background image

Texmate, Inc. Tel. (760) 598-9899  •  www.texmate.com

Page 2

DL-40JANUS-DCA/DCV manual (d0114)

Symbol

Explanation

This symbol represents the 

OPERATIONAL DISPLAY.

This is the PROGRAM button.

This is the UP button.

This is the DOWN button.

When a button is shown, press and 

release it to go onto the next step in the 

direction indicated by the arrow. When two 

or more buttons are shown, each with an 

arrow, this indicates that there is a number 

of programming choices.

When two buttons are shown side by side 

and enclosed by a dotted line, they must 

be pressed at the same time then released 

to go onto the next programming step.

If the display is shown with XXXX it means 

the value displayed will be the previously set 

value. When a number is shown it indicates 

the initial factory default setting or a specific 

“example number”.

P

P

When two displays are shown together with 
bursts, this indicates that the display is  
toggling (flashing) between the name of the 
function and the value.

Text or numbers shown between square 
brackets in a procedure indicate the pro-
gramming code name of the function or the 
value displayed on the meter display.

When the    and    buttons are shown 
together, the display value can be increased 
by pressing and releasing the    button  
or decreased by pressing and releasing the 

 button.

When the    and    buttons are shown  
with two displays, either display can be 
selected by pressing and releasing the   or 

 buttons.

When there are more than two display selec-
tions they are shown in brackets below the 
first display and are also selectable by press-
ing and releasing the   or   buttons.

A dotted box indicates these functions are 
omitted or bypassed when the related hard-
ware is not present

To explain software programming procedures, logic diagrams are

used to visually assist in following the programming steps. The 

fol-lowing symbols are used to represent various functions and 

associated display elements of the meter:

DOWN ARROW

BUTTON

Setpoint 

Annunciator 

LEDs

SP4
SP3
SP2
SP1

PROGRAM

BUTTON

P

Setpoint 

Annunciator LEDs

SP1 SP2 SP3 SP4   

[LHLH]
[HLHL]

[LLLL]

Front Panel Buttons

Program Button

The 

P

 button is used to move from one program step to the next. 

When pressed at the same time as the    button, it initiates the  

calibration mode. When pressed at the same time as the   but-

ton, it initiates the setpoint setting mode.

Up Button

When in the operational display, pressing the    button alone, 

allows you to view and reset the Peak and Valley  (Highest and 

Lowest Readings.)
When in the calibration mode or the setpoint setting mode the 

 button is used to increase the value of the displayed parameter.

Down Button

When in the operational display, pressing the    button alone, 

allows you to view, but not change, the setting of  setpoint 1,2,3 

& 4.
When in the calibration mode or the setpoint setting mode the 

 button is used to decrease the value of the displayed parameter.

Glossary of Programming Symbols

Controls and Indicators

[ScAL] 

       [9999]

UP ARROW 

BUTTON

Summary of Contents for DL-40JANUS-PROCESS

Page 1: ...l Features Specifications Software Features Index LEOPARD FAMILY DL 40JANUS PROCESS Two scaling methods MANUAL no external sig nal source required and AUTO requied an exter nal signal source Optional...

Page 2: ...ed by pressing and releasing the or buttons When there are more than two display selec tions they are shown in brackets below the first display and are also selectable by press ing and releasing the o...

Page 3: ...MAL POINT AND BRIGHTNESS SELECTION See Page 6 Setpoint 3 SP3 Setpoint 4 SP4 Valley Offset Scale Factor Calibrate Analog Output Lo Calibrate Analog Output Hi X XXX XX XX XXX X XXXX XXXX 2 3 4 Decimal P...

Page 4: ...out STEP B Select Between Calibration of Input or Output Note If the analog output option is not present Step B is skipped and the program goes directly from Step A to Step C 1 Press the or button to...

Page 5: ...wo Point Analog Output Note If the analog output option is not present Step B is skipped and the program goes directly from Step A to Step C 1 Press the or button to select the display toggling from C...

Page 6: ...ress the P and buttons at the same time Display toggles between CAL and oFF 2 Press the P button Display shows previous dP selection STEP E Set the Decimal Point 1 Using the and adjust the display to...

Page 7: ...counts and does not include the deci mal point If you need the decimal value with decimal point you will need to read the register convert it to decimal read 40024 see below to determine decimal locat...

Page 8: ...HYST2 Setpoint 2 Hysteresis setting 40019 0x0012 SINT16 R W 1999 9999 PRES3 Setpoint 3 setting 40020 0x0013 UINT16 R W 0 9999 HYST3 Setpoint 3 Hysteresis setting 40021 0x0014 SINT16 R W 1999 9999 PRE...

Page 9: ...e SP2 Delay on Make doM Delay Time Setting STEP H Set the SP2 Delay on Break dob Delay Time Setting STEP I Set the Hysteresis Setting for Setpoint 2 1 Using the and buttons adjust the display to the d...

Page 10: ...g with external signal OFF 17 16 19 19 18 MANUAL rescaling ON AUTO scaling OFF ON SP1 NO SP1 NO SP2 NO SP2 NO Pins 14 and 15 AC DC Power Input Auto sensing AC DC power supply For voltages between 85 2...

Page 11: ...es with 4 Independent 400V 210mA DC only SSRs DL 40JANUS Series 29 28 27 25 26 24 23 22 Options Order Code OR32 4A 4A 4A 4A 4A 4A OR34 4A 4A 4A 4A 4A 4A SP4 SP3 SP2 SP1 SP1 SP2 SP3 SP4 Relay Modules w...

Page 12: ...XC FullyUserScalable PIN 2 PIN 1 PIN 3 _ Exc On Off Header SPAN Pot HI LOW SPAN RANGE Header ZERO Pot ZERO ADJUST Header SPAN ADJUST Header ZERO OFFSET RANGE Header Decrease Increase Decrease Increase...

Page 13: ...ar 15 Turn Potentiometer 100 Counts 100 Counts 0 ZERO Potentiometer Pot If provided the ZERO pot is always to the left of the SPAN pot as viewed from the rear of the meter Typically it enables the inp...

Page 14: ...4 7mm 0 19 DIN Cutout Spacer 2mm 0 08 Connector Socket Prog SP1 SP1 SP2 SP4 SP3 SP5 SP6 Prog SP1 SP1 SP2 SP4 SP3 SP5 SP6 Prog SP1 SP1 SP2 SP4 SP3 SP5 SP6 When extra panel mounting tightness is requir...

Page 15: ...case is made from fire retardant polycar bonate A metal surround case can be ordered to enhance the meter s fire retardant capabilities and also provide shielding against electromagnetic interference...

Page 16: ...RELAY OUTPUT OPTIONS ACCESSORIES OA____ DL 40JANUS PROCESS Add to the basic model number the order code suffix for each standard option required The last suffix is to indicate how many different spec...

Reviews: