441 Series Cable Feeding Sheaves
Greenlee / A Textron Company
4455 Boeing Dr. • Rockford, IL 61109-2988 USA • 815-397-7070
3
Operation
Select the proper size feeding sheave and insert into the
feeding end of the conduit run. The feeding sheave will
help guide the cable and decrease friction throughout
the pulling operation.
When the pull is completed, the sheave can be removed
easily by sliding the cable through the opening in the
insert tube.
Applications
Typical Setups
The illustrations below show several ways that Greenlee
Cable Feeding Sheaves can save time and reduce
UNOCCUPIED VAULT
UNOCCUPIED VAULT
UNOCCUPIED VAULT
ABOVE GROUND
Angle
of Pull
Angle
of Pull
Angle
of Pull
Angle
of Pull
ABOVE GROUND
FOR FEEDING ONLY
Pulling
Direction
UNOCCUPIED VAULT
friction while pulling cable. Always refer to cable
specifications for tension information.
Load Rating
Pulling
Direction
Angle
of Pull
Angle
of Pull
MAXIMUM PULLING LOADS (lb)
441-2"
441-2-1/2"
441-3"
441-3-1/2"
441-4"
441-5"
441-6"
15°
1750
1900
6050
8000
8000
8000
8000
30°
900
1000
3150
5050
7000
8000
8000
45°
650
700
2200
3550
5200
7400
7400
60°
500
550
1800
2900
4200
6000
6000
75°
450
500
1600
2600
3650
5500
5500
90°
450
500
1550
2500
3500
5250
5250