FL-B101Q-DCA _ FL-B01Q-DCV (d0084)

Page 1

•  Standard Input Rnage

  – DCA
  

ID02 : DC mV ±20mV, ±50mV, ±100mV, ±200mV 

w/24V Exc.

  – DCV

 

 

ID01 : DC-Volts 

2V

/20V/200V

 w/24V Exc.

 

ID05 : DC-Volts 

2V

/20V/200V

 w/24V Exc. and Zero offset    

          adjustable pot

 

 

•  Two 9 Amp Form C, and two 4 Amp Form A relays available
•  Optional  isolated  16  bit  analog  output.  User  or  factory 

scalable to 4 to 20 mA, 0 to 20 mA or 0 to 10 V across any 

desired span from ± one bar to the full scale range

•  Provision  to  connect  an  external  programming  lockout 

switch. 

•  Optional NEMA-4 front cover.
•  24 V DC excitation is available to power external 4/20 mA

 

transmitters  and  5  or  10  V  DC  excitation  is  available  for

 

resistance bridge type sensors.

•  Four programmable setpoints.
•  Relays activation can be selected to occur above (HI) or 

below (LO) each setpoint.

•  UL Listed

Input Specs: ..............

Single-ended,  however  isolated  power  supply 

enables  differential  measurements  up  to  a 

maximum common mode of 50V.

 

A/D Converter: ..........14 bit single slope

Accuracy: ..................±(0.05% of r 1segment)

Temp. Coeff.: .............100 ppm/°C (Typical)

Warm up time: ...........2 minutes

Conversion Rate: ......10 conversions per second (Typical)

Bargraph Display: .....101 segment 4” vertical (std)

 

horizontal (optn), red (std), green (optn), 

Positive Overrange: ..Bargraph display flashes

Negative Overrange:

 

First segment of bargraph display flashes

Relay Output: ............Two  4  Amp  Form  A  relays  and  Two 

 

9 Amp Form C relays 

Analog Output: .........Isolated 16 bit user scalable mA or V

  OIC (mA out) ...........4-20 mA @ 0 to 500Ω max loop resistance

  OIV (volts out) .......... 0-10 V DC @ 500 Ω or higher resistance

Power Supply: ...........AC/DC Auto sensing wide range supply

 

PS1 (std) ................85-265 VAC, 50-400 Hz / 95-300 VDC @ 4.2W

  PS2 .........................15-48 VAC,50-400 Hz / 10-72 VDC @ 4.2W

Operating Temp.: ......0 to 50°C

Storage Temp: ...........–20°C to 70°C

Relative Humidity: ....95% (non condensing)

Case Dimensions: ....3/32 DIN, Bezel: 36x144 mm(1.42”x5.69”)

 

Depth  behind  bezel:  (4.64")  117.5  mm

 

Plus 10 mm (0.39”) for Right-angled con

-

nector, or plus 18.3 mm (0.72”) for Straight-

thru connector, or plus 26.5 mm (1.05”) for 

Push-On connector.

Weight: .......................9.5 oz., 12 oz when packed

General Features

Specifications

Index

LEOPARD FAMILY

Analog Output Scaling and Calibration . . . . . . . . . . . 9

Case Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Component Layout  . . . . . . . . . . . . . . . . . . . . . . . . .

11

Connector Pinouts . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Controls and Indicators . . . . . . . . . . . . . . . . . . . . . . . 2

Custom Face Plates and Scale. . . . . . . . . . . . . . . . 14

Glossary of Programming Symbols and Modes of 

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

General Features. . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Input Module Component Glossary. . . . . . . . . . . . . . .

13

Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

One Point Quickset Rescaling and Calibration 

Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . 15

Opening the Case to Access Mode Select Headers . . .4

Overview of Display Modes, Scaling Capabilities and 

Operation Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Pin Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Setpoint Adjust. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Setting the Colors  . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Standard Display Mode Calibration Procedure. . . . . 6

Two Point Quickset Scaling and Calibration . . . . . . . 5

DC Volts or DC Amps Meter Controller and 

Transmitter. 

 

Excelent replacement for Horizontal and 

Vertical Switchboard Meters.

FL-B101Q-DCA

20/50/100/200mV DC Full Scale

FL-B101Q-DCV

2/20/200V DC Meter

101 Segments in a 9/64 DIN Case

Summary of Contents for FL-B101Q-DCA

Page 1: ...s Analog Output Isolated 16 bit user scalable mA or V OIC mA out 4 20 mA 0 to 500 max loop resistance OIV volts out 0 10 V DC 500 or higher resistance Power Supply AC DC Auto sensing wide range supply...

Page 2: ...As there are no menu or sub menus to navigate the programming and setup is quick and Span Buttons Span Zero Buttons Zero Set Point Button SP1 SP2 SP3 SP4 Front Panel Buttons Zero Button The Zero Butt...

Page 3: ...alled Mode 3 Hysteresis Band between SP1 SP2 This mode enables the Hysteresis function In order for Hysteresis to function SP2 must be set to a value greater than SP1 and SP2 should be selected as Hig...

Page 4: ...ver and carefully lever the plastic catch up and tilt the Display Board assembly forward Then repeat this action with the bottom catches Step 5 Remove the entire Display Board assembly by sliding it o...

Page 5: ...or SPAN but ton is pressed the input signal being applied must be more than 5 higher or lower than the previously memorized value of the input signal that was being applied when the other button was...

Page 6: ...to 20mA If now the scaling has to be changed to read zero to full scale for an input of 0 to 20mA only the low 4 mA end needs to be recalibrated The high 20 mA end of the scaling is left untouched an...

Page 7: ...2 and SP4 activate when input is lower than set point SP1 and SP3 activate when input is equal to or higher than set point SP2 activate when input is lower than set point SP1 SP3 and SP4 activate when...

Page 8: ...SP2 color overrides the SP1 color STEP A ENTER COLOR SET MODE Hold down ALL four setpoint buttons SP1 SP2 SP3 and SP4 and apply power to the meter The meter will light up in the Color Set Mode Release...

Page 9: ...HI button adjust the analog output as measured on the external multimeter to be the required value 20mA in this example When the HI button is pressed the UP or DOWN indicator LED shows the direction o...

Page 10: ...T mA 0 to 20 mA 4 to 20 mA or V 0 to 10 V output is header selectable Pin 19 Programming LOCK By connecting the LOCK pin to the COMMON pin the meter s programmed parameters can be viewed but not chang...

Page 11: ...Pot Span Pot ID05 ID01 Zero Offset Pot Zero Offset Pot Input Range Header Input Range Header Input Range Header ID01 DC Volts 2 20 200V Custom w 24V DC Exc Custom 200V 20V 2V ON OFF 24V Exc 24V Exc D...

Page 12: ...or FI series IO board The adapter snaps on the 36x144 mm 1 42 x5 69 case and enables single unit or stack mounting in an existing 6 edgewise pointer meter cut out 100 0 25 50 75 100 0 25 50 75 SP1 SP2...

Page 13: ...into a Hi and a Lo range This has the effect of dividing the adjustment range of the SPAN pot into ten equal 10 steps across 100 of the input Signal Span Range HI LO HI LO SPAN Turn Clockwise to Incre...

Page 14: ...5 150 1500 2 20 200 2000 2 5 25 250 2500 3 30 300 3000 4 40 400 4000 4 5 45 450 4500 5 50 500 5000 6 60 600 6000 7 5 75 750 7500 8 80 800 8000 9 90 900 9000 1 2 12 120 1200 Div Face plate scales and n...

Page 15: ...g 5 93 PLUG5P DR Extra Screw Terminal Conn 5 Pin Plug 6 DN CAS144X36 Complete 144x36mm Case with bezel 25 OP MTL144X36 Metal Surround Case includes screw mounting clips 25 OP MTLCLIP Screw Mounting Cl...

Reviews: