activated with the “SendoPro, theSenda B/App” management 

remote control. The detector goes directly into test mode 

when the test mode is set:

 

The LED shows the light test mode (5 seconds on, 0.3 
seconds off).

 

The presence detector responds exactly as in normal 

operating mode, only the reaction to brightness/dark-

ness is faster.

 

In order to simulate this behaviour, either the area below 
the presence detector can be illuminated or the blinds 

operated.

 

Test mode ends automatically after 10 min.  

 

The detector restarts itself (see switch-on behaviour on 

page 12).

 

L

Note: Do not use a torch to switch on the presence 
detector! The adaptive light switching thresholds will be 
distorted!

Factory settings

The presence detector is supplied with the following parame-

ter values:

Parameter

Value

Function C1/C2

Control

Function C3

Control

Light measurement source C3

centre

Terminal S1 assignment

C1

Terminal S2 assignment

C2

Terminal S3/P assignment

Parallel

Brightness set point value C1, C2, C3

500 lux

Room correction factor Win, Mid, Inn, Int

0.3

Detection sensitivity (PIR)

Increment 3

Lighting time delay

10 min

Short presence 

On

Energy saving mode

eco

Presence switch-on delay

0 s

Presence time delay

10 min

Switch-on dimming value C1, C2, C3

50 %

Configuration type C1/C2, C3

auto

Control speed

Standard

Minimum dimming value

10 %

Maximum dimming value

100 %

Switching off brightness

10 min

Response after dimming

school

Standby time

0 s

Standby dimming value

10 %

IR group address C1

I

IR group address C2

II

IR group address C3

 III

Scene 1 C1, C2, C3

30 %

Scene 2 C1, C2, C3

70 %

Configuration button/RC

enabled

LED display motion

off

The parameters can only be set to factory settings by using 

the “SendoPro, theSenda B/App” management remote 

control.

Reset DALI ECGs

The connected DALI ECGs are reset to factory settings and the 

group addresses are deleted.

9.  Start-up

Initial operation (system not configured)

After first switching on the system power supply, the detector 

is restarted, automatically identifies all connected DALI lamps, 

assigns short addresses and manages them in a list. This 

stage is indicated by an LED flashing pattern (5 x on briefly 

every 3 s) and, depending on the size of the system, can last 

up to 3 min.

If no DALI ECG is connected to the detector or a DALI line is 

interrupted, the detector shows this with the LED flashing 

pattern (LED is on and flashes off briefly twice every 3 s). 

If the system is OK, the detector automatically enters con-

figuration mode and waits for configuration of the lighting 

groups. This is indicated by the LED flashing pattern (2 x on 

briefly every 3 s). If configuration has not been carried out the 

system will be in the following operating mode:

 

Detector is in broadcast mode.

 

Function is switching mode (only presence detection, no 

light measurement).

 

All lights are controlled with 100% switching/dimming 

value.

 

The operating mode is as a fully automatic device.

 

All connected buttons are active. It is possible to switch 
on and off, as well as dim.

 

Time delay 10 min.

Configuration of the lighting groups

For the configuration, several options are available:

 

Using the service remote control „theSenda B/App“

 

Using the management remote control „SendoPro 868-A“

 

Using the buttons or „theSenda S“ user remote control

Configuring the lighting groups with the theSenda B/app ser-

vice remote control

 

†

Connect the theSenda B with the corresponding „theSenda 

Plug“ app.

 

†

Place the theSenda B under the detector (direct the remote 

control towards the detector).

 

†

Select „theRonda P360-330 DALI“ as the type in the „the-

Senda Plug“ app.

 

†

In the „DALI configuration“ menu, select the required group 

assignment.

For the DALI configuration, there are 3 options available:

 

y

„Group assignment (unaddress.)“: only DALI EBs without a 

group address are processed.

 

y

„Group assignment (all)“: all connected DALI EBs are confi

-

gured. WARNING: All existing group assignments with group 

number 1, 2 or 3 will be deleted. 

 

y

„Change group assignment“: the next existing EB is 

searched for and selected.

 

L

The remote control must be directed to the detector! The 
LED is switched off.

 

▻ After selecting the required group assignment, the 

detector is in the programming mode.

 

▻ A DALI light starts to pulse (random order).

 

†

Use the button # to assign the required C1, C2 or C3 chan

-

nel to the DALI EB. 

 

▻ The lamp confirms the assignment by dimming to 20 %. 

Summary of Contents for 2080045

Page 1: ...al User remote control theSenda S option 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qualified electrician in accordance with the technical regulations applying to electri...

Page 2: ... automatically fully automa tic device or after the button is operated semi automatic device Lighting time delay The minimum time delay 10 s 60 min is adjustable It adjusts automatically to the user s behaviour and can incre ase to 30 minutes or drop back to the set minimum time With settings 2 min or 30 min the time delay remains unchanged at the set value If someone goes into an unoccu pied room...

Page 3: ...nnel As with 2 channel but with free choice between central light measurement A and integral light measurement average of light measurements A B C in the case of lighting channel C3 Switching Direct light influences the light measurement Avoid placing floor lamps or suspended lighting directly below the detector Constant light control The detector must be positioned in such a way that it only dete...

Page 4: ...er parallel switching Several masters can be used in parallel switching Each master controls its lighting groups according to its own brightness measurements Time delays and brightness setpoint values are set individually on each master Presence continues to be detected by all detectors Master DALI DALI DA DA S1 S2 S3 P N L N L EVG Master DA DA S1 S2 S3 P N L EVG Master with 2 lighting groups and ...

Page 5: ... mode Selection eco eco plus x x Presence switch on delay Value range in seconds minutes x Presence time delay Value range in seconds minutes x x Parameter Description Can be checked SendoPro theSenda B App Can be changed SendoPro theSenda B App Can be changed theSenda P Switch on dimming value C1 C2 C3 Value range in x Configuration type C1 C2 Selection auto man x x x Configuration type C3 Select...

Page 6: ...rightness The currently prevailing brightness is measured below the presence detector If the prevailing brightness is below the setpoint value the light is switched on when a presence is detected in configuration type fully automatic device A separate brightness setpoint value is available for each lighting channel C1 C2 C3 Value range Lux values with SendoPro theSenda B App manage ment remote con...

Page 7: ...ery sensitive By selecting the test presence operating mode the set sensi tivity increment is not changed Lighting time delay The time delay applies jointly to all lighting channels Value range Adjustable values with SendoPro 868 A manage ment remote control 10 s 60 min In the theSenda P installation remote control the following values are available 10 s button 30 s 60 s 2 min 10 min 20 min 60 min...

Page 8: ...nda B App Switches lighting off after a set amount of time 5 min 9 h Lighting is never switched off never off Manual dimming response With constant lighting control the manual dimming res ponse can be selected with the manual dimming response parameter Value range with SendoPro theSenda B App Constant light control remains active temporarily after manual dimming to the current brightness value as ...

Page 9: ...on and off together x Control command Description Can be triggered SendoPro theSenda B App Can be triggered theSenda P Teach in channel C1 Lighting channel C1 execution x x Teach in channel C2 Lighting channel C2 execution x x Teach in channel C3 Lighting channel C3 execution x Teach in channel C1 C2 C3 Activate for all lighting chan nels C1 C3 x Presence test On Off x x Light test On Off x Restar...

Page 10: ...s them in a list This stage is indicated by an LED flashing pattern 5 x on briefly every 3 s and depending on the size of the system can last up to 3 min If no DALI ECG is connected to the detector or a DALI line is interrupted the detector shows this with the LED flashing pattern LED is on and flashes off briefly twice every 3 s If the system is OK the detector automatically enters con figuration...

Page 11: ...mal operation and configuration is complete If so required the configuration can be completed by pressing End left hand function button In this case the system will not be ready for use If Change group assignment is selected the right arrow button can be used to switch to the next DALI ECG without changing the lighting group Otherwise the sequence remains the same When all desired changes have bee...

Page 12: ... Channel Operating voltage Colour Type Item number Ceiling installation Light 230 V AC White theRonda P360 330 DALI WH 2080045 Troubleshooting Fault Cause Light does not switch on and or off if pre sence is detected and in darkness Brightness setpoint value is set too low detector set on semi automatic light was switched off manually via button or theSenda S person not within detection area obstru...

Page 13: ...e en Cover clip for area restriction Item No 9070921 Details www theben de en theSenda P Item No 9070910 Details www theben de en theSenda S Item No 9070911 Details www theben de en theSenda B App Artikel Nr 9070985 Details www theben de en 13 Contact Theben AG Hohenbergstraße 32 72401 Haigerloch GERMANY Tel 49 7474 692 0 Fax 49 7474 692 150 Hotline Tel 49 7474 692 369 hotline theben de www theben...

Page 14: ...14 ...

Reviews: