4 Transmitter
68
NC contact
Monitoring minimum
Monitoring maximum
Hysteresis
Hysteresis
Limit value
Limit value
3.
Select
Channel x
(e.g. "Channel 1") with
X
or
S
and confirm
selection with
SET
.
4.
Select
Max control
or
Min control
with
X
or
S
(see graphic).
5.
Press
SET
and edit
Limit value
as well as
Hysteresis
: Scroll
one digit to the right using
X
and increase value of digit by 1
using
S
. Confirm with
SET
or abort entry with
ESC
.
6.
Select
Visual alarm
with
X
or
S
. Select
YES
or
NO
with
X
or
S
. Confirm with
SET
or abort entry with
ESC
.
7.
Press
SET
and edit
Alarm delay
: Scroll one digit to the right
using
X
and increase value of digit by 1 using
S
(0 to 240
seconds possible). Confirm with
SET
or abort entry with
ESC
.
8.
Return to
Channel x
with
ESC
.
9.
Return to
Alarm x
with
ESC
.
10.
Change to the other relays using
X
or
S
and perform settings
in the same way.
Using alarm as collective alarm or not using it at all
If an alarm is assigned to the collective alarm, the relay is switched
and a visual alarm can be issued via the display as soon as (at
least) one of the warning or error messages of the testo 6381
transmitter (or the connected testo 6610 probe) becomes active.
The messages affecting the collective alarm can only be
selected in the P2A software, see volume 2, Using the
software, page 131
✓
Alarm is selected (see previous steps 1 and 2).
1.
Use
X
or
S
to determine whether
Alarm x
should be used as a
Collective alarm
or
not used
. Confirm selection with
SET
.
2.
If collective alarm is selected: Select
Visual alarm
with
X
or
S
.
Select
YES
or
NO
with
X
or
S
. Confirm with
SET
and return to
Alarm x
.