background image

Texmate, Inc. Tel. (760) 598-9899  •  www.texmate.com

DL-40JANUS-SG manual (d0116)

Page 9

The following programming steps are required to enter the setpoint values and configure the relay 

functions in a meter with four relays using four setpoints. Generally if less than four relays are 

installed the software auto detects missing relays and deletes reference to them from the menu. In 

some cases setpoints without relays are operational for display only purposes.

STEP A  Enter the Setpoint Mode

 

1)  Press the 

P

 and   buttons at the same time. 

  Display toggles between [SP1] and the previous [SP1] setting.

STEP B  Set Setpoint 1 (SP1)

 

1)  Using the   and   buttons, adjust the display to the desired SP1 value.

 

2)  Press the 

P

 button. Display toggles between [doM] and the previous [doM] setting.

STEP C  Set the SP1 Delay-on-Make (doM) Delay Time Setting

 

1)  Using the   and   buttons, adjust the display to the desired [doM] value 

 

  (0 to 9999 seconds). The reading must continuously remain in an alarm condition    

until this delay time has elapsed before the relay will make contact (energize).

 

2)  Press the 

P

 button. Display toggles between [dob] and the previous [dob] setting.

STEP D  Set the SP1 Delay-on-Break (dob) Delay Time Setting

 

1)  Using the   and   buttons, adjust the display to the desired [dob] value (0 to 9999  

  seconds). The reading must continuously remain in an non-alarm condition until this  

  delay time has elapsed before the relay will break contact (de-energize).

 

2)  Press the 

P

 button. Display toggles between [HYSt] and the previous [HYSt] setting.

STEP E  Set the Hysteresis Setting for Setpoint 1

 1) 

Using the   and   buttons, adjust the display to the desired hysteresis [hYSt] value.

 

2)  Press the 

P

 button. Display toggles between [SP2] and the previous [SP2] setting.

  

NOTE: Half of the Hysteresis value selected is applied above and below the setpoint.

NOTE: Steps F, G, H and J have functionally the same procedure as steps B, C, D, and E shown above. 
STEP F  Set Setpoint 2 (SP2)

STEP G  Set the SP2 Delay-on-Make (doM) Delay Time Setting

STEP H  Set the SP2 Delay-on-Break (dob) Delay Time Setting

STEP I  Set the Hysteresis Setting for Setpoint 2

 1) 

Using the   and   buttons, adjust the display to the desired hysteresis [HYSt] value.

 

2)  Press the 

P

 button. Display toggles between [SP3] and the previous [SP4] setting.

STEP J  Set Setpoint 3 (SP3) (No [doM] or [dob])   

1)  Using the   and   buttons, adjust the display to the desired SP3 value.

 

2)  Press the 

P

 button. Display toggles between [HYSt] and the previous [HYSt] setting.

STEP K  Set the Hysteresis Setting for Setpoint 3

 1) 

Using the   and   buttons, adjust the display to the desired hysteresis [HYSt] value.

 

2)  Press the 

P

 button. Display toggles between [SP4] and the previous [SP4] setting.

STEP L  Set Setpoint 4 (SP4) (No [doM] or [dob])

 

1)  Using the   and   buttons, adjust the display to the desired SP4 value.

 

2)  Press the 

P

 button. Display toggles between [HYSt] and 0.

STEP M  Set the Hysteresis Setting for Setpoint 4

 1) 

Using the   and   buttons, adjust the display to the desired hysteresis [HYSt] value.

 

2)  Press the 

P

 button. Display toggles between [rLYS] and the previous relay setting.

STEP N  Set Relay Activation mode [rLYS]

  

(H) High the relay energizes when the setpoint is exceeded. (L) Low the relay energizes   

below the setpoint. The setpoint is indicated from left to right SP1, SP2, SP3, SP4.

 

1)  Using the   and   buttons, adjust the reading on the display to the desired  

 

relay settings: [LLLL], [LHLH], [HLHL], [HHHH].  

  If only 2 relays installed [LH--], [HL--], [HH--], [LL--].

 

2)  Press the 

P

 button.

 

  The meter exits the setpoint mode and returns to the operational display.

The Setpoint Relay programming mode is now complete.

Setpoint Setting and Relay Configuration Mode 

SETPOINT SETTING  AND 

RELAY CONFIGURATION MODE

See Page 9

STEP B  

Set 

Setpoint 1 (SP1)

STEP C  

Delay on 

Make (doM)

STEP D  

Delay on

Break (dob)

STEP F  

Setpoint 2 

(SP2)

STEP E  

Hysteresis

(HYSt)

STEP I  

Hysteresis

(HYSt)

STEP K  

Hysteresis

(HYSt)

STEP M  

Hysteresis

(HYSt)

STEP N  

Relays 

Activation [rLYS]

Confirm

STEP G  

Delay on 

Make (doM)

STEP H  

Delay on 

Break (dob)

STEP J  

Setpoint 3

(SP3)

NOTE: [dob] [dom] 

Functions are 

only available for 

SP1 and SP2

STEP L  

Setpoint 4

(SP4)

MAIN MENU

Operational Display

STEP A

[LHLH]

[HLHL]

[HHHH]

Summary of Contents for DL-40JANUS-SG

Page 1: ...utput Range Setting and Calibration 6 General Features Specifications Software Features Index LEOPARD FAMILY DL 40JANUS SG Two scaling methods MANUAL no external sig nal source required and AUTO requi...

Page 2: ...by pressing and releasing the or buttons When there are more than two display selec tions they are shown in brackets below the first display and are also selectable by press ing and releasing the or b...

Page 3: ...L POINT AND BRIGHTNESS SELECTION See Page 6 Setpoint 3 SP3 Setpoint 4 SP4 Valley Offset Scale Factor Calibrate Analog Output Lo Calibrate Analog Output Hi X XXX XX XX XXX X XXXX XXXX 2 3 4 Decimal Poi...

Page 4: ...t STEP B Select Between Calibration of Input or Output Note If the analog output option is not present Step B is skipped and the program goes directly from Step A to Step C 1 Press the or button to se...

Page 5: ...Point Analog Output Note If the analog output option is not present Step B is skipped and the program goes directly from Step A to Step C 1 Press the or button to select the display toggling from CAL...

Page 6: ...s the P and buttons at the same time Display toggles between CAL and oFF 2 Press the P button Display shows previous dP selection STEP E Set the Decimal Point 1 Using the and adjust the display to the...

Page 7: ...unts and does not include the deci mal point If you need the decimal value with decimal point you will need to read the register convert it to decimal read 40024 see below to determine decimal locatio...

Page 8: ...ST2 Setpoint 2 Hysteresis setting 40019 0x0012 SINT16 R W 1999 9999 PRES3 Setpoint 3 setting 40020 0x0013 UINT16 R W 0 9999 HYST3 Setpoint 3 Hysteresis setting 40021 0x0014 SINT16 R W 1999 9999 PRES4...

Page 9: ...P2 Delay on Make doM Delay Time Setting STEP H Set the SP2 Delay on Break dob Delay Time Setting STEP I Set the Hysteresis Setting for Setpoint 2 1 Using the and buttons adjust the display to the desi...

Page 10: ...with external signal OFF 17 16 19 19 18 MANUAL rescaling ON AUTO scaling OFF ON SP1 NO SP1 NO SP2 NO SP2 NO Pins 14 and 15 AC DC Power Input Auto sensing AC DC power supply For voltages between 85 265...

Page 11: ...air circulation 3 Separate input output leads from power lines to protect the meter from external noise Input output leads should be routed as far away as possible from contactors control relays tran...

Page 12: ...71 1 8 DIN Cutout spacers 87 4mm 3 45 Various bezel colors are available Black is standard Prog SP3 SP4 SP2 SP1 For additional strength extra Mounting Slide Clips can be ordered and doubled up one beh...

Page 13: ...se is made from fire retardant polycar bonate A metal surround case can be ordered to enhance the meter s fire retardant capabilities and also provide shielding against electromagnetic interference EM...

Page 14: ...OA____ DL 40JANUS SG Add to the basic model number the order code suffix for each standard option required The last suffix is to indicate how many different special options and or accessories that you...

Reviews: