switch
on and off, as well as dim.
•
Time delay 10 min.
Configuration of the lighting groups
For the configuration, several options are available:
•
Using the service remote control „theSenda B/App“
•
Using the management remote control „SendoPro 868-A“
•
Using the buttons or „theSenda S“ user remote control
Configuring the lighting groups with the theSenda B/app ser-
vice remote control
Connect the theSenda B with the corresponding „theSenda
Plug“ app.
Place the theSenda B under the detector (direct the remote
control towards the detector).
Select „theRonda P360-330 DALI“ as the type in the „the-
Senda Plug“ app.
In the „DALI configuration“ menu, select the required group
assignment.
For the DALI configuration, there are 3 options available:
y
„Group assignment (unaddress.)“: only DALI EBs without a
group address are processed.
y
„Group assignment (all)“: all connected DALI EBs are confi
-
gured. WARNING: All existing group assignments with group
number 1, 2 or 3 will be deleted.
y
„Change group assignment“: the next existing EB is
searched for and selected.
L
The remote control must be directed to the detector! The
LED is switched off.
▻ After selecting the required group assignment, the
detector is in the programming mode.
▻ A DALI light starts to pulse (random order).
Use the button # to assign the required C1, C2 or C3 chan
-
nel to the DALI EB.
▻ The lamp confirms the assignment by dimming to 20 %.
Summary of Contents for 2080045
Page 14: ...14 ...