TESY CN06 060 EA W Operation And Storage Manual Download Page 5

EN

Operation and Storage Manual of Panel Heater 

     

5

English

any of the buttons:   

 or 

 and confirm with “Mode”   button 

, user 

can enter the time and temperature, when it will automatically go to “Heating” 
mode. Initially a setting of 12 hours is set by default and by pushing 

 

or 

 buttons user can change the time settings in the desired direction. 

After the hour of “delay start” mode is chosen, press “Mode”  

 button for 

confirmation. After that set the temperature at which the convector will start 
operating by pushing of any of buttons:  

 or 

 . Confirm with “Mode”  

button 

. If any of  

 or 

 buttons is held for more than 0.5 seconds, 

the time and temperature settings start automatically increase or decrease at a 
rate of 4 units per second. Confirm with “Mode” button 

 or don’t press any 

button for 3 seconds. 

If user enters time – 00, this mode will not be implemented. If the “Delay start” 
mode is already enabled and user selects the “Delay Start” mode again, it can 
be changed the remaining time in both possible directions. You can exit this 
mode by pushing the “On/Off” 

  button. Then panel heater will go into 

“Heating” mode. The “Delay start” needs to be set from 0 to 96 hours.

 

Visualization on Display in “Delay start” settings 

:

The display shows “Delay start” in the top and the set temperature  

  

 

 

  

Anti-frost mode  

If the room temperature falls below 5°C and the panel heater is off, the heater 
will turn on automatically in order to prevent freezing of the area. Indication – 

 in left top corner   - only when work the anti-frost mode

Factory settings of the function is ON (switched On).

 

Activation and deactivation of Anti-frost mode  

- If the customer wants to change it – push “Mode”  button 

for 3 sec  and 

select “Anti-frost”  mode 

 by pushing any of the buttons: 

 or 

Confirm with “Mode”  button  

and user can push 

 button to reach ‘’OFF”. 

Confirm with “Mode”  button 

.

To activate the function – push “Mode”  button 

  for 3 sec  and select “Anti-

frost” mode 

 by pushing any of the buttons: 

 or 

. Confirm with 

“Mode” button      

. It starts blinking and user has to push 

 button to 

reach ‘’ON’’. Confirm with “Mode”  button 

 .

 

Visualization on Display in “Anti-frost” settings 

:

  

“Temperature correction for the sensor” function 

 

Due to the specifics of the temperature profile in some premises there may 
be difference from the temperature shown on the display and the actually 
measured temperature in the various locations of the heating appliance in the 
room. 

See the temperature shown on the display of the appliance 

Measure the temperature at a place where the temperature is “comfortable” 
enough for you (usually at a height of 60 cm from the floor, in sitting positon). 
If you find a difference within a range of ±4°С, you can set the necessary 
correction in the convector’s menu (It is important to note that this function 
can be set only after the temperature has become the same all around the 
room, and depending on the room type, the minimum required time is 7 

hours) by entering the temperature difference resulting between the value on 
the display and the actually measured temperature. 

 

This function is used with the purpose of providing better temperature 

comfort and energy saving for the user of the electric convector in the room 

which it is in. A temperature difference greater than ±4 °C from the measured 
temperature in a specific location in the room indicates that the room where you 
use the convector in is not well insulated or the temperature is not the same all 
around the room. 

Example

: a convector in a room on a stone floor – the convector displays 18°С 

(the set temperature is 22°С), the actually measured temperature (feeling of 
reached comfort temperature) is 22°С at a height of 60 cm from the floor - > in 
this case the convector continues to overheat the room (this is a direct energy 
loss, but the convector cannot reach the set temperature because it measures the 
temperature at a low height close to the floor) and it will never switch off. In this 
case a temperature correction of +4°С needs to be applied to the sensor, thus the 
convector will display 22°С and it will start switching off, and eventually it will 
maintain the set temperature of 22°С). 

The normal status of the function is 0°C by default

If the customer wants to change it - by pushing “Mode” 

 button for 3 

sec  and select “Temperature correction” 

  mode by pushing any of the 

buttons: 

 or 

 . Confirm with “Mode”  button  

– by pushing  

 

or 

 button user can reach a temperature correction in the diapason from 

‘’-4°C” up to ‘’+4°C”. Confirm with “Mode”   button 

.

If user wants to see the already set correction, should press “Mode”  button 

 for 3 sec and select “Temperature correction” 

  mode by pushing any 

of the buttons:     

 or 

 . Confirm with “Mode”   button 

. User can 

change it by pushing button     

 or 

 to give a new value of correction in 

the diapason ±4°C. Confirm with “Mode”  

 button.

If the factory reset function is used, the temperature correction has to be set 
again. The factory setting of its value is 0°C.

 

Visualization on Display in “Temperature correction” settings 

 :

Function Adaptive start  

Adaptive start is a function which predicts and initiates the optimal start of 
heating in order to reach the set-point temperature at the desired time;

Test according to user instruction / documentation. The function is tested in a room 
with a continuous heat demand of  50 - 60% with reference to the wattage of the 
test device. The product is working at a comfort temperature 23°C ± 3°C setpoint 
until stable conditions. This temperature is the reference comfort temperature “Ct”. 
Activate a set-back period of 7h +2h/-0h per 24h with a set-back of 4°C ± 1°C . The 
comfort period being 17 -2h/+0h hours.  With the adaptive control activated - let 
the heater thermostat working during 4 periods (4 x 24 hours) of comfort and low 
setback cycles. After the latest low setback period finishes the comfort temperature 
“Ct” should be reached within ± 30 minutes deviation to the time target - with a 
maximal difference of ± 1⁰C from the reference comfort temperature “Ct”. 

- Factory settings of the function is ‘’ON” 

 

Deactivation of function Adaptive start 

:

- If the customer wants to change it – by pushing the “Mode”  button 

 for 

3 sec  and select “Adaptive start”  

  mode by pushing any of the buttons:      

 or 

.  Confirm with “Mode”  button 

and user can push 

 button 

to reach ‘’OFF”. Confirm with “Mode”  button 

. In this case, the function 

adaptive start is switched OFF.

 

Activation of function Adaptive start 

:

To return again in condition ‘’ON’’ –  by pushing the “Mode”  button 

 for 

3 sec  and select “Adaptive start”

 mode by pushing any of the buttons:      

 or 

.  Confirm with “Mode” button 

 and user can push 

 button 

to reach ‘’ON”. Confirm with “Mode”  button 

. In this case the function 

Adaptive start is switched ON.

 

Visualization on Display in “Adaptive start” settings 

:

Summary of Contents for CN06 060 EA W

Page 1: ...ltd CN 06 EA CLOUD AS W 230V 50Hz 600 1000 1400 2000W 206403 v1 0 ENELECTRIC PANEL HEATER 2 12 Operation and Storage Manual of Panel Heater BG 13 23 ROCONVECTOR ELECTRIC 24 34 Instruc iuni de utiliza...

Page 2: ...eration only When positioning the appliance do not cover the safety grilles do not hamper the incoming and outgoing air flow All objects must be at a safe distance of at least 1 meter away from the ap...

Page 3: ...not less than 1 meter and it is compulsory the appliance to be wall mounted If you do not feel sure about the installation of this panel heater in a bathroom we recommend you to consult a professional...

Page 4: ...e in Comfort mode User could set the time range for operating in Sleep mode then the appliance switches to Comfort mode By default 6 hours Activation of Sleep mode Push the button Mode for 3 sec and s...

Page 5: ...from the measured temperature in a specific location in the room indicates that the room where you use the convector in is not well insulated or the temperature is not the same all around the room Exa...

Page 6: ...panel remain locked Hold buttons and Mode together for 3 seconds The display should show a message when this mode is activated When user wants to turn off this function has to hold the same button co...

Page 7: ...ecessary the convector to be switched on and heated the set temperature is higher than the ambient temperature When the temperature of the heater rises the natural air flow starts in the room Colder a...

Page 8: ...teed and up to 180 minutes not guaranteed If the time is more than 120 min the appliance going to Stand by mode PROTECTION The appliance is equipped with a safety thermo turn off device which automati...

Page 9: ...lectric appliances contain valuable materials and consequently they should not be treated as domestic waste We ask for your cooperation and your active contribution to protect the resources and the en...

Page 10: ...ion yes With distance control option no With adaptive start control yes With working time limitation no With black bulb sensor no Model identifier s 1 CN06 060 EA AS W 2 CN06 100 EA AS W 3 CN06 140 EA...

Page 11: ...ection yes With distance control option yes With adaptive start control yes With working time limitation no With black bulb sensor no Model identifier s 1 CN06 060 EA CLOUD AS W 2 CN06 100 EA CLOUD AS...

Page 12: ...oid obstructions that may prevent normal air exchange between the appliance and the indoor air Open window door detection is not enabled Switch on open window door detection Adaptive start function do...

Page 13: ...BG 13 3 3 8 3 8 8 a 100 1 100 UVA UVA 45 3 2 1 2 3 1 volume 1 4 2 volume 2 3...

Page 14: ...BG 14 5 HD60364 7 701 IEC 60364 7 701 2006 IP24 2 volume 2 1 3 VOLUME 3 25 3 CN06 1 5 ON OFF ON OFF 1 Mode 1 Mode 3...

Page 15: ...BG 15 1 1 1 23 C Mode 3 Mode 10 30 C Mode On Off 1 5 Mode 1 2 18 C Mode 3 Mode Mode Mode Mode 00 00 24 00 On Off 1 5 Mode 1 3 3 C 6 Mode 3 Mode Mode Mode 00 00 24 00 On Off 1 5 Mode 2...

Page 16: ...1 5 On Off 1 5 0 5 6 10 30 C Mode 3 Mode 12 Mode Mode 0 5 4 Mode 3 00 ON OFF 0 96 5 stand by 5 Mode 3 Mode OFF Mode Mode 3 Mode ON Mode 60 4 7 4 C 18oc 22 22 60 4 22 22 0 C Mode 3 Mode 4 C 4 C Mode M...

Page 17: ...e 0 C 50 60 23 C 3 C Ct 7h 2h 0h 24h 4 C 1 C 17 2h 0h 4 4 24 Ct 30 1 C Ct Mode 3 Mode OFF Mode Mode 3 Mode ON Mode Mode 3 Mode 0 C 5 C 15 0 5 C 5 C 60 Mode 3 Mode OFF Mode Mode 3 Mode ON Mode Mode 3 3...

Page 18: ...7 ON OFF 1 5 ON OFF Mode 3 Mode Mode 1 Mode 2 00 00 24 00 Mode 00 00 24 00 Mode 3 10 30 C Mode 22 C 12 30 15 00 ON OFF 0 5 30 Mode Mode Mode Mode ON OFF AirSafe CN 06 xxx E CLOUD AS W CN 06 xxx E AS...

Page 19: ...e ON Mode Air Safe 2 45 tilt Wi Fi CN 06 xxx EA CLOUD AS W CN 06 xxx EA CLOUD W Wi Fi Mode 3 Wi Fi Mode Wi Fi OFF Mode Mode 6 Wi Fi Mode Wi Fi ON Mode Mode 3 Wi Fi Mode Wi Fi LOCAL Mode Wi Fi 100 5 Mo...

Page 20: ...www tesy com CN 06 060 EA CLOUD AS W 600W 10 23 m3 4 9 m2 CN 06 100 EA CLOUD AS W 1000W 24 33 m3 10 13 m2 CN 06 140 EA CLOUD AS W 1400W 34 45 m3 14 18 m2 CN 06 200 EA CLOUD AS W 2000W 46 65 m3 19 26...

Page 21: ...0 1 00 1 40 2 00 kW elmax 0 57 0 92 1 32 1 93 kW elmin 0 00 0 00 0 00 0 00 kW el SB 0 0002 kW 1 CN06 060 EA AS W 2 CN06 100 EA AS W 3 CN06 140 EA AS W 4 CN06 200 EA AS W 230V 50Hz 1 2 3 4 Pnom 0 60 1...

Page 22: ...1 00 1 40 2 00 kW elmax 0 57 0 92 1 32 1 93 kW elmin 0 00 0 00 0 00 0 00 kW el SB 0 00054 kW 1 CN06 060 EA CLOUD AS W 2 CN06 100 EA CLOUD AS W 3 CN06 140 EA CLOUD AS W 4 CN06 200 EA CLOUD AS W 230V 5...

Page 23: ...BG 23 ON OFF Protection from children 4 100W m2 2 50 m 30W m3 Adaptive start Adaptive start Adaptive start Adaptive start t1 t2 t1 t2...

Page 24: ...it pentru utilizare n cre terea animalelor acesta este destinat numai pentru uz casnic Nu acoperi i grilele de siguran nu bloca i intrarea fluxului de aer prin a ezarea aparatului vizavi de orice supr...

Page 25: ...i unitatea trebuie s fie montat pe perete Dac nu sunte i sigur cu privire la modul de instalare a acestui convector n baie v recomand m s consulta i un electrician profesionist Nota n cazul n care con...

Page 26: ...ratura Pe afi aj apare pictograma modului c i temperatura setat 1 3 Modul Somn cu op iunea On Off la dou ore dup activare convectorul scade temperatura setat cu 3 C comparativ cu cea setat n modul Con...

Page 27: ...pozi ia a ezat n caz de constatare a unei diferen e n diapazonul 4 pute i seta ajustarea necesar din meniul convectorului O condi ie important func ia nu se poate seta numai dup temperarea nc perii ca...

Page 28: ...e 3 secunde i selecta i func ia Fereastr U deschise apas nd butoanele sau i confirma i cu butonul Mod Mode Utilizatorul poate ap sa butonul pentru a atinge ON pornit Confirma i cu butonul Mod Mode n a...

Page 29: ...lzitorul are o intensitate i o energie foarte redus i nu are efecte d un toare asupra oamenilor plantelor i animalelor 3 F r generarea de ozon peroxid de hidrogen molecule organice sau anorganice sau...

Page 30: ...ornire nt rziat Programul s pt m nal Ie ire din fiecare meniu ap s nd o dat butonul ON OFF MODUL DE EROARE Dac pe afi aj apare t1 sau t2 sistemul de autodiagnosticare a detectat o problem n termosenzo...

Page 31: ...lzit minim garantat de nc lzire la un coeficient mediu de conductivitate ter mic 0 5 W m2K pentru nc perea nc lzit La valori ridicate pentru volumul suprafa a nc lzit se realizeaz la o valoare medie...

Page 32: ...i camerei cu detectarea unei ferestre deschise da cu op iune de control la distan nu cu demaraj adaptabil da cu limitarea timpului de func ionare nu cu senzor cu bulb negru nu Identificatorul de model...

Page 33: ...ise da cu op iune de control la distan da cu demaraj adaptabil da cu limitarea timpului de func ionare nu cu senzor cu bulb negru nu Identificatorul de model e 1 CN06 060 EA CLOUD AS W 2 CN06 100 EA C...

Page 34: ...u ideschise necesit o temperatur stabil anterioar stabil Evita i blocajele care pot interfera cu schimbul normal de aer ntre unitate i aerul din camer Func ie de identificare de fereastr u deschis nu...

Page 35: ...RS 35 Djeca manje od tri godine treba osim ako pod nadzorom 3 8 3 8 ure aja 100 1 50 100 22 UVA UVA 45 2 1 2 3 1 volume 1 4 2 volume 2 3...

Page 36: ...RS 36 5 HD60364 7 701 IEC 60364 7 701 2006 IP24 2 volume2 1 3 VOLUME 3 25 3 CN06 1 5 ON OFF ON OFF 1 Mode 1 Mode 3 1 Comfort Eco Sleep 1 1 Comfort 23 C...

Page 37: ...5 Mode Comfort Heating 1 2 Eco 18 C Comfort Eco Mode 3 Mode Mode Mode Mode 00 00 24 00 Comfort Eco On Off 1 5 Mode 1 3 Sleep 3 C Comfort Comfort 6 Sleep Mode 3 Sleep Mode Mode Mode 00 00 24 00 Comfor...

Page 38: ...ode Mode 0 5 4 Mode 3 00 Delayed start Delayed start ON OFF 0 96 Delayed start Anti frost 5 stand by 5 Anti frost Mode 3 Anti frost Mode OFF Mode Mode 3 Anti frost Mode ON Mode Anti frost T C Correcti...

Page 39: ...1 C 17 2h 0h 4 4 24 Ct 30 1 C Ct Mode 3 Mode OFF Mode Mode 3 Mode ON Mode Mode 3 Mode 0 C Open window door 5 C 15 0 5 C 5 C 60 Open window door Mode 3 Mode OFF Mode Mode 3 Mode ON Mode Keyboard lock...

Page 40: ...Mode 3 Mode Mode 1 Mode 2 00 00 24 00 Mode 00 00 24 00 Mode 3 10 30 C Mode 22 C 12 30 15 00 ON OFF 0 5 30 Mode Mode Mode Mode ON OFF Air Safe CN 06 xxx E CLOUD AS W CN 06 xxx E AS W Air Safe Air Safe...

Page 41: ...afe 2 45 tilt Wi Fi CN 06 xxx EA CLOUD AS W CN 06 xxx EA CLOUD W Wi Fi Mode 3 Wi Fi Mode OFF Mode Mode 3 Wi Fi Mode ON Mode Mode 3 Wi Fi Mode Wi Fi LOCAL Mode Wi Fi 100 5 Mode 3 Mode 0 Mode Mode 3 Mod...

Page 42: ...om CN 06 060 EA CLOUD AS W 600W 10 23 m3 4 9 m2 CN 06 100 EA CLOUD AS W 1000W 24 33 m3 10 13 m2 CN 06 140 EA CLOUD AS W 1400W 34 45 m3 14 18 m2 CN 06 200 EA CLOUD AS W 2000W 46 65 m3 19 26 m2 0 5 W m2...

Page 43: ...RS 43 ON OFF Protection from children 4 100W m2 2 50 m 30W m3 Adaptive start Adaptive start Adaptive start Adaptive start t1 t2 t1 t2...

Page 44: ...TESY Ltd Head office 1166 Sofia Sofia Park Building 16V 2nd Floor PHONE 359 2 902 6666 FAX 359 2 902 6660 office tesy com 206403_001...

Reviews: