background image

5

The lighting groups can also be configured using the but

-

tons. All connected buttons can be used for configuration. A 

detailed description can be found in chapter „9. Start-up“.

Configuration via the buttons can be disabled using the “Sen

-

doPro, theSenda B/App” management remote control when 

the <Configuration button/RC> parameter is set to “disabled”.

Parameters via remote control

The following parameters can be checked or changed via 

the remote control for support during start-up as well as 

servicing:

Parameter

Description

Can be 

checked 

SendoPro, 

theSenda 

B/App

Can be 

changed 

SendoPro, 

theSenda 

B/App

Can be 

changed 

theSenda 

P

Function C1/C2

Function C3

Selection: 

switching/control

x

x

Light measure-

ment source C3

Selection: Centre / 

Integral

x

Terminal S1 

assignment

Terminal S2 

assignment

Selection: C1 / C2 / 

C1+C2 / C3 / C1+C3 

/ C2+C3 / C1+C2+C3

x

Terminal S3/P 

assignment

Selection: Parallel / 

C1 / C2 / C1+C2 / 

C3 / C1+C3 / C2+C3 

/ C1+C2+C3

x

Brightness set 

point value 

C1, C2

Value range in lux/

measurement off

x

x

x

Brightness set 

point value C3

Value range in lux/

measurement off

x

x

Brightness 

actual value C1, 

C2, C3

Query brightness 

actual value

x

Room correc-

tion factor Win

Room correction 

factor on side 

towards window

x

x

Brightness 

measurement 

value Win

Lux meter bright

-

ness value on side 

towards window 

in lux

x

x

Room correc-

tion factor Mid

Room correction 

factor middle

x

x

Brightness 

measurement 

value Mid

Lux meter bright

-

ness value middle 

in lux

x

Room correc-

tion factor Inn

Room correction 

factor Inn

x

x

Brightness 

measurement 

value Ins

Lux meter bright

-

ness value interior 

in lux

x

Room correc-

tion factor Int

Room correction 

factor Integral

x

x

Brightness 

measurement 

value Int

Lux meter bright

-

ness value Integral 

in lux

x

Detection sen-

sitivity (PIR)

Value range in 

increments

x

x

x

Lighting time 

delay

Value range in 

seconds and 

minutes

x

x

Short presence

Short-term pre-

sence: On/Off

x

x

Energy saving 

mode

Selection: eco/eco 

plus

x

x

Presence 

switch-on delay

Value range in 

seconds/minutes

x

Presence time 

delay

Value range in 

seconds/minutes

x

x

Parameter

Description

Can be 

checked 

SendoPro, 

theSenda 

B/App

Can be 

changed 

SendoPro, 

theSenda 

B/App

Can be 

changed 

theSenda 

P

Switch-on 

dimming value 

C1, C2, C3

Value range in %

x

Configuration 

type C1/C2

Selection: auto/man

x

x

x

Configuration 

type C3

Selection: auto/man

x

x

Control speed

Selection: standard/

medium/fast

x

Minimum dim-

ming value

Value range in %

x

Maximum dim

-

ming value

Value range in %

x

Switching off 

brightness

Value range in 

minutes/hours/

never off

x

Manual dim-

ming response

Selection: school/

office

x

Standby time

Value range in 

seconds/minutes/

Permanently on

x

Standby dim-

ming value

Value range in %

x

IR group 

address C1, 

C2, C3

Selection: All/I/II/III

x

Scene 1 C1

Scene 2 C1

Scene for lighting 

channel C1 value 

range in %

x

Scene 1 C2

Scene 2 C2

Scene for lighting 

channel C2 value 

range in %

x

Scene 1 C3

Scene 2 C3

Scene for lighting 

channel C3 value 

range in %

x

Configuration 

button/RC

Selection: enabled/

disabled

x

LED display 

motion

Off/On

x

The parameters are sent to the presence detector with the 

“SendoPro, theSenda B/App” management remote control or 

with the “theSenda P” installation remote control via infra-red. 

Changed parameters are applied and used by the detector. 

 

L

Ensure that the parameter selection is limited on the „the-

Senda P“ remote control.

With the “SendoPro, theSenda B/App” management remote 

control, parameters can be queried by sending values level-

by-level to the detector. 

If the sent value is below the set 

parameter, the LED illuminates briefly. If the sent value is 

equal to or above the set parameter, the LED flickers for 2 s.

Function C1, C2

The lighting channels C1 and C2 can be operated together in 

the switching operation or constant lighting control function. 

Settings are made via the <Function C1/C2> parameter. 

Value range (with SendoPro, theSenda B/App)

Switching

Lighting channels C1 and C2 are in the switching operating 

function

Control

Lighting channels C1 and C2 light are in the constant lighting 

control function

Summary of Contents for 2080045

Page 1: ...al User remote control theSenda S option 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qualified electrician in accordance with the technical regulations applying to electri...

Page 2: ... automatically fully automa tic device or after the button is operated semi automatic device Lighting time delay The minimum time delay 10 s 60 min is adjustable It adjusts automatically to the user s behaviour and can incre ase to 30 minutes or drop back to the set minimum time With settings 2 min or 30 min the time delay remains unchanged at the set value If someone goes into an unoccu pied room...

Page 3: ...nnel As with 2 channel but with free choice between central light measurement A and integral light measurement average of light measurements A B C in the case of lighting channel C3 Switching Direct light influences the light measurement Avoid placing floor lamps or suspended lighting directly below the detector Constant light control The detector must be positioned in such a way that it only dete...

Page 4: ...er parallel switching Several masters can be used in parallel switching Each master controls its lighting groups according to its own brightness measurements Time delays and brightness setpoint values are set individually on each master Presence continues to be detected by all detectors Master DALI DALI DA DA S1 S2 S3 P N L N L EVG Master DA DA S1 S2 S3 P N L EVG Master with 2 lighting groups and ...

Page 5: ... mode Selection eco eco plus x x Presence switch on delay Value range in seconds minutes x Presence time delay Value range in seconds minutes x x Parameter Description Can be checked SendoPro theSenda B App Can be changed SendoPro theSenda B App Can be changed theSenda P Switch on dimming value C1 C2 C3 Value range in x Configuration type C1 C2 Selection auto man x x x Configuration type C3 Select...

Page 6: ...rightness The currently prevailing brightness is measured below the presence detector If the prevailing brightness is below the setpoint value the light is switched on when a presence is detected in configuration type fully automatic device A separate brightness setpoint value is available for each lighting channel C1 C2 C3 Value range Lux values with SendoPro theSenda B App manage ment remote con...

Page 7: ...ery sensitive By selecting the test presence operating mode the set sensi tivity increment is not changed Lighting time delay The time delay applies jointly to all lighting channels Value range Adjustable values with SendoPro 868 A manage ment remote control 10 s 60 min In the theSenda P installation remote control the following values are available 10 s button 30 s 60 s 2 min 10 min 20 min 60 min...

Page 8: ...nda B App Switches lighting off after a set amount of time 5 min 9 h Lighting is never switched off never off Manual dimming response With constant lighting control the manual dimming res ponse can be selected with the manual dimming response parameter Value range with SendoPro theSenda B App Constant light control remains active temporarily after manual dimming to the current brightness value as ...

Page 9: ...on and off together x Control command Description Can be triggered SendoPro theSenda B App Can be triggered theSenda P Teach in channel C1 Lighting channel C1 execution x x Teach in channel C2 Lighting channel C2 execution x x Teach in channel C3 Lighting channel C3 execution x Teach in channel C1 C2 C3 Activate for all lighting chan nels C1 C3 x Presence test On Off x x Light test On Off x Restar...

Page 10: ...s them in a list This stage is indicated by an LED flashing pattern 5 x on briefly every 3 s and depending on the size of the system can last up to 3 min If no DALI ECG is connected to the detector or a DALI line is interrupted the detector shows this with the LED flashing pattern LED is on and flashes off briefly twice every 3 s If the system is OK the detector automatically enters con figuration...

Page 11: ...mal operation and configuration is complete If so required the configuration can be completed by pressing End left hand function button In this case the system will not be ready for use If Change group assignment is selected the right arrow button can be used to switch to the next DALI ECG without changing the lighting group Otherwise the sequence remains the same When all desired changes have bee...

Page 12: ... Channel Operating voltage Colour Type Item number Ceiling installation Light 230 V AC White theRonda P360 330 DALI WH 2080045 Troubleshooting Fault Cause Light does not switch on and or off if pre sence is detected and in darkness Brightness setpoint value is set too low detector set on semi automatic light was switched off manually via button or theSenda S person not within detection area obstru...

Page 13: ...e en Cover clip for area restriction Item No 9070921 Details www theben de en theSenda P Item No 9070910 Details www theben de en theSenda S Item No 9070911 Details www theben de en theSenda B App Artikel Nr 9070985 Details www theben de en 13 Contact Theben AG Hohenbergstraße 32 72401 Haigerloch GERMANY Tel 49 7474 692 0 Fax 49 7474 692 150 Hotline Tel 49 7474 692 369 hotline theben de www theben...

Page 14: ...14 ...