background image

Texmate, Inc. Tel. (760) 598-9899  •  www.texmate.com

Page 2

   BX-B31 Data Sheet (BX3)

Functional Diagram

Pins 1 to 6 - Input Module: See the individual pin out of the input sig-
nal conditioning module selected. Usually Pin 1 is the Signal Input High
pin and Pin 3 is the Signal Input Low pin. All calibration and scaling
functions are performed on the individual input signal conditioner mod-
ule. See pages 6 and 7.
Pin 8 - Common of 10 Amp Form C or 5 Amp Form A SP1 Relay.

Pin 9 - Normally Closed Contact of 10 Amp Form C SP1 Relay.

Pin 10 - Normally Open Contact of 10 Amp Form C or 5 Amp Form A
SP1 Relay.

Pin 11 & Pin 12- Normally Open Contacts of 5 Amp Form A SP2
Relay.

Pin 14 & Pin 15 - AC/DC Power Input: These pins are the power pins
of the meter and they only accept a special polarized screw terminal
plug that can not be inserted into any other input socket. The stan-
dard meter has a auto sensing AC/DC power supply that operates
from 85-265 VAC/95-370 VDC (PS1 Std). An optional isolated low
voltage power supply that operates from 15-48 VAC/10-72 VDC (PS2) is
also available.

Connector Pinouts

Pin Descriptions

Pin Socket

Pin Socket

Right-angled

Screw Terminal Plug

Input Power

Screw Terminal Plug

Connectors

15 to 48 VAC
10 to 72 VDC

85 to 265 VAC
95 to 370 VDC

NC 1

NO 1

COM 2

NO 2

9

8

1

2

3

4

5

6

10 11 12

14 15

AC 

Neutral

– DC

AC 

Line

+ DC

See Lynx Family Input 

Signal Conditioning Modules

PS2

PS1

COM 1

This meter comes standard with screw terminal plug connections.

Top Catches  

TO REMOVE REAR COVER  

Release From Bottom   

This meter uses plug-in type screw terminal connectors for all input
and output connections. The power supply connections (pins 14
and 15) have a unique plug and socket outline to prevent cross con-
nection. The main board uses standard right-angled connectors.

I-

Series Input Signal

Conditioning Module

NO 2

NC 1

NO 1

9

10
11
12

14

15

2

3

5

1

4

1

2

3

4

5

6

7

8

9

10

Input and output 
pins vary for 
different modules. 
Please see the 
specific module 
data sheet for 
details.

1.25 V 

Bandgap 

Reference

BX-B31 Functional Diagram with one 10 Amp Form C 

and one 5 Amp Form A Relay

AC Neutral, – DC

AC Line, + DC

AC/DC Power Input

1    3    5    7    

2 4 6 8

9    

1 0

Socket for Input Signal
Conditioning Module

Input Hi
Input Lo

+5VDC

-5VDC

+24VDC

Analog Common

System Ground

24 V Return

Amplifier

Circuit

Proportional

Brightness

Circuit

Proportional

Brightness Pot

Relay Activation

Selection Header

10K

Comparators

and LED

1 to 10

Driver Circuit

Comparators

and LED

11 to 20

Driver Circuit

Comparators

and LED

21 to 30

Driver Circuit

Com 1 8

SP1 Relay

Driver Circuit

SP2 Relay

Driver Circuit

BX-B31 with no setpoints

BX-B31 with 1 setpoint

BX-B31 with 2 setpoints

5A

SP2

+5 V

+5 V

10A

SP1

+5 V

5A

SP2

8

NO 1

9

NO 1

NO 2

10
11
12

with two 5 Amp Form A relays

14

15

5A

+5 V

SP1

AC Neutral, – DC

AC Line, + DC

AC/DC Power Input

Low 1

High 1

Low 2

High 2

NTC

EMI Filter

Isolated 

Switching 

Supply

-5 V DC

+5 V DC

+24 V DC

ISO
GND

GND

+15 V DC

ISO
GND

NTC

EMI Filter

Isolated 

Switching 

Supply

-5 V DC

+5 V DC

+24 V DC

ISO
GND

GND

+15 V DC

ISO
GND

FRONT OF METER WITH BEZEL AND FILTER REMOVED

To adjust the setpoint on the BX-B31 with relays, remove the
front bezel and faceplates. Use needlenose pliers to remove
and reposition the setpoint jumper clips.

For Setpoint #1: Insert the jumper clip between Row #1 and
Row #2, directly below the LED that you wish to activate.

For Setpoint #2: Insert the jumper clip between Row #2 and
Row #3, directly below the LED that you wish to activate.

LEDs

Row 1
Row 2
Row 3

Custom Face Plates

Changing the Setpoints From the Front of the Meter

Low 1

High 1

Low 2

High 2

Relay Activation Select Header

Select High to energize the relay when the setpoint is
exceeded. Select Low to energize the relay when the
display is below the setpoint.

The Proportional Brightness Potentiometer superimposes a proportion-
al brightness band to the leading edge of the bargraph which creates

Proportional Brightness Band Potentiometer

WARNING

:

AC and DC input signals and power

supply voltages can be hazardous. Do Not connect

live wires to screw terminal plugs, and do not insert, remove or

handle screw terminal plugs with live wires connected.

!

Texmate Produces Thousands of Custom

OEM Face Plates 

Have Texmate Design and Build a Custom Face Plate

to Suit your Next project!

• Custom face plates have a non-recurring artwork

charge. A serial number is then assigned to each

artwork, to facilitate re-ordering.

• Small Run or One-Off custom face plates incur an installation charge,

and are generally printed on a special plastic film, which is then lami-

nated to custom faceplate blanks as required.

• Large Run (250 pieces min): custom face plates are production silk

screened, issued a part number, and held in stock for free installation

as required by customer orders.

• OEMs may also order Custom Meter Labels, Box Labels    Custom

Data Sheets and Instruction Manuals.

the optical appearance of a pointed arrow      . This feature produces a
display of infinite resolution. The position of the signal in relation to any
two adjacent segments and the scale on the faceplate can be accu-
rately ascertained to within 1%. When the amplitude of the proportion-
al band is adjusted counterclockwise to zero, the smooth proportional
advance of the display will be replaced by a step by step movement as
each bar is either turned full on or full off.

Summary of Contents for BX-B31

Page 1: ...of meters As shown on pages 4 to 5 See www texmate com for an up to date listing 31 segment AC DC powered modular compact bargraph 1 16 DIN 96 x 24mm case easily mounts in thin or thick panels up to 2...

Page 2: ...SP2 Relay Driver Circuit BX B31 with no setpoints BX B31 with 1 setpoint BX B31 with 2 setpoints 5A SP2 5 V 5 V 10A SP1 5 V 5A SP2 8 NO 1 9 NO 1 NO 2 10 11 12 with two 5 Amp Form A relays 14 15 5A 5 V...

Page 3: ...white on black face plate will be provided as standard Alternatively a face plate with black letters on a white background or a blank white or black face plate may be ordered as a no charge substitut...

Page 4: ...ion Special Options on last page ALL MODELS Symbols Indicate Module Compatibility Within Meter Families SOME MODELS MODEL SPECIFIC TIGER Family LEOPARD Family LYNX Family TIGER Family LEOPARD Family L...

Page 5: ...ormity error to NIST tables at 25 C J 2 C 1 digit typical J 4 F 1 digit maximum K 3 C 1 digit typical K 5 F 1 digit maximum LEOPARD LYNX TIGER IT01 LINEARITY ZERO SPAN 272D 24V Exc ON OFF 24V Exc DCmA...

Page 6: ...accept negative signals also and may be scaled for inputs from 50 to 100 of the range selected on the input signal conditioning module Wide range scaling in engineering units not requir ing offsets w...

Page 7: ...ting over range Signal Span is then scaled down by selecting the position of the SPAN RANGE Header and or the SPAN ADJUST Header which will reduce the input Signal Span to a percentage that the requir...

Page 8: ...r Custom Selectable Range CSR SETUP NRC to Set up Custom Selectable Range CSR INSTL Installation of Custom Selectable Range CSS SETUP NRC to Set up Custom Special Scaling CSS BR INSTL Installation of...

Reviews: