441 Series Cable Feeding Sheaves

Greenlee / A Textron Company

4455 Boeing Dr. • Rockford, IL 61109-2988 USA • 815-397-7070

3

Operation

Select the proper size feeding sheave and insert into the 

feeding end of the conduit run. The feeding sheave will 

help guide the cable and decrease friction throughout 

the pulling operation.
When the pull is completed, the sheave can be removed 

easily by sliding the cable through the opening in the 

insert tube.

Applications

Typical Setups

The illustrations below show several ways that Greenlee 

Cable Feeding Sheaves can save time and reduce 

UNOCCUPIED VAULT

UNOCCUPIED VAULT

UNOCCUPIED VAULT

ABOVE GROUND

Angle

of Pull

Angle

of Pull

Angle

of Pull

Angle

of Pull

ABOVE GROUND

FOR FEEDING ONLY

Pulling

Direction

UNOCCUPIED VAULT

 friction while pulling cable. Always refer to cable 

 specifications for tension information.

Load Rating

Pulling

Direction

Angle

of Pull

Angle 

of Pull

MAXIMUM PULLING LOADS (lb)

441-2"

441-2-1/2"

441-3"

441-3-1/2"

441-4"

441-5"

441-6"

15°

1750

1900

6050

8000

8000

8000

8000

30°

 900

1000

3150

5050

7000

8000

8000

45°

 650

 700

2200

3550

5200

7400

7400

60°

 500

 550

1800

2900

4200

6000

6000

75°

 450

 500

1600

2600

3650

5500

5500

90°

 450

 500

1550

2500

3500

5250

5250