©Copyright Task Force Tips LLC 2004-2020
14
LIX-300 October 23, 2020 Rev22
4.0 INSTALLATION
4.1 ELECTRICAL INSTALLATION
See Remote Control (RC) Monitor Electrical Controls Supplemental Instructions LIY-500.
4.2 STRUCTURAL REQUIREMENTS
The structure that the monitor is mounted to must withstand the internal pressure of the monitor as well as shear and bending forces due
to nozzle reaction. Nozzle reaction can be as high as 1100 lbs (500 kg)(2100 gpm at 100 psi).
For flanged connections, the use of flat flanges without raised faces is recommended. Use a ring gasket as defined in ASME 16.21 or
ISO 7483. Tighten flange bolts in an alternating sequence as shown below. Tighten sequentially each bolt or stud three times to 30%,
then 60%, and finally 100% of the specified torque. Tighten to a total of 76-80 ft-lb (100-110 N·m).
Figure 4.2
4.2.1 MOUNTING THE MONITOR
The Hurricane Monitor is mounted on a riser pipe by a bolted flange or threaded joint. The area around the monitor must be free from
obstructions which would limit its range of motion and usefulness. If a valve is mounted under the HURRICANE, make sure the monitor
will not interfere with the valve handle. If a butterfly valve is mounted under the monitor make sure that the butterfly valve assembly does
not interfere with the flanged base.
WARNING
Reaction forces generated by master stream flows are capable of causing injury and property
damage if not properly supported. Monitors should be securely installed by qualified individuals.
• Mounting objects must be capable of withstanding maximum nozzle reaction force listed in
SPECIFICATIONS.
• The monitor must be securely mounted to rigid support members.
• Do not use flanges or pipe made from plastic for monitor mounting.
• Torque all fasteners to specified values.
1
3
2
4
1
5
3
7
2
6
4
8
Tighten Sequentially Each Bolt Three Times to a Total of 76-80 ft-lb (100-110 N·m)