Page 14
DL-40JANUS-DCA/DCV manual (d0114)
Case Dimensions
96 mm
(3.78")
48 mm
(1.89")
3.9 mm
(0.15") typical
FRONT VIEW
1/8 DIN 96x48mm
These dimensions are
increased by 1.6mm (0.06")
when the metal surround
case is installed.
The 96x48mm case is
particularly suitable for
mounting in mosaic panels
or insulative panels up to 2"
thick. They can also stack
mount, 2 up in existing
cutouts for 1/4 DIN
(96x96mm) or 4 up in
1/2 DIN (96X192mm).
NOTE: The Metal Surround Case
is pre-installed at the factory and cannot
be removed without damage to the case.
Metal Surround Case
P/N:(OP-MTL96X48)
uses
Metal Screw Mount Clips
and has a max. panel
thickness mounting
of 15.5 mm (0.61").
Removable
Key-lock
Cam
Opening
Safety
Catch
Clear Lockable NEMA 4X
Splash Proof Cover
P/N:(OP-N4/96x48)
40.8 mm
(1.61")
117 mm
(4.61")
SIDE VIEW
5.3 mm
(0.21")
3.7mm
(0.15")
43.4 mm
(1.71")
DIN Cutout spacers
Straight-thru Connector for
meters with output board
20mm (0.79")
Right-angled Connector
11.8mm (0.47")
PANEL CUTOUT
Case will mount in standard 1/8 DIN cutouts
45 mm
(1.77")
Snug Fitting
Mosaic Fitting
92 mm
(3.62")
Loose Fitting
91.6mm
(3.6")
40.8mm
(1.61")
8 places
3mm
(0.12")
8 places
4mm
(0.16")
43.4mm
(1.71")
1/8 DIN
Cutout spacers
87.4mm
(3.45")
Various bezel
colors are available.
Black is standard.
Prog.
SP3
SP4
SP2
SP1
For additional strength, extra Mounting
Slide Clips can be ordered and doubled up
one behind the other. P/N: (75-DMTCLIPF)
TOP VIEW
87.4mm
(3.45")
mosaic
fitting
95.4mm
(3.77")
Max. panel thickness
50mm
(1.97")
96 mm
(3.78")
91.6mm
(3.6")
DIN
Cutout
Spacer
To open rear cover,
use a small flat
bladescrew driver.
Press down lightly to
release catch on top
or bottom of case
and leaver outwards.
4.7mm
(0.19")
DIN Cutout Spacer
2mm
(0.08")
Connector
Socket
Prog.
SP1
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP1
SP2
SP4
SP3
SP5
SP6
Prog.
SP1
SP1
SP2
SP4
SP3
SP5
SP6
When extra panel
mounting tightness is
required, order the
optional screw mount clip.
P/N:(OP-MTLCLIP)
High Strength Panel
Mounting Kit
P/N: OP-PMA96X48
For extra strength in portable applications, the 8 DIN
spacers should be snipped off and the Mosaic fitting
cutout used. Alternatively, the High Strength Panel
Mounting Kit (Part # OP-PMA96X48) can be used.
Panel adaptor plates are
available to retrofit most
existing panel cutouts.
Installation Guidelines
Installation
1. Install and wire meter per local applicable codes/reg-
ulations, the particular application, and good installation
practices.
2. Install meter in a location that does not exceed the
maximum operating temperature and that provides
good air circulation.
3. Separate input/output leads from power lines to
protect the meter from external noise. Input/output
leads should be routed as far away as possible from
contactors, control relays, transformers and other noisy
components. Shielding cables for input/output leads is
recommended with shield connection to earth ground
near the meter preferred.
4. A circuit breaker or disconnect switch is required to
disconnect power to the meter. The breaker/switch
should be in close proximity to the meter and marked as
the disconnecting device for the meter or meter circuit.
The circuit breaker or wall switch must be rated for the
applied voltage (e.g., 120VAC or 240VAC) and current
appropriate for the electrical application (e.g., 15A or
20A).
5. See
Case Dimensions section
for panel cutout infor-
mation.
6. See
Connector Pinouts section
for wiring.
7. Use 28-12 AWG wiring, minimum 90˚C (HH) tempera-
ture rating. Strip wire approximately 0.3 in. (7-8 mm).
8. Recommended torque on all terminal plug screws is
4.5 lb-in (0.51 N-m).