background image

5

with the “theSenda P”. In this sense, the remote controls 

serve as set-up aids. A range of variable parameters is availa-

ble for adjustment with the remote control (see section “Para-

meters via remote control”).

Settings via the button 

Pressing the button for longer than 15 s triggers the teach-in 

of the brightness setpoint value by the teach-in function. In 

addition, the teach-in function can be conveniently executed 

with the „SendoPro, theSenda B/App“ management remote 

control or the “theSenda P” installation remote control (see 

section “Control commands via remote control”). 

The teach-in function via the button can be disabled using 

the „SendoPro, theSenda B/App“ management remote 

control when the “Configuration button” parameter is set to 

“disabled”.

Parameters via remote control

The following parameters can be queried or changed via 

the remote control for support during start-up as well as 

servicing:

Parameter

Description

Can be 

queried 

Sendo-

Pro / 

theSenda 

B (App)

Can be 

changed 

Sendo-

Pro / 

theSenda 

B (App)

Can be 

changed 

theSenda 

P

Function C1

Selection: 

switching/control

x

x

Brightness set 

point value C1

Value range in lux/

measurement off

x

x

x

Brightness 

actual value C1

Query brightness 

actual value

x

Room correction 

factor mid

Room correction 

factor

x

x

Brightness 

measurement 

value mid

Lux meter bright-

ness value in lux

x

Detection sensi-

tivity (PIR)

Value range in 

increments

x

x

x

Lighting time 

delay

Value range in 

seconds and 

minutes

x

x

Short presence

Short-term pre-

sence: On/Off

x

x

Energy saving 

mode

Selection: eco/eco 

plus

x

x

Presence switch-

on delay

Value range in 

seconds/minutes

x

Presence time 

delay

x

x

Switch-on dim-

ming value C1

Value range in %

x

Configuration 

type C1

Selection: auto/man

x

x

x

Control speed

Selection: standard/

medium/fast

x

Minimum dim-

ming value

Value range in %

x

Maximum dim-

ming value

Value range in %

x

Switch off 

brightness

Value range in 

minutes/hours/

never off

x

Manual dimming 

response

Selection: school/

office

x

Standby time

Value range in 

seconds/minutes/

permanently on

x

Parameter

Description

Can be 

queried 

Sendo-

Pro / 

theSenda 

B (App)

Can be 

changed 

Sendo-

Pro / 

theSenda 

B (App)

Can be 

changed 

theSenda 

P

Standby dim-

ming value

Value range in %

x

IR group address 

C1

Selection: all/I/II/III

x

Scene 1 C1

Value range in %

x

Scene 2 C1

Value range in %

x

Configuration 

button

Selection: enabled / 

disabled

x

LED display 

motion

Off/On

x

The parameters are sent to the presence detector with the 

„SendoPro, theSenda B/App“ management remote control or 

with the “theSenda P” installation remote control via infra-red. 

Changed parameters are applied and used by the detector. 

With the „SendoPro, theSenda B/App“ management remote 

control, parameters can be queried by sending values level-

by-level to the detector. If the sent value is below the set 

parameter, the LED illuminates briefly. If the sent value is 

equal or above the set parameter, the LED flickers for 2 s.

Function C1

The channel C1 light can be operated in the switching opera-

tion or constant lighting control function. Settings are made 

via the “Function C1” parameter. 

Value range (with the „SendoPro, theSenda B/App“)

Switching

Channel C1 light is in the switching operating function

Control

Channel C1 light is in the constant lighting control function

Further information can be found in the section “4. Function”, 

under the “Channel C1 light” section on page 1. 

Brightness set point value C1

The brightness setpoint value defines the minimum required 

brightness. The currently prevailing brightness is measured 

below the presence detector. If the prevailing brightness is 

below the setpoint value, the light is switched on when a 

presence is detected (in configuration type fully automatic 

device).

Value range

 

Lux values with „SendoPro, theSenda B/App“ manage-
ment remote control: 10 – 3000 lux, measuring off

 

The following values are available with the “theSenda 
P” installation remote control: 10, 15, 300, 500, 800 lux, 
measuring off (  button)

 

The currently measured brightness value (lux) can be 
adopted as a new brightness setpoint value with the 
„SendoPro, theSenda B/App“ management remote con-
trol by using the teach-in control command, or with the 
“theSenda P” installation remote control via the teach-in 

button. Values outside the permitted range will auto-

matically be set to the appropriate limit value.

Summary of Contents for 2080040

Page 1: ...ntrol SendoPro theSenda B App optional Installation remote control theSenda P option User remote control theSenda S option 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qual...

Page 2: ...ic device or after the button is operated semi automatic device Lighting time delay The minimum time delay 10 s 60 min is adjustable It adjusts automatically to the user s behaviour and can incre ase to 30 minutes or reduce back to the set minimum time With settings 2 min or 30 min the time delay remains unchanged at the set value If someone goes into an unoccu pied room only briefly and leaves it...

Page 3: ...m 452 m2 Ø 24 m 50 m2 Ø 8 m 28 m2 Ø 6 m 3 5 m 452 m2 Ø 24 m 50 m2 Ø 8 m 38 m2 Ø 7 m 4 0 m 452 m2 Ø 24 m 50 m2 Ø 8 m 5 0 m 452 m2 Ø 24 m 50 m2 Ø 8 m 6 0 m 452 m2 Ø 24 m 50 m2 Ø 8 m 10 0 m 491 m2 Ø 25 m 50 m2 Ø 8 m All figures are guidance value Detection areas according to sensNORM IEC 63180 see data sheet Brightness measurement The presence detector measures artificial lighting and day light The i...

Page 4: ...DALI DA DA L Slave S1 S3 P N P N Light measurement only with the Master Switch up to 10 detectors in parallel Use the same phase for all detectors and buttons Slave theRonda P360 Slave 2080080 Master Master parallel switching Several Masters can be used in parallel switching Each Master controls its lighting group according to its own bright ness measurements Time delays and brightness setpoint va...

Page 5: ...ription Can be queried Sendo Pro theSenda B App Can be changed Sendo Pro theSenda B App Can be changed theSenda P Standby dim ming value Value range in x IR group address C1 Selection all I II III x Scene 1 C1 Value range in x Scene 2 C1 Value range in x Configuration button Selection enabled disabled x LED display motion Off On x The parameters are sent to the presence detector with the SendoPro ...

Page 6: ... middle increment 3 Increments 1 to 5 can be selected and sent to the detector with the SendoPro theSenda B App management remote control On the theSenda P installation remote control the sensitivity can be decreased by one increment each time the button is pushed or increased with the button Value range Incre ment Sensitivity 1 Very insensitive 2 Insensitive 3 Standard 4 Sensitive 5 Very sensitiv...

Page 7: ...ghting is never switched off Never off Manual dimming response With constant lighting control the manual dimming res ponse can be selected with the manual dimming response parameter Value range with SendoPro theSenda B App Constant light control remains active temporarily after manual dimming to the current brightness value as the new setpoint value After the lighting time delay has expired the or...

Page 8: ...the lighting is switched on The lighting is switched off after 10 seconds when the room is unoccupied Brightness measurement is deactivated detector does not respond to brightness Constant light control is deactivated switching mode Standby function is deactivated The detector reacts as in configuration type fully auto matic device even if semi automatic is set Teach in cannot be activated in test...

Page 9: ... 101 IEC 62386 103 Product overview Type of installation Channel Operating voltage Colour Type Item number Ceiling installation Light 230 V AC White theRonda P360 110 DALI WH 2080040 Ceiling installation Light 230 V AC White theRonda S360 110 DALI WH 2080580 Troubleshooting Fault Cause Light does not switch on and or off if pre sence is detected and in darkness Brightness setpoint value is set too...

Page 10: ... de en Cover clip for area restriction Item No 9070921 Details www theben de en theSenda P Item No 9070910 Details www theben de en theSenda S Item No 9070911 Details www theben de en theSenda B App Artikel Nr 9070985 Details www theben de 13 Contact Theben AG Hohenbergstraße 32 72401 Haigerloch GERMANY Tel 49 7474 692 0 Fax 49 7474 692 150 Hotline Tel 49 7474 692 369 hotline theben de www theben ...