background image

Page 4

CL-B101D40RPM(d0097) manual

STEP A  Enter the Calibration Mode

 1) 

Press the 

P

 and   buttons at the same time. Display tog-

gles between [CAL] and [oFF].

 

2)  Press the   or   button. Display changes from [oFF] to 

[on].

 3) 

Press the 

P

 button. Display toggles between [CAL] and 

[out].

Note:

 If at this point, the display skips directly to STEP C and toggles 

between [SPAn] and the previous [SPan] setting, the software is 

detecting that the optional analog output hardware is NOT installed.

STEP B  Select Pulese Per Revolution, Range Slection

 

1)  Press the   or   button to select CAL [iP] for Pulses Per 

Revolution Slection.

 

2)  Press the 

P

 button. Display toggles between [PPr] and 

the previous Pulses Per Revolution setting.

STEP C  Enter the Pulese Per Revolution (PPR)

 

1)  Using the   and   buttons, enter the number of pulese 

per revolution. Any number between 1 and 9999 may be 

enterd.

 

2)  Press the 

P

 button. Display toggles between [rg] and the 

previous range setting.

STEP D  Select the Range

 

1)  Using the   and   buttons, selete the required range. 

There are three ranges with resolutions of 0.1 (max. 999.9 

RPM), 1 (max. 9999 RPM) and 10 RPM (max. 99.99 x 10000 

RPM)

 

2)  Press the 

P

 button.

Pulses Per Revolution and Range Selection

MAIN MENU

Operational Display

Sub-menu 

MODE

STEP A  Calibration

Mode

STEP B  Calibration

Mode

STEP C  PPR

STEP D  Range

To Digital Span Selection for

Bargraph Display Page 5

cAL out/iP branch will only

appear if the analog output

option is installed, otherwise

cAL on goes directly to ZEro

setting

 PULSES PER 

REVOLUTION, RANGE

SELECTION

To Digital Span Selection

for Bargraph Display

See Page 6

To Two Point Analog

Output Range Setting

and Calibration

See Page 7

[0.1]

[1]

[10]

Summary of Contents for CL-B101D40RPM

Page 1: ...Conventions 2 Input Specs Depends on Input signal conditioner A D Converter 14 bit single slope Accuracy 0 05 of reading 2 counts Temp Coeff 100 ppm C Typical Warm up time 2 minutes Conversion Rate 10 conversions per second Typical Digital Display 4 digit 0 56 LED red std green optn Range 0 to 9999 counts Bargraph Display 101 segment 235º circular bar red std green optn or tricolor optn Polarity A...

Page 2: ...xplain software programming procedures logic diagrams are used to visually assist in following the programming steps The following symbols are used throughout the logic diagrams to represent the buttons and indicators on the meter Programming Conventions X XXX XX XX XXX X XXXX XXXX Front Panel Buttons Program Button The P button is used to move from one program step to the next When pressed at the...

Page 3: ...INT VIEW MODE Bargraph Center Point Display Selection cto This branch will only appear if the analog output option is installed Back to Operational Display Digital Display ON OFF Selection diSP Sub menu MODE Calibration Mode Calibration Input Calibration Output Calibrate Analog Output Low cLo Calibrate Analog Output High chi Select the Digital Reading at which the Analog Output Hi chi will occur S...

Page 4: ...lution PPR 1 Using the and buttons enter the number of pulese per revolution Any number between 1 and 9999 may be enterd 2 Press the P button Display toggles between rg and the previous range setting STEP D Select the Range 1 Using the and buttons selete the required range There are three ranges with resolutions of 0 1 max 999 9 RPM 1 max 9999 RPM and 10 RPM max 99 99 x 10000 RPM 2 Press the P but...

Page 5: ...p for Input Signals up to 3999 counts Bargraph lights up for Input Signals above 4000 counts Bar High Bar Low Bar High Bar Low 0 25 75 100 50 0 25 75 100 50 No bargraph display Digital display No bargraph display Digital display An example of setting the digital span of the bargraph display to be different than the digital display range The bargraph can be set to display full scale 0 101 bars any ...

Page 6: ... is off If the digital display is selected to be off pressing any button to make programming changes or to view setpoints activates the digital display When the procedure is complete the digital display will then automatically switch off The Display Bargraph settings are now complete Operational Display STEP E STEP F See Example of Bargraph Center Point Display Mode Selection Above From Digital Sp...

Page 7: ...any value from 0 3 mA to 18 mA mA output selected or from 0 6 V to 8 V volt output selected However the output of cLo must always be less than the value selected for chi If a reversed analog output is desired the values selected to establish the Digital Span can be reversed see top of page 6 For digital readings outside the Digital Span selected the analog output will not go any lower than the cal...

Page 8: ...to the desired hysteresis hYSt value 2 Press the P button Display toggles between SP2 and the previous SP2 setting STEP F Set Setpoint 2 SP2 1 Using the and buttons adjust the display to the desired SP2 value 2 Press the P button Display toggles between hySt and the previous hySt setting STEP G Set the Hysteresis hYSt Setting for Setpoint 2 1 Using the and buttons adjust the display to the desired...

Page 9: ...Bargraph Color when the bar is ABOVE SP2 Setpoint 1 Using the and buttons select the desired bargraph color grn oran or red 2 Press the P button Display toggles between CSP3 and the previous color setting STEP T Select Bargraph Color when the bar is ABOVE SP3 Setpoint 1 Using the and buttons select the desired bargraph color grn oran or red 2 Press the P button Display toggles between CSP4 and the...

Page 10: ...rminal plugs and do not insert remove or handle screw terminal plugs with live wires connected 17 16 14 15 8 9 10 11 See Leopard Family Input Signal Conditioning Modules 1 2 3 4 5 6 21 20 19 Relay Outputs Reserved for RS 485 LOCK COMMON No Function DIM ANALOG OUTPUT AC Neutral DC AC Line DC ANALOG OUTPUT 29 28 27 26 25 24 23 22 Standard plug in screw terminal connectors provided by Texmate Connect...

Page 11: ...SP4 SP2 Relay Modules with 2 Non Isolated 4A Form A Relays and 2 Non Isolated 9A Form C Relays 29 28 27 25 26 24 23 22 DL Series Options Order Code OR51 OR52 OR53 OR54 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA 210mA SP4 SP3 SP2 SP1 SP4 SP3 SP2 SP1 Relay Modules with 4 Independent 300V 210mA DC only 29 28 27 25 26 24 23 22 DL Series Options Order Code OR31 OR32 OR33 OR34 5A 5A 5A 5A 5A ...

Page 12: ...s for input output leads is recommended with shield connection to earth ground near the meter preferred 4 A circuit breaker or disconnect switch is required to disconnect power to the meter The breaker switch should be in close proximity to the meter and marked as the disconnecting device for the meter or meter circuit The circuit breaker or wall switch must be rated for the applied voltage e g 12...

Page 13: ...en LED Bargraph w 4 Digit Red DPM Horizontal 20 HRG Red LED Bargraph w 4 Digit Green DPM Horizontal 15 HTG Tri Color Bargraph w 4 Digit Green DPM Horizontal 60 HTR Tri Color Bargraph w 4 Digit Red DPM Horizontal 50 DSGG Dual Scale Green LED Vertical Bargraph w 4 Digit Green DPM 30 DSGR Dual Scale Green LED Vertical Bargraph w 4 Digit Red DPM 20 DSRG Dual Scale Red LED Vertical Bargraph w 4 Digit G...

Reviews: